diff --git a/alarm-01.tn.esss.lu.se/F04.xml b/alarm-01.tn.esss.lu.se/F04.xml index 256926768f0fb270cf0247ca86ca2997f91bc91f..e11439362ffb389bf48fb0ca48bbf66a57eea677 100644 --- a/alarm-01.tn.esss.lu.se/F04.xml +++ b/alarm-01.tn.esss.lu.se/F04.xml @@ -30,12 +30,25 @@ If confirmed fire 112 is called</details> <annunciating>true</annunciating> <guidance> <title>[Gate Guard Action]</title> - <details>Call out First Responders + <details>Check OpenBrkrPwrLineAlrm, then possibly call out First Responders +This alarm is known to occur spuriously. If OpenBrkrPwrLineAlrm also occurs, treat as a real smoke alarm, otherwise inform MCR. +If real smoke alarm: First Responders to investigate and will determine if it is a confirmed fire If an additional building alarm then it is considered a confirmed fire If confirmed fire 112 is called</details> </guidance> </pv> + <pv name="Spk-010RFC:RFS-RFPS-010:OpenBrkrPwrLineAlrm"> + <description>Power breaker is open in Spk-010RFC:RFS-RFPS-010. It is located at STUB 120</description> + <latching>true</latching> + <annunciating>true</annunciating> + <guidance> + <title>[Gate Guard Action]</title> + <details>Check for smoke alarms +If the machine is in maintenance and no active smoke alarms, no action. +If the machine is in production or there are any active smoke alarms, call the first responder team</details> + </guidance> + </pv> <pv name="Spk-010RFC:RFS-RFPS-020:SolidStateRackSmokeAlrm"> <description>Smoke is detected in RF Power Station Spk-010RFC:RFS-RFPS-020. It is located at STUB 120. It has been turned OFF</description> <latching>true</latching> @@ -66,12 +79,25 @@ If confirmed fire 112 is called</details> <annunciating>true</annunciating> <guidance> <title>[Gate Guard Action]</title> - <details>Call out First Responders + <details>Check OpenBrkrPwrLineAlrm, then possibly call out First Responders +This alarm is known to occur spuriously. If OpenBrkrPwrLineAlrm also occurs, treat as a real smoke alarm, otherwise inform MCR. +If real smoke alarm: First Responders to investigate and will determine if it is a confirmed fire If an additional building alarm then it is considered a confirmed fire If confirmed fire 112 is called</details> </guidance> </pv> + <pv name="Spk-010RFC:RFS-RFPS-020:OpenBrkrPwrLineAlrm"> + <description>Power breaker is open in Spk-010RFC:RFS-RFPS-020. It is located at STUB 120</description> + <latching>true</latching> + <annunciating>true</annunciating> + <guidance> + <title>[Gate Guard Action]</title> + <details>Check for smoke alarms +If the machine is in maintenance and no active smoke alarms, no action. +If the machine is in production or there are any active smoke alarms, call the first responder team</details> + </guidance> + </pv> <pv name="Spk-020RFC:RFS-RFPS-010:SolidStateRackSmokeAlrm"> <description>Smoke is detected in RF Power Station Spk-020RFC:RFS-RFPS-010. It is located at STUB 120. It has been turned OFF</description> <latching>true</latching> @@ -102,12 +128,25 @@ If confirmed fire 112 is called</details> <annunciating>true</annunciating> <guidance> <title>[Gate Guard Action]</title> - <details>Call out First Responders + <details>Check OpenBrkrPwrLineAlrm, then possibly call out First Responders +This alarm is known to occur spuriously. If OpenBrkrPwrLineAlrm also occurs, treat as a real smoke alarm, otherwise inform MCR. +If real smoke alarm: First Responders to investigate and will determine if it is a confirmed fire If an additional building alarm then it is considered a confirmed fire If confirmed fire 112 is called</details> </guidance> </pv> + <pv name="Spk-020RFC:RFS-RFPS-010:OpenBrkrPwrLineAlrm"> + <description>Power breaker is open in Spk-020RFC:RFS-RFPS-010. It is located at STUB 120</description> + <latching>true</latching> + <annunciating>true</annunciating> + <guidance> + <title>[Gate Guard Action]</title> + <details>Check for smoke alarms +If the machine is in maintenance and no active smoke alarms, no action. +If the machine is in production or there are any active smoke alarms, call the first responder team</details> + </guidance> + </pv> <pv name="Spk-020RFC:RFS-RFPS-020:SolidStateRackSmokeAlrm"> <description>Smoke is detected in RF Power Station Spk-020RFC:RFS-RFPS-020. It is located at STUB 120. It has been turned OFF</description> <latching>true</latching> @@ -138,12 +177,25 @@ If confirmed fire 112 is called</details> <annunciating>true</annunciating> <guidance> <title>[Gate Guard Action]</title> - <details>Call out First Responders + <details>Check OpenBrkrPwrLineAlrm, then possibly call out First Responders +This alarm is known to occur spuriously. If OpenBrkrPwrLineAlrm also occurs, treat as a real smoke alarm, otherwise inform MCR. +If real smoke alarm: First Responders to investigate and will determine if it is a confirmed fire If an additional building alarm then it is considered a confirmed fire If confirmed fire 112 is called</details> </guidance> </pv> + <pv name="Spk-020RFC:RFS-RFPS-020:OpenBrkrPwrLineAlrm"> + <description>Power breaker is open in Spk-020RFC:RFS-RFPS-020. It is located at STUB 120</description> + <latching>true</latching> + <annunciating>true</annunciating> + <guidance> + <title>[Gate Guard Action]</title> + <details>Check for smoke alarms +If the machine is in maintenance and no active smoke alarms, no action. +If the machine is in production or there are any active smoke alarms, call the first responder team</details> + </guidance> + </pv> <pv name="Spk-030RFC:RFS-RFPS-010:SolidStateRackSmokeAlrm"> <description>Smoke is detected in RF Power Station Spk-030RFC:RFS-RFPS-010. It is located at STUB 120. It has been turned OFF</description> <latching>true</latching> @@ -172,14 +224,27 @@ If confirmed fire 112 is called</details> <description>Smoke is detected in RF Power Station Spk-030RFC:RFS-RFPS-010. It is located at STUB 120. It has been turned OFF</description> <latching>true</latching> <annunciating>true</annunciating> - <guidance> + <guidance> <title>[Gate Guard Action]</title> - <details>Call out First Responders + <details>Check OpenBrkrPwrLineAlrm, then possibly call out First Responders +This alarm is known to occur spuriously. If OpenBrkrPwrLineAlrm also occurs, treat as a real smoke alarm, otherwise inform MCR. +If real smoke alarm: First Responders to investigate and will determine if it is a confirmed fire If an additional building alarm then it is considered a confirmed fire If confirmed fire 112 is called</details> </guidance> </pv> + <pv name="Spk-030RFC:RFS-RFPS-010:OpenBrkrPwrLineAlrm"> + <description>Power breaker is open in Spk-030RFC:RFS-RFPS-010. It is located at STUB 120</description> + <latching>true</latching> + <annunciating>true</annunciating> + <guidance> + <title>[Gate Guard Action]</title> + <details>Check for smoke alarms +If the machine is in maintenance and no active smoke alarms, no action. +If the machine is in production or there are any active smoke alarms, call the first responder team</details> + </guidance> + </pv> <pv name="Spk-030RFC:RFS-RFPS-020:SolidStateRackSmokeAlrm"> <description>Smoke is detected in RF Power Station Spk-030RFC:RFS-RFPS-020. It is located at STUB 120. It has been turned OFF</description> <latching>true</latching> @@ -210,12 +275,25 @@ If confirmed fire 112 is called</details> <annunciating>true</annunciating> <guidance> <title>[Gate Guard Action]</title> - <details>Call out First Responders + <details>Check OpenBrkrPwrLineAlrm, then possibly call out First Responders +This alarm is known to occur spuriously. If OpenBrkrPwrLineAlrm also occurs, treat as a real smoke alarm, otherwise inform MCR. +If real smoke alarm: First Responders to investigate and will determine if it is a confirmed fire If an additional building alarm then it is considered a confirmed fire If confirmed fire 112 is called</details> </guidance> </pv> + <pv name="Spk-030RFC:RFS-RFPS-020:OpenBrkrPwrLineAlrm"> + <description>Power breaker is open in Spk-030RFC:RFS-RFPS-020. It is located at STUB 120</description> + <latching>true</latching> + <annunciating>true</annunciating> + <guidance> + <title>[Gate Guard Action]</title> + <details>Check for smoke alarms +If the machine is in maintenance and no active smoke alarms, no action. +If the machine is in production or there are any active smoke alarms, call the first responder team</details> + </guidance> + </pv> <pv name="Spk-040RFC:RFS-RFPS-010:SolidStateRackSmokeAlrm"> <description>Smoke is detected in RF Power Station Spk-040RFC:RFS-RFPS-010. It is located at STUB 120. It has been turned OFF</description> <latching>true</latching> @@ -246,12 +324,25 @@ If confirmed fire 112 is called</details> <annunciating>true</annunciating> <guidance> <title>[Gate Guard Action]</title> - <details>Call out First Responders + <details>Check OpenBrkrPwrLineAlrm, then possibly call out First Responders +This alarm is known to occur spuriously. If OpenBrkrPwrLineAlrm also occurs, treat as a real smoke alarm, otherwise inform MCR. +If real smoke alarm: First Responders to investigate and will determine if it is a confirmed fire If an additional building alarm then it is considered a confirmed fire If confirmed fire 112 is called</details> </guidance> </pv> + <pv name="Spk-040RFC:RFS-RFPS-010:OpenBrkrPwrLineAlrm"> + <description>Power breaker is open in Spk-040RFC:RFS-RFPS-010. It is located at STUB 120</description> + <latching>true</latching> + <annunciating>true</annunciating> + <guidance> + <title>[Gate Guard Action]</title> + <details>Check for smoke alarms +If the machine is in maintenance and no active smoke alarms, no action. +If the machine is in production or there are any active smoke alarms, call the first responder team</details> + </guidance> + </pv> <pv name="Spk-040RFC:RFS-RFPS-020:SolidStateRackSmokeAlrm"> <description>Smoke is detected in RF Power Station Spk-040RFC:RFS-RFPS-020. It is located at STUB 120. It has been turned OFF</description> <latching>true</latching> @@ -282,12 +373,25 @@ If confirmed fire 112 is called</details> <annunciating>true</annunciating> <guidance> <title>[Gate Guard Action]</title> - <details>Call out First Responders + <details>Check OpenBrkrPwrLineAlrm, then possibly call out First Responders +This alarm is known to occur spuriously. If OpenBrkrPwrLineAlrm also occurs, treat as a real smoke alarm, otherwise inform MCR. +If real smoke alarm: First Responders to investigate and will determine if it is a confirmed fire If an additional building alarm then it is considered a confirmed fire If confirmed fire 112 is called</details> </guidance> </pv> + <pv name="Spk-040RFC:RFS-RFPS-020:OpenBrkrPwrLineAlrm"> + <description>Power breaker is open in Spk-040RFC:RFS-RFPS-020. It is located at STUB 120</description> + <latching>true</latching> + <annunciating>true</annunciating> + <guidance> + <title>[Gate Guard Action]</title> + <details>Check for smoke alarms +If the machine is in maintenance and no active smoke alarms, no action. +If the machine is in production or there are any active smoke alarms, call the first responder team</details> + </guidance> + </pv> <pv name="Spk-050RFC:RFS-RFPS-010:SolidStateRackSmokeAlrm"> <description>Smoke is detected in RF Power Station Spk-050RFC:RFS-RFPS-010. It is located at STUB 130. It has been turned OFF</description> <latching>true</latching> @@ -318,12 +422,25 @@ If confirmed fire 112 is called</details> <annunciating>true</annunciating> <guidance> <title>[Gate Guard Action]</title> - <details>Call out First Responders + <details>Check OpenBrkrPwrLineAlrm, then possibly call out First Responders +This alarm is known to occur spuriously. If OpenBrkrPwrLineAlrm also occurs, treat as a real smoke alarm, otherwise inform MCR. +If real smoke alarm: First Responders to investigate and will determine if it is a confirmed fire If an additional building alarm then it is considered a confirmed fire If confirmed fire 112 is called</details> </guidance> </pv> + <pv name="Spk-050RFC:RFS-RFPS-010:OpenBrkrPwrLineAlrm"> + <description>Power breaker is open in Spk-050RFC:RFS-RFPS-010. It is located at STUB 130</description> + <latching>true</latching> + <annunciating>true</annunciating> + <guidance> + <title>[Gate Guard Action]</title> + <details>Check for smoke alarms +If the machine is in maintenance and no active smoke alarms, no action. +If the machine is in production or there are any active smoke alarms, call the first responder team</details> + </guidance> + </pv> <pv name="Spk-050RFC:RFS-RFPS-020:SolidStateRackSmokeAlrm"> <description>Smoke is detected in RF Power Station Spk-050RFC:RFS-RFPS-020. It is located at STUB 130. It has been turned OFF</description> <latching>true</latching> @@ -352,14 +469,27 @@ If confirmed fire 112 is called</details> <description>Smoke is detected in RF Power Station Spk-050RFC:RFS-RFPS-020. It is located at STUB 130. It has been turned OFF</description> <latching>true</latching> <annunciating>true</annunciating> - <guidance> + <guidance> <title>[Gate Guard Action]</title> - <details>Call out First Responders + <details>Check OpenBrkrPwrLineAlrm, then possibly call out First Responders +This alarm is known to occur spuriously. If OpenBrkrPwrLineAlrm also occurs, treat as a real smoke alarm, otherwise inform MCR. +If real smoke alarm: First Responders to investigate and will determine if it is a confirmed fire If an additional building alarm then it is considered a confirmed fire If confirmed fire 112 is called</details> </guidance> </pv> + <pv name="Spk-050RFC:RFS-RFPS-020:OpenBrkrPwrLineAlrm"> + <description>Power breaker is open in Spk-050RFC:RFS-RFPS-020. It is located at STUB 130</description> + <latching>true</latching> + <annunciating>true</annunciating> + <guidance> + <title>[Gate Guard Action]</title> + <details>Check for smoke alarms +If the machine is in maintenance and no active smoke alarms, no action. +If the machine is in production or there are any active smoke alarms, call the first responder team</details> + </guidance> + </pv> <pv name="Spk-060RFC:RFS-RFPS-010:SolidStateRackSmokeAlrm"> <description>Smoke is detected in RF Power Station Spk-060RFC:RFS-RFPS-010. It is located at STUB 130. It has been turned OFF</description> <latching>true</latching> @@ -390,12 +520,25 @@ If confirmed fire 112 is called</details> <annunciating>true</annunciating> <guidance> <title>[Gate Guard Action]</title> - <details>Call out First Responders + <details>Check OpenBrkrPwrLineAlrm, then possibly call out First Responders +This alarm is known to occur spuriously. If OpenBrkrPwrLineAlrm also occurs, treat as a real smoke alarm, otherwise inform MCR. +If real smoke alarm: First Responders to investigate and will determine if it is a confirmed fire If an additional building alarm then it is considered a confirmed fire If confirmed fire 112 is called</details> </guidance> </pv> + <pv name="Spk-060RFC:RFS-RFPS-010:OpenBrkrPwrLineAlrm"> + <description>Power breaker is open in Spk-060RFC:RFS-RFPS-010. It is located at STUB 130</description> + <latching>true</latching> + <annunciating>true</annunciating> + <guidance> + <title>[Gate Guard Action]</title> + <details>Check for smoke alarms +If the machine is in maintenance and no active smoke alarms, no action. +If the machine is in production or there are any active smoke alarms, call the first responder team</details> + </guidance> + </pv> <pv name="Spk-060RFC:RFS-RFPS-020:SolidStateRackSmokeAlrm"> <description>Smoke is detected in RF Power Station Spk-060RFC:RFS-RFPS-020. It is located at STUB 130. It has been turned OFF</description> <latching>true</latching> @@ -426,12 +569,25 @@ If confirmed fire 112 is called</details> <annunciating>true</annunciating> <guidance> <title>[Gate Guard Action]</title> - <details>Call out First Responders + <details>Check OpenBrkrPwrLineAlrm, then possibly call out First Responders +This alarm is known to occur spuriously. If OpenBrkrPwrLineAlrm also occurs, treat as a real smoke alarm, otherwise inform MCR. +If real smoke alarm: First Responders to investigate and will determine if it is a confirmed fire If an additional building alarm then it is considered a confirmed fire If confirmed fire 112 is called</details> </guidance> </pv> + <pv name="Spk-060RFC:RFS-RFPS-020:OpenBrkrPwrLineAlrm"> + <description>Power breaker is open in Spk-060RFC:RFS-RFPS-020. It is located at STUB 130</description> + <latching>true</latching> + <annunciating>true</annunciating> + <guidance> + <title>[Gate Guard Action]</title> + <details>Check for smoke alarms +If the machine is in maintenance and no active smoke alarms, no action. +If the machine is in production or there are any active smoke alarms, call the first responder team</details> + </guidance> + </pv> <pv name="Spk-070RFC:RFS-RFPS-010:SolidStateRackSmokeAlrm"> <description>Smoke is detected in RF Power Station Spk-070RFC:RFS-RFPS-010. It is located at STUB 130. It has been turned OFF</description> <latching>true</latching> @@ -462,12 +618,25 @@ If confirmed fire 112 is called</details> <annunciating>true</annunciating> <guidance> <title>[Gate Guard Action]</title> - <details>Call out First Responders + <details>Check OpenBrkrPwrLineAlrm, then possibly call out First Responders +This alarm is known to occur spuriously. If OpenBrkrPwrLineAlrm also occurs, treat as a real smoke alarm, otherwise inform MCR. +If real smoke alarm: First Responders to investigate and will determine if it is a confirmed fire If an additional building alarm then it is considered a confirmed fire If confirmed fire 112 is called</details> </guidance> </pv> + <pv name="Spk-070RFC:RFS-RFPS-010:OpenBrkrPwrLineAlrm"> + <description>Power breaker is open in Spk-070RFC:RFS-RFPS-010. It is located at STUB 130</description> + <latching>true</latching> + <annunciating>true</annunciating> + <guidance> + <title>[Gate Guard Action]</title> + <details>Check for smoke alarms +If the machine is in maintenance and no active smoke alarms, no action. +If the machine is in production or there are any active smoke alarms, call the first responder team</details> + </guidance> + </pv> <pv name="Spk-070RFC:RFS-RFPS-020:SolidStateRackSmokeAlrm"> <description>Smoke is detected in RF Power Station Spk-070RFC:RFS-RFPS-020. It is located at STUB 130. It has been turned OFF</description> <latching>true</latching> @@ -498,12 +667,25 @@ If confirmed fire 112 is called</details> <annunciating>true</annunciating> <guidance> <title>[Gate Guard Action]</title> - <details>Call out First Responders + <details>Check OpenBrkrPwrLineAlrm, then possibly call out First Responders +This alarm is known to occur spuriously. If OpenBrkrPwrLineAlrm also occurs, treat as a real smoke alarm, otherwise inform MCR. +If real smoke alarm: First Responders to investigate and will determine if it is a confirmed fire If an additional building alarm then it is considered a confirmed fire If confirmed fire 112 is called</details> </guidance> </pv> + <pv name="Spk-070RFC:RFS-RFPS-020:OpenBrkrPwrLineAlrm"> + <description>Power breaker is open in Spk-070RFC:RFS-RFPS-020. It is located at STUB 130</description> + <latching>true</latching> + <annunciating>true</annunciating> + <guidance> + <title>[Gate Guard Action]</title> + <details>Check for smoke alarms +If the machine is in maintenance and no active smoke alarms, no action. +If the machine is in production or there are any active smoke alarms, call the first responder team</details> + </guidance> + </pv> <pv name="Spk-080RFC:RFS-RFPS-010:SolidStateRackSmokeAlrm"> <description>Smoke is detected in RF Power Station Spk-080RFC:RFS-RFPS-010. It is located at STUB 130. It has been turned OFF</description> <latching>true</latching> @@ -534,12 +716,25 @@ If confirmed fire 112 is called</details> <annunciating>true</annunciating> <guidance> <title>[Gate Guard Action]</title> - <details>Call out First Responders + <details>Check OpenBrkrPwrLineAlrm, then possibly call out First Responders +This alarm is known to occur spuriously. If OpenBrkrPwrLineAlrm also occurs, treat as a real smoke alarm, otherwise inform MCR. +If real smoke alarm: First Responders to investigate and will determine if it is a confirmed fire If an additional building alarm then it is considered a confirmed fire If confirmed fire 112 is called</details> </guidance> </pv> + <pv name="Spk-080RFC:RFS-RFPS-010:OpenBrkrPwrLineAlrm"> + <description>Power breaker is open in Spk-080RFC:RFS-RFPS-010. It is located at STUB 130</description> + <latching>true</latching> + <annunciating>true</annunciating> + <guidance> + <title>[Gate Guard Action]</title> + <details>Check for smoke alarms +If the machine is in maintenance and no active smoke alarms, no action. +If the machine is in production or there are any active smoke alarms, call the first responder team</details> + </guidance> + </pv> <pv name="Spk-080RFC:RFS-RFPS-020:SolidStateRackSmokeAlrm"> <description>Smoke is detected in RF Power Station Spk-080RFC:RFS-RFPS-020. It is located at STUB 130. It has been turned OFF</description> <latching>true</latching> @@ -570,12 +765,25 @@ If confirmed fire 112 is called</details> <annunciating>true</annunciating> <guidance> <title>[Gate Guard Action]</title> - <details>Call out First Responders + <details>Check OpenBrkrPwrLineAlrm, then possibly call out First Responders +This alarm is known to occur spuriously. If OpenBrkrPwrLineAlrm also occurs, treat as a real smoke alarm, otherwise inform MCR. +If real smoke alarm: First Responders to investigate and will determine if it is a confirmed fire If an additional building alarm then it is considered a confirmed fire If confirmed fire 112 is called</details> </guidance> </pv> + <pv name="Spk-080RFC:RFS-RFPS-020:OpenBrkrPwrLineAlrm"> + <description>Power breaker is open in Spk-080RFC:RFS-RFPS-020. It is located at STUB 130</description> + <latching>true</latching> + <annunciating>true</annunciating> + <guidance> + <title>[Gate Guard Action]</title> + <details>Check for smoke alarms +If the machine is in maintenance and no active smoke alarms, no action. +If the machine is in production or there are any active smoke alarms, call the first responder team</details> + </guidance> + </pv> <pv name="Spk-090RFC:RFS-RFPS-010:SolidStateRackSmokeAlrm"> <description>Smoke is detected in RF Power Station Spk-090RFC:RFS-RFPS-010. It is located at STUB 140. It has been turned OFF</description> <latching>true</latching> @@ -606,12 +814,25 @@ If confirmed fire 112 is called</details> <annunciating>true</annunciating> <guidance> <title>[Gate Guard Action]</title> - <details>Call out First Responders + <details>Check OpenBrkrPwrLineAlrm, then possibly call out First Responders +This alarm is known to occur spuriously. If OpenBrkrPwrLineAlrm also occurs, treat as a real smoke alarm, otherwise inform MCR. +If real smoke alarm: First Responders to investigate and will determine if it is a confirmed fire If an additional building alarm then it is considered a confirmed fire If confirmed fire 112 is called</details> </guidance> </pv> + <pv name="Spk-090RFC:RFS-RFPS-010:OpenBrkrPwrLineAlrm"> + <description>Power breaker is open in Spk-090RFC:RFS-RFPS-010. It is located at STUB 140</description> + <latching>true</latching> + <annunciating>true</annunciating> + <guidance> + <title>[Gate Guard Action]</title> + <details>Check for smoke alarms +If the machine is in maintenance and no active smoke alarms, no action. +If the machine is in production or there are any active smoke alarms, call the first responder team</details> + </guidance> + </pv> <pv name="Spk-090RFC:RFS-RFPS-020:SolidStateRackSmokeAlrm"> <description>Smoke is detected in RF Power Station Spk-090RFC:RFS-RFPS-020. It is located at STUB 140. It has been turned OFF</description> <latching>true</latching> @@ -640,14 +861,27 @@ If confirmed fire 112 is called</details> <description>Smoke is detected in RF Power Station Spk-090RFC:RFS-RFPS-020. It is located at STUB 140. It has been turned OFF</description> <latching>true</latching> <annunciating>true</annunciating> - <guidance> + <guidance> <title>[Gate Guard Action]</title> - <details>Call out First Responders + <details>Check OpenBrkrPwrLineAlrm, then possibly call out First Responders +This alarm is known to occur spuriously. If OpenBrkrPwrLineAlrm also occurs, treat as a real smoke alarm, otherwise inform MCR. +If real smoke alarm: First Responders to investigate and will determine if it is a confirmed fire If an additional building alarm then it is considered a confirmed fire If confirmed fire 112 is called</details> </guidance> </pv> + <pv name="Spk-090RFC:RFS-RFPS-020:OpenBrkrPwrLineAlrm"> + <description>Power breaker is open in Spk-090RFC:RFS-RFPS-020. It is located at STUB 140</description> + <latching>true</latching> + <annunciating>true</annunciating> + <guidance> + <title>[Gate Guard Action]</title> + <details>Check for smoke alarms +If the machine is in maintenance and no active smoke alarms, no action. +If the machine is in production or there are any active smoke alarms, call the first responder team</details> + </guidance> + </pv> <pv name="Spk-100RFC:RFS-RFPS-010:SolidStateRackSmokeAlrm"> <description>Smoke is detected in RF Power Station Spk-100RFC:RFS-RFPS-010. It is located at STUB 140. It has been turned OFF</description> <latching>true</latching> @@ -678,12 +912,25 @@ If confirmed fire 112 is called</details> <annunciating>true</annunciating> <guidance> <title>[Gate Guard Action]</title> - <details>Call out First Responders + <details>Check OpenBrkrPwrLineAlrm, then possibly call out First Responders +This alarm is known to occur spuriously. If OpenBrkrPwrLineAlrm also occurs, treat as a real smoke alarm, otherwise inform MCR. +If real smoke alarm: First Responders to investigate and will determine if it is a confirmed fire If an additional building alarm then it is considered a confirmed fire If confirmed fire 112 is called</details> </guidance> </pv> + <pv name="Spk-100RFC:RFS-RFPS-010:OpenBrkrPwrLineAlrm"> + <description>Power breaker is open in Spk-100RFC:RFS-RFPS-010. It is located at STUB 140</description> + <latching>true</latching> + <annunciating>true</annunciating> + <guidance> + <title>[Gate Guard Action]</title> + <details>Check for smoke alarms +If the machine is in maintenance and no active smoke alarms, no action. +If the machine is in production or there are any active smoke alarms, call the first responder team</details> + </guidance> + </pv> <pv name="Spk-100RFC:RFS-RFPS-020:SolidStateRackSmokeAlrm"> <description>Smoke is detected in RF Power Station Spk-100RFC:RFS-RFPS-020. It is located at STUB 140. It has been turned OFF</description> <latching>true</latching> @@ -714,12 +961,25 @@ If confirmed fire 112 is called</details> <annunciating>true</annunciating> <guidance> <title>[Gate Guard Action]</title> - <details>Call out First Responders + <details>Check OpenBrkrPwrLineAlrm, then possibly call out First Responders +This alarm is known to occur spuriously. If OpenBrkrPwrLineAlrm also occurs, treat as a real smoke alarm, otherwise inform MCR. +If real smoke alarm: First Responders to investigate and will determine if it is a confirmed fire If an additional building alarm then it is considered a confirmed fire If confirmed fire 112 is called</details> </guidance> </pv> + <pv name="Spk-100RFC:RFS-RFPS-020:OpenBrkrPwrLineAlrm"> + <description>Power breaker is open in Spk-100RFC:RFS-RFPS-020. It is located at STUB 140</description> + <latching>true</latching> + <annunciating>true</annunciating> + <guidance> + <title>[Gate Guard Action]</title> + <details>Check for smoke alarms +If the machine is in maintenance and no active smoke alarms, no action. +If the machine is in production or there are any active smoke alarms, call the first responder team</details> + </guidance> + </pv> <pv name="Spk-110RFC:RFS-RFPS-010:SolidStateRackSmokeAlrm"> <description>Smoke is detected in RF Power Station Spk-110RFC:RFS-RFPS-010. It is located at STUB 140. It has been turned OFF</description> <latching>true</latching> @@ -750,12 +1010,25 @@ If confirmed fire 112 is called</details> <annunciating>true</annunciating> <guidance> <title>[Gate Guard Action]</title> - <details>Call out First Responders + <details>Check OpenBrkrPwrLineAlrm, then possibly call out First Responders +This alarm is known to occur spuriously. If OpenBrkrPwrLineAlrm also occurs, treat as a real smoke alarm, otherwise inform MCR. +If real smoke alarm: First Responders to investigate and will determine if it is a confirmed fire If an additional building alarm then it is considered a confirmed fire If confirmed fire 112 is called</details> </guidance> </pv> + <pv name="Spk-110RFC:RFS-RFPS-010:OpenBrkrPwrLineAlrm"> + <description>Power breaker is open in Spk-110RFC:RFS-RFPS-010. It is located at STUB 140</description> + <latching>true</latching> + <annunciating>true</annunciating> + <guidance> + <title>[Gate Guard Action]</title> + <details>Check for smoke alarms +If the machine is in maintenance and no active smoke alarms, no action. +If the machine is in production or there are any active smoke alarms, call the first responder team</details> + </guidance> + </pv> <pv name="Spk-110RFC:RFS-RFPS-020:SolidStateRackSmokeAlrm"> <description>Smoke is detected in RF Power Station Spk-110RFC:RFS-RFPS-020. It is located at STUB 140. It has been turned OFF</description> <latching>true</latching> @@ -786,12 +1059,25 @@ If confirmed fire 112 is called</details> <annunciating>true</annunciating> <guidance> <title>[Gate Guard Action]</title> - <details>Call out First Responders + <details>Check OpenBrkrPwrLineAlrm, then possibly call out First Responders +This alarm is known to occur spuriously. If OpenBrkrPwrLineAlrm also occurs, treat as a real smoke alarm, otherwise inform MCR. +If real smoke alarm: First Responders to investigate and will determine if it is a confirmed fire If an additional building alarm then it is considered a confirmed fire If confirmed fire 112 is called</details> </guidance> </pv> + <pv name="Spk-110RFC:RFS-RFPS-020:OpenBrkrPwrLineAlrm"> + <description>Power breaker is open in Spk-110RFC:RFS-RFPS-020. It is located at STUB 140</description> + <latching>true</latching> + <annunciating>true</annunciating> + <guidance> + <title>[Gate Guard Action]</title> + <details>Check for smoke alarms +If the machine is in maintenance and no active smoke alarms, no action. +If the machine is in production or there are any active smoke alarms, call the first responder team</details> + </guidance> + </pv> <pv name="Spk-120RFC:RFS-RFPS-010:SolidStateRackSmokeAlrm"> <description>Smoke is detected in RF Power Station Spk-120RFC:RFS-RFPS-010. It is located at STUB 140. It has been turned OFF</description> <latching>true</latching> @@ -822,12 +1108,25 @@ If confirmed fire 112 is called</details> <annunciating>true</annunciating> <guidance> <title>[Gate Guard Action]</title> - <details>Call out First Responders + <details>Check OpenBrkrPwrLineAlrm, then possibly call out First Responders +This alarm is known to occur spuriously. If OpenBrkrPwrLineAlrm also occurs, treat as a real smoke alarm, otherwise inform MCR. +If real smoke alarm: First Responders to investigate and will determine if it is a confirmed fire If an additional building alarm then it is considered a confirmed fire If confirmed fire 112 is called</details> </guidance> </pv> + <pv name="Spk-120RFC:RFS-RFPS-010:OpenBrkrPwrLineAlrm"> + <description>Power breaker is open in Spk-120RFC:RFS-RFPS-010. It is located at STUB 140</description> + <latching>true</latching> + <annunciating>true</annunciating> + <guidance> + <title>[Gate Guard Action]</title> + <details>Check for smoke alarms +If the machine is in maintenance and no active smoke alarms, no action. +If the machine is in production or there are any active smoke alarms, call the first responder team</details> + </guidance> + </pv> <pv name="Spk-120RFC:RFS-RFPS-020:SolidStateRackSmokeAlrm"> <description>Smoke is detected in RF Power Station Spk-120RFC:RFS-RFPS-020. It is located at STUB 140. It has been turned OFF</description> <latching>true</latching> @@ -856,14 +1155,27 @@ If confirmed fire 112 is called</details> <description>Smoke is detected in RF Power Station Spk-120RFC:RFS-RFPS-020. It is located at STUB 140. It has been turned OFF</description> <latching>true</latching> <annunciating>true</annunciating> - <guidance> + <guidance> <title>[Gate Guard Action]</title> - <details>Call out First Responders + <details>Check OpenBrkrPwrLineAlrm, then possibly call out First Responders +This alarm is known to occur spuriously. If OpenBrkrPwrLineAlrm also occurs, treat as a real smoke alarm, otherwise inform MCR. +If real smoke alarm: First Responders to investigate and will determine if it is a confirmed fire If an additional building alarm then it is considered a confirmed fire If confirmed fire 112 is called</details> </guidance> </pv> + <pv name="Spk-120RFC:RFS-RFPS-020:OpenBrkrPwrLineAlrm"> + <description>Power breaker is open in Spk-120RFC:RFS-RFPS-020. It is located at STUB 140</description> + <latching>true</latching> + <annunciating>true</annunciating> + <guidance> + <title>[Gate Guard Action]</title> + <details>Check for smoke alarms +If the machine is in maintenance and no active smoke alarms, no action. +If the machine is in production or there are any active smoke alarms, call the first responder team</details> + </guidance> + </pv> <pv name="Spk-130RFC:RFS-RFPS-010:SolidStateRackSmokeAlrm"> <description>Smoke is detected in RF Power Station Spk-130RFC:RFS-RFPS-010. It is located at STUB 150. It has been turned OFF</description> <latching>true</latching> @@ -892,14 +1204,27 @@ If confirmed fire 112 is called</details> <description>Smoke is detected in RF Power Station Spk-130RFC:RFS-RFPS-010. It is located at STUB 150. It has been turned OFF</description> <latching>true</latching> <annunciating>true</annunciating> - <guidance> + <guidance> <title>[Gate Guard Action]</title> - <details>Call out First Responders + <details>Check OpenBrkrPwrLineAlrm, then possibly call out First Responders +This alarm is known to occur spuriously. If OpenBrkrPwrLineAlrm also occurs, treat as a real smoke alarm, otherwise inform MCR. +If real smoke alarm: First Responders to investigate and will determine if it is a confirmed fire If an additional building alarm then it is considered a confirmed fire If confirmed fire 112 is called</details> </guidance> </pv> + <pv name="Spk-130RFC:RFS-RFPS-010:OpenBrkrPwrLineAlrm"> + <description>Power breaker is open in Spk-130RFC:RFS-RFPS-010. It is located at STUB 150</description> + <latching>true</latching> + <annunciating>true</annunciating> + <guidance> + <title>[Gate Guard Action]</title> + <details>Check for smoke alarms +If the machine is in maintenance and no active smoke alarms, no action. +If the machine is in production or there are any active smoke alarms, call the first responder team</details> + </guidance> + </pv> <pv name="Spk-130RFC:RFS-RFPS-020:SolidStateRackSmokeAlrm"> <description>Smoke is detected in RF Power Station Spk-130RFC:RFS-RFPS-020. It is located at STUB 150. It has been turned OFF</description> <latching>true</latching> @@ -930,12 +1255,25 @@ If confirmed fire 112 is called</details> <annunciating>true</annunciating> <guidance> <title>[Gate Guard Action]</title> - <details>Call out First Responders + <details>Check OpenBrkrPwrLineAlrm, then possibly call out First Responders +This alarm is known to occur spuriously. If OpenBrkrPwrLineAlrm also occurs, treat as a real smoke alarm, otherwise inform MCR. +If real smoke alarm: First Responders to investigate and will determine if it is a confirmed fire If an additional building alarm then it is considered a confirmed fire If confirmed fire 112 is called</details> </guidance> </pv> + <pv name="Spk-130RFC:RFS-RFPS-020:OpenBrkrPwrLineAlrm"> + <description>Power breaker is open in Spk-130RFC:RFS-RFPS-020. It is located at STUB 150</description> + <latching>true</latching> + <annunciating>true</annunciating> + <guidance> + <title>[Gate Guard Action]</title> + <details>Check for smoke alarms +If the machine is in maintenance and no active smoke alarms, no action. +If the machine is in production or there are any active smoke alarms, call the first responder team</details> + </guidance> + </pv> </component> </config>