From 4faa08c10f20890cd315ce62f3592a9ce8f0a250 Mon Sep 17 00:00:00 2001
From: Luciano Carneiro Guedes <luciano.carneiroguedes@ess.eu>
Date: Wed, 30 Oct 2024 11:53:30 +0100
Subject: [PATCH] ICSHWI-19564: Remove latching of Alarms and add missing PV

---
 alarm-01.tn.esss.lu.se/ODH.xml | 229 +++++++++++++++++----------------
 1 file changed, 119 insertions(+), 110 deletions(-)

diff --git a/alarm-01.tn.esss.lu.se/ODH.xml b/alarm-01.tn.esss.lu.se/ODH.xml
index eb99e9d..d5db4f3 100644
--- a/alarm-01.tn.esss.lu.se/ODH.xml
+++ b/alarm-01.tn.esss.lu.se/ODH.xml
@@ -11,6 +11,15 @@
 <config name="ODH">
   <component name="DIAG">
     <component name="ACC">
+        <pv name="HEBT-010Row:CnPw-U-011:CabHealthy">
+        <description>Device error in the PLC cabinet</description>
+        <latching>false</latching>
+        <annunciating>false</annunciating>
+        <guidance>
+          <title>[Operator Action]</title>
+          <details>Hardware error detected in the PLC cabinet. Inform PSS team.</details>
+        </guidance>
+      </pv>
       <pv name="Spk-070Row:CnPw-U-015:CabHealthy">
         <description>Device error in the RIO1 cabinet</description>
         <latching>false</latching>
@@ -40,7 +49,7 @@
       </pv>
       <pv name="AccODH-AT:Ctrl-CPU-001:FGCPU_CommStatus_Ok">
         <description>Connection between Safety PLC and gateway PLC has been lost</description>
-        <latching>true</latching>
+        <latching>false</latching>
         <annunciating>true</annunciating>
         <guidance>
           <title>[Operator Action]</title>
@@ -49,7 +58,7 @@
       </pv>
       <pv name="AccODH-AT:Ctrl-GCPU-001:AliveR">
         <description>Connection between gateway PLC and IOC has been lost</description>
-        <latching>true</latching>
+        <latching>false</latching>
         <annunciating>true</annunciating>
         <guidance>
           <title>[Operator Action]</title>
@@ -58,7 +67,7 @@
       </pv>
       <pv name="AccODH-AT:Ctrl-CPU-001:ChecksumStd_check">
         <description>Safety PLC standard software checksum mismatch</description>
-        <latching>true</latching>
+        <latching>false</latching>
         <annunciating>false</annunciating>
         <guidance>
           <title>[Operator Action]</title>
@@ -67,7 +76,7 @@
       </pv>
       <pv name="AccODH-AT:Ctrl-GCPU-001:ChecksumGW_check">
         <description>Gateway PLC standard software checksum mismatch</description>
-        <latching>true</latching>
+        <latching>false</latching>
         <annunciating>false</annunciating>
         <guidance>
           <title>[Operator Action]</title>
@@ -96,7 +105,7 @@
       </pv>
       <pv name="KG-GTA:ODH-PLC-01:FGCPU_CommStatus_Ok">
         <description>Connection between Safety PLC and gateway PLC has been lost</description>
-        <latching>true</latching>
+        <latching>false</latching>
         <annunciating>true</annunciating>
         <guidance>
           <title>[Operator Action]</title>
@@ -105,7 +114,7 @@
       </pv>
       <pv name="KG-GTA:ODH-PLC-01:ChecksumStd_check">
         <description>Connection between gateway PLC and IOC has been lost</description>
-        <latching>true</latching>
+        <latching>false</latching>
         <annunciating>true</annunciating>
         <guidance>
           <title>[Operator Action]</title>
@@ -114,7 +123,7 @@
       </pv>
       <pv name="KG-GTA:ODH-PLC-02:ChecksumGW_check">
         <description>Safety PLC standard software checksum mismatch</description>
-        <latching>true</latching>
+        <latching>false</latching>
         <annunciating>false</annunciating>
         <guidance>
           <title>[Operator Action]</title>
@@ -123,7 +132,7 @@
       </pv>
       <pv name="KG-GTA:ODH-PLC-02:AliveR">
         <description>Gateway PLC standard software checksum mismatch</description>
-        <latching>true</latching>
+        <latching>false</latching>
         <annunciating>false</annunciating>
         <guidance>
           <title>[Operator Action]</title>
@@ -134,7 +143,7 @@
     <component name="TS">
       <pv name="TgtGDS:CnPw-U-001:CabHealthy">
         <description>Device error in the PLC cabinet</description>
-        <latching>true</latching>
+        <latching>false</latching>
         <annunciating>false</annunciating>
         <guidance>
           <title>[Operator Action]</title>
@@ -245,7 +254,7 @@ Call cryo on call
     </pv>
     <pv name="AccODH-AT:ODH-Area-001:Attention">
       <description>Zone minor issue</description>
-      <latching>true</latching>
+      <latching>false</latching>
       <annunciating>false</annunciating>
       <guidance>
         <title>[Operator Action]</title>
@@ -255,7 +264,7 @@ Call cryo on call
     </pv>
     <pv name="AccODH-AT:ODH-Area-001:Maintenance">
       <description>Zone oxygen monitor in maintenance mode</description>
-      <latching>true</latching>
+      <latching>false</latching>
       <annunciating>false</annunciating>
       <guidance>
         <title>[Operator Action]</title>
@@ -264,7 +273,7 @@ Call cryo on call
     </pv>
     <pv name="AccODH-AT:ODH-Area-001:HwError">
       <description>Zone PLC HW failure</description>
-      <latching>true</latching>
+      <latching>false</latching>
       <annunciating>false</annunciating>
       <guidance>
         <title>[Operator Action]</title>
@@ -284,7 +293,7 @@ Call cryo on call
     </pv>
     <pv name="AccODH-AT:ODH-Area-001:ConfirmedAlrm">
       <description>Zone ODH confirmed alarm</description>
-      <latching>true</latching>
+      <latching>false</latching>
       <annunciating>false</annunciating>
       <guidance>
         <title>[Operator Action]</title>
@@ -297,7 +306,7 @@ Call cryo on call
     </pv>
     <pv name="AccODH-AT:ODH-Area-001:StartUp">
       <description>Zone equipment starting-up</description>
-      <latching>true</latching>
+      <latching>false</latching>
       <annunciating>false</annunciating>
       <guidance>
         <title>[Operator Action]</title>
@@ -306,7 +315,7 @@ Call cryo on call
     </pv>
     <pv name="AccODH-AT:ODH-Area-001:Muted">
       <description>Zone audible alarm muted</description>
-      <latching>true</latching>
+      <latching>false</latching>
       <annunciating>false</annunciating>
       <guidance>
         <title>[Operator Action]</title>
@@ -315,7 +324,7 @@ Call cryo on call
     </pv>
     <pv name="AccODH-AT:ODH-Area-001:DeviceFailure">
       <description>Zone alarm device failure</description>
-      <latching>true</latching>
+      <latching>false</latching>
       <annunciating>false</annunciating>
       <guidance>
         <title>[Operator Action]</title>
@@ -747,7 +756,7 @@ Call cryo on call
         </pv>
         <pv name="AccODH-AT:ODH-O2iM-001:Maintenance">
           <description>Monitor maintenance mode</description>
-          <latching>true</latching>
+          <latching>false</latching>
           <annunciating>false</annunciating>
           <guidance>
             <title>[Operator Action]</title>
@@ -776,7 +785,7 @@ Call cryo on call
         </pv>
         <pv name="AccODH-AT:ODH-O2iM-001:AiBadValue">
           <description>Oxygen level value is not valid</description>
-          <latching>true</latching>
+          <latching>false</latching>
           <annunciating>false</annunciating>
           <guidance>
             <title>[Operator Action]</title>
@@ -814,7 +823,7 @@ Call cryo on call
         </pv>
         <pv name="AccODH-AT:ODH-O2iM-002:Maintenance">
           <description>Monitor maintenance mode</description>
-          <latching>true</latching>
+          <latching>false</latching>
           <annunciating>false</annunciating>
           <guidance>
             <title>[Operator Action]</title>
@@ -843,7 +852,7 @@ Call cryo on call
         </pv>
         <pv name="AccODH-AT:ODH-O2iM-002:AiBadValue">
           <description>Oxygen level value is not valid</description>
-          <latching>true</latching>
+          <latching>false</latching>
           <annunciating>false</annunciating>
           <guidance>
             <title>[Operator Action]</title>
@@ -881,7 +890,7 @@ Call cryo on call
         </pv>
         <pv name="AccODH-AT:ODH-O2iM-003:Maintenance">
           <description>Monitor maintenance mode</description>
-          <latching>true</latching>
+          <latching>false</latching>
           <annunciating>false</annunciating>
           <guidance>
             <title>[Operator Action]</title>
@@ -910,7 +919,7 @@ Call cryo on call
         </pv>
         <pv name="AccODH-AT:ODH-O2iM-003:AiBadValue">
           <description>Oxygen level value is not valid</description>
-          <latching>true</latching>
+          <latching>false</latching>
           <annunciating>false</annunciating>
           <guidance>
             <title>[Operator Action]</title>
@@ -948,7 +957,7 @@ Call cryo on call
         </pv>
         <pv name="AccODH-AT:ODH-O2iM-004:Maintenance">
           <description>Monitor maintenance mode</description>
-          <latching>true</latching>
+          <latching>false</latching>
           <annunciating>false</annunciating>
           <guidance>
             <title>[Operator Action]</title>
@@ -977,7 +986,7 @@ Call cryo on call
         </pv>
         <pv name="AccODH-AT:ODH-O2iM-004:AiBadValue">
           <description>Oxygen level value is not valid</description>
-          <latching>true</latching>
+          <latching>false</latching>
           <annunciating>false</annunciating>
           <guidance>
             <title>[Operator Action]</title>
@@ -1015,7 +1024,7 @@ Call cryo on call
         </pv>
         <pv name="AccODH-AT:ODH-O2iM-005:Maintenance">
           <description>Monitor maintenance mode</description>
-          <latching>true</latching>
+          <latching>false</latching>
           <annunciating>false</annunciating>
           <guidance>
             <title>[Operator Action]</title>
@@ -1044,7 +1053,7 @@ Call cryo on call
         </pv>
         <pv name="AccODH-AT:ODH-O2iM-005:AiBadValue">
           <description>Oxygen level value is not valid</description>
-          <latching>true</latching>
+          <latching>false</latching>
           <annunciating>false</annunciating>
           <guidance>
             <title>[Operator Action]</title>
@@ -1082,7 +1091,7 @@ Call cryo on call
         </pv>
         <pv name="AccODH-AT:ODH-O2iM-006:Maintenance">
           <description>Monitor maintenance mode</description>
-          <latching>true</latching>
+          <latching>false</latching>
           <annunciating>false</annunciating>
           <guidance>
             <title>[Operator Action]</title>
@@ -1111,7 +1120,7 @@ Call cryo on call
         </pv>
         <pv name="AccODH-AT:ODH-O2iM-006:AiBadValue">
           <description>Oxygen level value is not valid</description>
-          <latching>true</latching>
+          <latching>false</latching>
           <annunciating>false</annunciating>
           <guidance>
             <title>[Operator Action]</title>
@@ -1149,7 +1158,7 @@ Call cryo on call
         </pv>
         <pv name="AccODH-AT:ODH-O2iM-007:Maintenance">
           <description>Monitor maintenance mode</description>
-          <latching>true</latching>
+          <latching>false</latching>
           <annunciating>false</annunciating>
           <guidance>
             <title>[Operator Action]</title>
@@ -1178,7 +1187,7 @@ Call cryo on call
         </pv>
         <pv name="AccODH-AT:ODH-O2iM-007:AiBadValue">
           <description>Oxygen level value is not valid</description>
-          <latching>true</latching>
+          <latching>false</latching>
           <annunciating>false</annunciating>
           <guidance>
             <title>[Operator Action]</title>
@@ -1216,7 +1225,7 @@ Call cryo on call
         </pv>
         <pv name="AccODH-AT:ODH-O2iM-008:Maintenance">
           <description>Monitor maintenance mode</description>
-          <latching>true</latching>
+          <latching>false</latching>
           <annunciating>false</annunciating>
           <guidance>
             <title>[Operator Action]</title>
@@ -1245,7 +1254,7 @@ Call cryo on call
         </pv>
         <pv name="AccODH-AT:ODH-O2iM-008:AiBadValue">
           <description>Oxygen level value is not valid</description>
-          <latching>true</latching>
+          <latching>false</latching>
           <annunciating>false</annunciating>
           <guidance>
             <title>[Operator Action]</title>
@@ -1283,7 +1292,7 @@ Call cryo on call
         </pv>
         <pv name="AccODH-AT:ODH-O2iM-009:Maintenance">
           <description>Monitor maintenance mode</description>
-          <latching>true</latching>
+          <latching>false</latching>
           <annunciating>false</annunciating>
           <guidance>
             <title>[Operator Action]</title>
@@ -1312,7 +1321,7 @@ Call cryo on call
         </pv>
         <pv name="AccODH-AT:ODH-O2iM-009:AiBadValue">
           <description>Oxygen level value is not valid</description>
-          <latching>true</latching>
+          <latching>false</latching>
           <annunciating>false</annunciating>
           <guidance>
             <title>[Operator Action]</title>
@@ -1350,7 +1359,7 @@ Call cryo on call
         </pv>
         <pv name="AccODH-AT:ODH-O2iM-010:Maintenance">
           <description>Monitor maintenance mode</description>
-          <latching>true</latching>
+          <latching>false</latching>
           <annunciating>false</annunciating>
           <guidance>
             <title>[Operator Action]</title>
@@ -1379,7 +1388,7 @@ Call cryo on call
         </pv>
         <pv name="AccODH-AT:ODH-O2iM-010:AiBadValue">
           <description>Oxygen level value is not valid</description>
-          <latching>true</latching>
+          <latching>false</latching>
           <annunciating>false</annunciating>
           <guidance>
             <title>[Operator Action]</title>
@@ -1417,7 +1426,7 @@ Call cryo on call
         </pv>
         <pv name="AccODH-AT:ODH-O2iM-011:Maintenance">
           <description>Monitor maintenance mode</description>
-          <latching>true</latching>
+          <latching>false</latching>
           <annunciating>false</annunciating>
           <guidance>
             <title>[Operator Action]</title>
@@ -1446,7 +1455,7 @@ Call cryo on call
         </pv>
         <pv name="AccODH-AT:ODH-O2iM-011:AiBadValue">
           <description>Oxygen level value is not valid</description>
-          <latching>true</latching>
+          <latching>false</latching>
           <annunciating>false</annunciating>
           <guidance>
             <title>[Operator Action]</title>
@@ -1484,7 +1493,7 @@ Call cryo on call
         </pv>
         <pv name="AccODH-AT:ODH-O2iM-012:Maintenance">
           <description>Monitor maintenance mode</description>
-          <latching>true</latching>
+          <latching>false</latching>
           <annunciating>false</annunciating>
           <guidance>
             <title>[Operator Action]</title>
@@ -1513,7 +1522,7 @@ Call cryo on call
         </pv>
         <pv name="AccODH-AT:ODH-O2iM-012:AiBadValue">
           <description>Oxygen level value is not valid</description>
-          <latching>true</latching>
+          <latching>false</latching>
           <annunciating>false</annunciating>
           <guidance>
             <title>[Operator Action]</title>
@@ -1551,7 +1560,7 @@ Call cryo on call
         </pv>
         <pv name="AccODH-AT:ODH-O2iM-013:Maintenance">
           <description>Monitor maintenance mode</description>
-          <latching>true</latching>
+          <latching>false</latching>
           <annunciating>false</annunciating>
           <guidance>
             <title>[Operator Action]</title>
@@ -1580,7 +1589,7 @@ Call cryo on call
         </pv>
         <pv name="AccODH-AT:ODH-O2iM-013:AiBadValue">
           <description>Oxygen level value is not valid</description>
-          <latching>true</latching>
+          <latching>false</latching>
           <annunciating>false</annunciating>
           <guidance>
             <title>[Operator Action]</title>
@@ -1618,7 +1627,7 @@ Call cryo on call
         </pv>
         <pv name="AccODH-AT:ODH-O2iM-014:Maintenance">
           <description>Monitor maintenance mode</description>
-          <latching>true</latching>
+          <latching>false</latching>
           <annunciating>false</annunciating>
           <guidance>
             <title>[Operator Action]</title>
@@ -1647,7 +1656,7 @@ Call cryo on call
         </pv>
         <pv name="AccODH-AT:ODH-O2iM-014:AiBadValue">
           <description>Oxygen level value is not valid</description>
-          <latching>true</latching>
+          <latching>false</latching>
           <annunciating>false</annunciating>
           <guidance>
             <title>[Operator Action]</title>
@@ -2081,7 +2090,7 @@ Call cryo on call
     </pv>
     <pv name="CTLG-CS:ODH-Area:Attention">
       <description>Zone minor issue</description>
-      <latching>true</latching>
+      <latching>false</latching>
       <annunciating>false</annunciating>
       <guidance>
         <title>[Operator Action]</title>
@@ -2091,7 +2100,7 @@ Call cryo on call
     </pv>
     <pv name="CTLG-CS:ODH-Area:Maintenance">
       <description>Zone oxygen monitor in maintenance mode</description>
-      <latching>true</latching>
+      <latching>false</latching>
       <annunciating>false</annunciating>
       <guidance>
         <title>[Operator Action]</title>
@@ -2100,7 +2109,7 @@ Call cryo on call
     </pv>
     <pv name="CTLG-CS:ODH-Area:HwError">
       <description>Zone PLC HW failure</description>
-      <latching>true</latching>
+      <latching>false</latching>
       <annunciating>false</annunciating>
       <guidance>
         <title>[Operator Action]</title>
@@ -2110,7 +2119,7 @@ Call cryo on call
     </pv>
     <pv name="CTLG-CS:ODH-Area:ConfirmedAlrm">
       <description>Zone ODH confirmed alarm</description>
-      <latching>true</latching>
+      <latching>false</latching>
       <annunciating>false</annunciating>
       <guidance>
         <title>[Operator Action]</title>
@@ -2123,7 +2132,7 @@ Call cryo on call
     </pv>
     <pv name="CTLG-CS:ODH-Area:StartUp">
       <description>Zone equipment starting-up</description>
-      <latching>true</latching>
+      <latching>false</latching>
       <annunciating>false</annunciating>
       <guidance>
         <title>[Operator Action]</title>
@@ -2132,7 +2141,7 @@ Call cryo on call
     </pv>
     <pv name="CTLG-CS:ODH-Area:Muted">
       <description>Zone audible alarm muted</description>
-      <latching>true</latching>
+      <latching>false</latching>
       <annunciating>false</annunciating>
       <guidance>
         <title>[Operator Action]</title>
@@ -2169,7 +2178,7 @@ Call cryo on call
         </pv>
         <pv name="CTLG-CS:ODH-O2iM-20:Maintenance">
           <description>Monitor maintenance mode</description>
-          <latching>true</latching>
+          <latching>false</latching>
           <annunciating>false</annunciating>
           <guidance>
             <title>[Operator Action]</title>
@@ -2198,7 +2207,7 @@ Call cryo on call
         </pv>
         <pv name="CTLG-CS:ODH-O2iM-20:AiBadValue">
           <description>Oxygen level value is not valid</description>
-          <latching>true</latching>
+          <latching>false</latching>
           <annunciating>false</annunciating>
           <guidance>
             <title>[Operator Action]</title>
@@ -2236,7 +2245,7 @@ Call cryo on call
         </pv>
         <pv name="CTLG-CS:ODH-O2iM-21:Maintenance">
           <description>Monitor maintenance mode</description>
-          <latching>true</latching>
+          <latching>false</latching>
           <annunciating>false</annunciating>
           <guidance>
             <title>[Operator Action]</title>
@@ -2265,7 +2274,7 @@ Call cryo on call
         </pv>
         <pv name="CTLG-CS:ODH-O2iM-21:AiBadValue">
           <description>Oxygen level value is not valid</description>
-          <latching>true</latching>
+          <latching>false</latching>
           <annunciating>false</annunciating>
           <guidance>
             <title>[Operator Action]</title>
@@ -2303,7 +2312,7 @@ Call cryo on call
         </pv>
         <pv name="CTLG-CS:ODH-O2iM-22:Maintenance">
           <description>Monitor maintenance mode</description>
-          <latching>true</latching>
+          <latching>false</latching>
           <annunciating>false</annunciating>
           <guidance>
             <title>[Operator Action]</title>
@@ -2332,7 +2341,7 @@ Call cryo on call
         </pv>
         <pv name="CTLG-CS:ODH-O2iM-22:AiBadValue">
           <description>Oxygen level value is not valid</description>
-          <latching>true</latching>
+          <latching>false</latching>
           <annunciating>false</annunciating>
           <guidance>
             <title>[Operator Action]</title>
@@ -2382,7 +2391,7 @@ Call cryo on call
     </pv>
     <pv name="CXB-CXH:ODH-Area:Attention">
       <description>Zone minor issue</description>
-      <latching>true</latching>
+      <latching>false</latching>
       <annunciating>false</annunciating>
       <guidance>
         <title>[Operator Action]</title>
@@ -2392,7 +2401,7 @@ Call cryo on call
     </pv>
     <pv name="CXB-CXH:ODH-Area:Maintenance">
       <description>Zone oxygen monitor in maintenance mode</description>
-      <latching>true</latching>
+      <latching>false</latching>
       <annunciating>false</annunciating>
       <guidance>
         <title>[Operator Action]</title>
@@ -2401,7 +2410,7 @@ Call cryo on call
     </pv>
     <pv name="CXB-CXH:ODH-Area:HwError">
       <description>Zone PLC HW failure</description>
-      <latching>true</latching>
+      <latching>false</latching>
       <annunciating>false</annunciating>
       <guidance>
         <title>[Operator Action]</title>
@@ -2411,7 +2420,7 @@ Call cryo on call
     </pv>
     <pv name="CXB-CXH:ODH-Area:ConfirmedAlrm">
       <description>Zone ODH confirmed alarm</description>
-      <latching>true</latching>
+      <latching>false</latching>
       <annunciating>false</annunciating>
       <guidance>
         <title>[Operator Action]</title>
@@ -2424,7 +2433,7 @@ Call cryo on call
     </pv>
     <pv name="CXB-CXH:ODH-Area:StartUp">
       <description>Zone equipment starting-up</description>
-      <latching>true</latching>
+      <latching>false</latching>
       <annunciating>false</annunciating>
       <guidance>
         <title>[Operator Action]</title>
@@ -2433,7 +2442,7 @@ Call cryo on call
     </pv>
     <pv name="CXB-CXH:ODH-Area:Muted">
       <description>Zone audible alarm muted</description>
-      <latching>true</latching>
+      <latching>false</latching>
       <annunciating>false</annunciating>
       <guidance>
         <title>[Operator Action]</title>
@@ -2470,7 +2479,7 @@ Call cryo on call
         </pv>
         <pv name="CXB-CXH:ODH-O2iM-13:Maintenance">
           <description>Monitor maintenance mode</description>
-          <latching>true</latching>
+          <latching>false</latching>
           <annunciating>false</annunciating>
           <guidance>
             <title>[Operator Action]</title>
@@ -2499,7 +2508,7 @@ Call cryo on call
         </pv>
         <pv name="CXB-CXH:ODH-O2iM-13:AiBadValue">
           <description>Oxygen level value is not valid</description>
-          <latching>true</latching>
+          <latching>false</latching>
           <annunciating>false</annunciating>
           <guidance>
             <title>[Operator Action]</title>
@@ -2537,7 +2546,7 @@ Call cryo on call
         </pv>
         <pv name="CXB-CXH:ODH-O2iM-14:Maintenance">
           <description>Monitor maintenance mode</description>
-          <latching>true</latching>
+          <latching>false</latching>
           <annunciating>false</annunciating>
           <guidance>
             <title>[Operator Action]</title>
@@ -2566,7 +2575,7 @@ Call cryo on call
         </pv>
         <pv name="CXB-CXH:ODH-O2iM-14:AiBadValue">
           <description>Oxygen level value is not valid</description>
-          <latching>true</latching>
+          <latching>false</latching>
           <annunciating>false</annunciating>
           <guidance>
             <title>[Operator Action]</title>
@@ -2604,7 +2613,7 @@ Call cryo on call
         </pv>
         <pv name="CXB-CXH:ODH-O2iM-16:Maintenance">
           <description>Monitor maintenance mode</description>
-          <latching>true</latching>
+          <latching>false</latching>
           <annunciating>false</annunciating>
           <guidance>
             <title>[Operator Action]</title>
@@ -2633,7 +2642,7 @@ Call cryo on call
         </pv>
         <pv name="CXB-CXH:ODH-O2iM-16:AiBadValue">
           <description>Oxygen level value is not valid</description>
-          <latching>true</latching>
+          <latching>false</latching>
           <annunciating>false</annunciating>
           <guidance>
             <title>[Operator Action]</title>
@@ -2671,7 +2680,7 @@ Call cryo on call
         </pv>
         <pv name="CXB-CXH:ODH-O2iM-17:Maintenance">
           <description>Monitor maintenance mode</description>
-          <latching>true</latching>
+          <latching>false</latching>
           <annunciating>false</annunciating>
           <guidance>
             <title>[Operator Action]</title>
@@ -2700,7 +2709,7 @@ Call cryo on call
         </pv>
         <pv name="CXB-CXH:ODH-O2iM-17:AiBadValue">
           <description>Oxygen level value is not valid</description>
-          <latching>true</latching>
+          <latching>false</latching>
           <annunciating>false</annunciating>
           <guidance>
             <title>[Operator Action]</title>
@@ -2750,7 +2759,7 @@ Call cryo on call
     </pv>
     <pv name="HCB-DogSh:ODH-Area:Attention">
       <description>Zone minor issue</description>
-      <latching>true</latching>
+      <latching>false</latching>
       <annunciating>false</annunciating>
       <guidance>
         <title>[Operator Action]</title>
@@ -2760,7 +2769,7 @@ Call cryo on call
     </pv>
     <pv name="HCB-DogSh:ODH-Area:Maintenance">
       <description>Zone oxygen monitor in maintenance mode</description>
-      <latching>true</latching>
+      <latching>false</latching>
       <annunciating>false</annunciating>
       <guidance>
         <title>[Operator Action]</title>
@@ -2769,7 +2778,7 @@ Call cryo on call
     </pv>
     <pv name="HCB-DogSh:ODH-Area:HwError">
       <description>Zone PLC HW failure</description>
-      <latching>true</latching>
+      <latching>false</latching>
       <annunciating>false</annunciating>
       <guidance>
         <title>[Operator Action]</title>
@@ -2779,7 +2788,7 @@ Call cryo on call
     </pv>
     <pv name="HCB-DogSh:ODH-Area:ConfirmedAlrm">
       <description>Zone ODH confirmed alarm</description>
-      <latching>true</latching>
+      <latching>false</latching>
       <annunciating>false</annunciating>
       <guidance>
         <title>[Operator Action]</title>
@@ -2792,7 +2801,7 @@ Call cryo on call
     </pv>
     <pv name="HCB-DogSh:ODH-Area:StartUp">
       <description>Zone equipment starting-up</description>
-      <latching>true</latching>
+      <latching>false</latching>
       <annunciating>false</annunciating>
       <guidance>
         <title>[Operator Action]</title>
@@ -2801,7 +2810,7 @@ Call cryo on call
     </pv>
     <pv name="HCB-DogSh:ODH-Area:Muted">
       <description>Zone audible alarm muted</description>
-      <latching>true</latching>
+      <latching>false</latching>
       <annunciating>false</annunciating>
       <guidance>
         <title>[Operator Action]</title>
@@ -2838,7 +2847,7 @@ Call cryo on call
         </pv>
         <pv name="HCB-DogSh:ODH-O2iM-12:Maintenance">
           <description>Monitor maintenance mode</description>
-          <latching>true</latching>
+          <latching>false</latching>
           <annunciating>false</annunciating>
           <guidance>
             <title>[Operator Action]</title>
@@ -2867,7 +2876,7 @@ Call cryo on call
         </pv>
         <pv name="HCB-DogSh:ODH-O2iM-12:AiBadValue">
           <description>Oxygen level value is not valid</description>
-          <latching>true</latching>
+          <latching>false</latching>
           <annunciating>false</annunciating>
           <guidance>
             <title>[Operator Action]</title>
@@ -2917,7 +2926,7 @@ Call cryo on call
     </pv>
     <pv name="HCB-ACH:ODH-Area:Attention">
       <description>Zone minor issue</description>
-      <latching>true</latching>
+      <latching>false</latching>
       <annunciating>false</annunciating>
       <guidance>
         <title>[Operator Action]</title>
@@ -2927,7 +2936,7 @@ Call cryo on call
     </pv>
     <pv name="HCB-ACH:ODH-Area:Maintenance">
       <description>Zone oxygen monitor in maintenance mode</description>
-      <latching>true</latching>
+      <latching>false</latching>
       <annunciating>false</annunciating>
       <guidance>
         <title>[Operator Action]</title>
@@ -2936,7 +2945,7 @@ Call cryo on call
     </pv>
     <pv name="HCB-ACH:ODH-Area:HwError">
       <description>Zone PLC HW failure</description>
-      <latching>true</latching>
+      <latching>false</latching>
       <annunciating>false</annunciating>
       <guidance>
         <title>[Operator Action]</title>
@@ -2946,7 +2955,7 @@ Call cryo on call
     </pv>
     <pv name="HCB-ACH:ODH-Area:ConfirmedAlrm">
       <description>Zone ODH confirmed alarm</description>
-      <latching>true</latching>
+      <latching>false</latching>
       <annunciating>false</annunciating>
       <guidance>
         <title>[Operator Action]</title>
@@ -2959,7 +2968,7 @@ Call cryo on call
     </pv>
     <pv name="HCB-ACH:ODH-Area:StartUp">
       <description>Zone equipment starting-up</description>
-      <latching>true</latching>
+      <latching>false</latching>
       <annunciating>false</annunciating>
       <guidance>
         <title>[Operator Action]</title>
@@ -2968,7 +2977,7 @@ Call cryo on call
     </pv>
     <pv name="HCB-ACH:ODH-Area:Muted">
       <description>Zone audible alarm muted</description>
-      <latching>true</latching>
+      <latching>false</latching>
       <annunciating>false</annunciating>
       <guidance>
         <title>[Operator Action]</title>
@@ -3005,7 +3014,7 @@ Call cryo on call
         </pv>
         <pv name="HCB-ACH:ODH-O2iM-2:Maintenance">
           <description>Monitor maintenance mode</description>
-          <latching>true</latching>
+          <latching>false</latching>
           <annunciating>false</annunciating>
           <guidance>
             <title>[Operator Action]</title>
@@ -3034,7 +3043,7 @@ Call cryo on call
         </pv>
         <pv name="HCB-ACH:ODH-O2iM-2:AiBadValue">
           <description>Oxygen level value is not valid</description>
-          <latching>true</latching>
+          <latching>false</latching>
           <annunciating>false</annunciating>
           <guidance>
             <title>[Operator Action]</title>
@@ -3072,7 +3081,7 @@ Call cryo on call
         </pv>
         <pv name="HCB-ACH:ODH-O2iM-3:Maintenance">
           <description>Monitor maintenance mode</description>
-          <latching>true</latching>
+          <latching>false</latching>
           <annunciating>false</annunciating>
           <guidance>
             <title>[Operator Action]</title>
@@ -3101,7 +3110,7 @@ Call cryo on call
         </pv>
         <pv name="HCB-ACH:ODH-O2iM-3:AiBadValue">
           <description>Oxygen level value is not valid</description>
-          <latching>true</latching>
+          <latching>false</latching>
           <annunciating>false</annunciating>
           <guidance>
             <title>[Operator Action]</title>
@@ -3139,7 +3148,7 @@ Call cryo on call
         </pv>
         <pv name="HCB-ACH:ODH-O2iM-4:Maintenance">
           <description>Monitor maintenance mode</description>
-          <latching>true</latching>
+          <latching>false</latching>
           <annunciating>false</annunciating>
           <guidance>
             <title>[Operator Action]</title>
@@ -3168,7 +3177,7 @@ Call cryo on call
         </pv>
         <pv name="HCB-ACH:ODH-O2iM-4:AiBadValue">
           <description>Oxygen level value is not valid</description>
-          <latching>true</latching>
+          <latching>false</latching>
           <annunciating>false</annunciating>
           <guidance>
             <title>[Operator Action]</title>
@@ -3206,7 +3215,7 @@ Call cryo on call
         </pv>
         <pv name="HCB-ACH:ODH-O2iM-5:Maintenance">
           <description>Monitor maintenance mode</description>
-          <latching>true</latching>
+          <latching>false</latching>
           <annunciating>false</annunciating>
           <guidance>
             <title>[Operator Action]</title>
@@ -3235,7 +3244,7 @@ Call cryo on call
         </pv>
         <pv name="HCB-ACH:ODH-O2iM-5:AiBadValue">
           <description>Oxygen level value is not valid</description>
-          <latching>true</latching>
+          <latching>false</latching>
           <annunciating>false</annunciating>
           <guidance>
             <title>[Operator Action]</title>
@@ -3273,7 +3282,7 @@ Call cryo on call
         </pv>
         <pv name="HCB-TCH:ODH-O2iM-6:Maintenance">
           <description>Monitor maintenance mode</description>
-          <latching>true</latching>
+          <latching>false</latching>
           <annunciating>false</annunciating>
           <guidance>
             <title>[Operator Action]</title>
@@ -3302,7 +3311,7 @@ Call cryo on call
         </pv>
         <pv name="HCB-TCH:ODH-O2iM-6:AiBadValue">
           <description>Oxygen level value is not valid</description>
-          <latching>true</latching>
+          <latching>false</latching>
           <annunciating>false</annunciating>
           <guidance>
             <title>[Operator Action]</title>
@@ -3340,7 +3349,7 @@ Call cryo on call
         </pv>
         <pv name="HCB-TCH:ODH-O2iM-8:Maintenance">
           <description>Monitor maintenance mode</description>
-          <latching>true</latching>
+          <latching>false</latching>
           <annunciating>false</annunciating>
           <guidance>
             <title>[Operator Action]</title>
@@ -3369,7 +3378,7 @@ Call cryo on call
         </pv>
         <pv name="HCB-TCH:ODH-O2iM-8:AiBadValue">
           <description>Oxygen level value is not valid</description>
-          <latching>true</latching>
+          <latching>false</latching>
           <annunciating>false</annunciating>
           <guidance>
             <title>[Operator Action]</title>
@@ -3407,7 +3416,7 @@ Call cryo on call
         </pv>
         <pv name="HCB-TCH:ODH-O2iM-9:Maintenance">
           <description>Monitor maintenance mode</description>
-          <latching>true</latching>
+          <latching>false</latching>
           <annunciating>false</annunciating>
           <guidance>
             <title>[Operator Action]</title>
@@ -3436,7 +3445,7 @@ Call cryo on call
         </pv>
         <pv name="HCB-TCH:ODH-O2iM-9:AiBadValue">
           <description>Oxygen level value is not valid</description>
-          <latching>true</latching>
+          <latching>false</latching>
           <annunciating>false</annunciating>
           <guidance>
             <title>[Operator Action]</title>
@@ -3474,7 +3483,7 @@ Call cryo on call
         </pv>
         <pv name="HCB-HPGS:ODH-O2iM-10:Maintenance">
           <description>Monitor maintenance mode</description>
-          <latching>true</latching>
+          <latching>false</latching>
           <annunciating>false</annunciating>
           <guidance>
             <title>[Operator Action]</title>
@@ -3503,7 +3512,7 @@ Call cryo on call
         </pv>
         <pv name="HCB-HPGS:ODH-O2iM-10:AiBadValue">
           <description>Oxygen level value is not valid</description>
-          <latching>true</latching>
+          <latching>false</latching>
           <annunciating>false</annunciating>
           <guidance>
             <title>[Operator Action]</title>
@@ -3553,7 +3562,7 @@ Call cryo on call
     </pv>
     <pv name="KG-GTA:ODH-Area-001:Attention">
       <description>Zone minor issue</description>
-      <latching>true</latching>
+      <latching>false</latching>
       <annunciating>false</annunciating>
       <guidance>
         <title>[Operator Action]</title>
@@ -3563,7 +3572,7 @@ Call cryo on call
     </pv>
     <pv name="KG-GTA:ODH-Area-001:Maintenance">
       <description>Zone oxygen monitor in maintenance mode</description>
-      <latching>true</latching>
+      <latching>false</latching>
       <annunciating>false</annunciating>
       <guidance>
         <title>[Operator Action]</title>
@@ -3572,7 +3581,7 @@ Call cryo on call
     </pv>
     <pv name="KG-GTA:ODH-Area-001:HwError">
       <description>Zone PLC HW failure</description>
-      <latching>true</latching>
+      <latching>false</latching>
       <annunciating>false</annunciating>
       <guidance>
         <title>[Operator Action]</title>
@@ -3582,7 +3591,7 @@ Call cryo on call
     </pv>
     <pv name="KG-GTA:ODH-Area-001:ConfirmedAlrm">
       <description>Zone ODH confirmed alarm</description>
-      <latching>true</latching>
+      <latching>false</latching>
       <annunciating>false</annunciating>
       <guidance>
         <title>[Operator Action]</title>
@@ -3595,7 +3604,7 @@ Call cryo on call
     </pv>
     <pv name="KG-GTA:ODH-Area-001:StartUp">
       <description>Zone equipment starting-up</description>
-      <latching>true</latching>
+      <latching>false</latching>
       <annunciating>false</annunciating>
       <guidance>
         <title>[Operator Action]</title>
@@ -3604,7 +3613,7 @@ Call cryo on call
     </pv>
     <pv name="KG-GTA:ODH-Area-001:Muted">
       <description>Zone audible alarm muted</description>
-      <latching>true</latching>
+      <latching>false</latching>
       <annunciating>false</annunciating>
       <guidance>
         <title>[Operator Action]</title>
@@ -3641,7 +3650,7 @@ Call cryo on call
         </pv>
         <pv name="KG-GTA:ODH-O2iM-23:Maintenance">
           <description>Monitor maintenance mode</description>
-          <latching>true</latching>
+          <latching>false</latching>
           <annunciating>false</annunciating>
           <guidance>
             <title>[Operator Action]</title>
@@ -3670,7 +3679,7 @@ Call cryo on call
         </pv>
         <pv name="KG-GTA:ODH-O2iM-23:AiBadValue">
           <description>Oxygen level value is not valid</description>
-          <latching>true</latching>
+          <latching>false</latching>
           <annunciating>false</annunciating>
           <guidance>
             <title>[Operator Action]</title>
@@ -3708,7 +3717,7 @@ Call cryo on call
         </pv>
         <pv name="KG-GTA:ODH-O2iM-24:Maintenance">
           <description>Monitor maintenance mode</description>
-          <latching>true</latching>
+          <latching>false</latching>
           <annunciating>false</annunciating>
           <guidance>
             <title>[Operator Action]</title>
@@ -3737,7 +3746,7 @@ Call cryo on call
         </pv>
         <pv name="KG-GTA:ODH-O2iM-24:AiBadValue">
           <description>Oxygen level value is not valid</description>
-          <latching>true</latching>
+          <latching>false</latching>
           <annunciating>false</annunciating>
           <guidance>
             <title>[Operator Action]</title>
-- 
GitLab