From 4faa08c10f20890cd315ce62f3592a9ce8f0a250 Mon Sep 17 00:00:00 2001 From: Luciano Carneiro Guedes <luciano.carneiroguedes@ess.eu> Date: Wed, 30 Oct 2024 11:53:30 +0100 Subject: [PATCH] ICSHWI-19564: Remove latching of Alarms and add missing PV --- alarm-01.tn.esss.lu.se/ODH.xml | 229 +++++++++++++++++---------------- 1 file changed, 119 insertions(+), 110 deletions(-) diff --git a/alarm-01.tn.esss.lu.se/ODH.xml b/alarm-01.tn.esss.lu.se/ODH.xml index eb99e9d..d5db4f3 100644 --- a/alarm-01.tn.esss.lu.se/ODH.xml +++ b/alarm-01.tn.esss.lu.se/ODH.xml @@ -11,6 +11,15 @@ <config name="ODH"> <component name="DIAG"> <component name="ACC"> + <pv name="HEBT-010Row:CnPw-U-011:CabHealthy"> + <description>Device error in the PLC cabinet</description> + <latching>false</latching> + <annunciating>false</annunciating> + <guidance> + <title>[Operator Action]</title> + <details>Hardware error detected in the PLC cabinet. Inform PSS team.</details> + </guidance> + </pv> <pv name="Spk-070Row:CnPw-U-015:CabHealthy"> <description>Device error in the RIO1 cabinet</description> <latching>false</latching> @@ -40,7 +49,7 @@ </pv> <pv name="AccODH-AT:Ctrl-CPU-001:FGCPU_CommStatus_Ok"> <description>Connection between Safety PLC and gateway PLC has been lost</description> - <latching>true</latching> + <latching>false</latching> <annunciating>true</annunciating> <guidance> <title>[Operator Action]</title> @@ -49,7 +58,7 @@ </pv> <pv name="AccODH-AT:Ctrl-GCPU-001:AliveR"> <description>Connection between gateway PLC and IOC has been lost</description> - <latching>true</latching> + <latching>false</latching> <annunciating>true</annunciating> <guidance> <title>[Operator Action]</title> @@ -58,7 +67,7 @@ </pv> <pv name="AccODH-AT:Ctrl-CPU-001:ChecksumStd_check"> <description>Safety PLC standard software checksum mismatch</description> - <latching>true</latching> + <latching>false</latching> <annunciating>false</annunciating> <guidance> <title>[Operator Action]</title> @@ -67,7 +76,7 @@ </pv> <pv name="AccODH-AT:Ctrl-GCPU-001:ChecksumGW_check"> <description>Gateway PLC standard software checksum mismatch</description> - <latching>true</latching> + <latching>false</latching> <annunciating>false</annunciating> <guidance> <title>[Operator Action]</title> @@ -96,7 +105,7 @@ </pv> <pv name="KG-GTA:ODH-PLC-01:FGCPU_CommStatus_Ok"> <description>Connection between Safety PLC and gateway PLC has been lost</description> - <latching>true</latching> + <latching>false</latching> <annunciating>true</annunciating> <guidance> <title>[Operator Action]</title> @@ -105,7 +114,7 @@ </pv> <pv name="KG-GTA:ODH-PLC-01:ChecksumStd_check"> <description>Connection between gateway PLC and IOC has been lost</description> - <latching>true</latching> + <latching>false</latching> <annunciating>true</annunciating> <guidance> <title>[Operator Action]</title> @@ -114,7 +123,7 @@ </pv> <pv name="KG-GTA:ODH-PLC-02:ChecksumGW_check"> <description>Safety PLC standard software checksum mismatch</description> - <latching>true</latching> + <latching>false</latching> <annunciating>false</annunciating> <guidance> <title>[Operator Action]</title> @@ -123,7 +132,7 @@ </pv> <pv name="KG-GTA:ODH-PLC-02:AliveR"> <description>Gateway PLC standard software checksum mismatch</description> - <latching>true</latching> + <latching>false</latching> <annunciating>false</annunciating> <guidance> <title>[Operator Action]</title> @@ -134,7 +143,7 @@ <component name="TS"> <pv name="TgtGDS:CnPw-U-001:CabHealthy"> <description>Device error in the PLC cabinet</description> - <latching>true</latching> + <latching>false</latching> <annunciating>false</annunciating> <guidance> <title>[Operator Action]</title> @@ -245,7 +254,7 @@ Call cryo on call </pv> <pv name="AccODH-AT:ODH-Area-001:Attention"> <description>Zone minor issue</description> - <latching>true</latching> + <latching>false</latching> <annunciating>false</annunciating> <guidance> <title>[Operator Action]</title> @@ -255,7 +264,7 @@ Call cryo on call </pv> <pv name="AccODH-AT:ODH-Area-001:Maintenance"> <description>Zone oxygen monitor in maintenance mode</description> - <latching>true</latching> + <latching>false</latching> <annunciating>false</annunciating> <guidance> <title>[Operator Action]</title> @@ -264,7 +273,7 @@ Call cryo on call </pv> <pv name="AccODH-AT:ODH-Area-001:HwError"> <description>Zone PLC HW failure</description> - <latching>true</latching> + <latching>false</latching> <annunciating>false</annunciating> <guidance> <title>[Operator Action]</title> @@ -284,7 +293,7 @@ Call cryo on call </pv> <pv name="AccODH-AT:ODH-Area-001:ConfirmedAlrm"> <description>Zone ODH confirmed alarm</description> - <latching>true</latching> + <latching>false</latching> <annunciating>false</annunciating> <guidance> <title>[Operator Action]</title> @@ -297,7 +306,7 @@ Call cryo on call </pv> <pv name="AccODH-AT:ODH-Area-001:StartUp"> <description>Zone equipment starting-up</description> - <latching>true</latching> + <latching>false</latching> <annunciating>false</annunciating> <guidance> <title>[Operator Action]</title> @@ -306,7 +315,7 @@ Call cryo on call </pv> <pv name="AccODH-AT:ODH-Area-001:Muted"> <description>Zone audible alarm muted</description> - <latching>true</latching> + <latching>false</latching> <annunciating>false</annunciating> <guidance> <title>[Operator Action]</title> @@ -315,7 +324,7 @@ Call cryo on call </pv> <pv name="AccODH-AT:ODH-Area-001:DeviceFailure"> <description>Zone alarm device failure</description> - <latching>true</latching> + <latching>false</latching> <annunciating>false</annunciating> <guidance> <title>[Operator Action]</title> @@ -747,7 +756,7 @@ Call cryo on call </pv> <pv name="AccODH-AT:ODH-O2iM-001:Maintenance"> <description>Monitor maintenance mode</description> - <latching>true</latching> + <latching>false</latching> <annunciating>false</annunciating> <guidance> <title>[Operator Action]</title> @@ -776,7 +785,7 @@ Call cryo on call </pv> <pv name="AccODH-AT:ODH-O2iM-001:AiBadValue"> <description>Oxygen level value is not valid</description> - <latching>true</latching> + <latching>false</latching> <annunciating>false</annunciating> <guidance> <title>[Operator Action]</title> @@ -814,7 +823,7 @@ Call cryo on call </pv> <pv name="AccODH-AT:ODH-O2iM-002:Maintenance"> <description>Monitor maintenance mode</description> - <latching>true</latching> + <latching>false</latching> <annunciating>false</annunciating> <guidance> <title>[Operator Action]</title> @@ -843,7 +852,7 @@ Call cryo on call </pv> <pv name="AccODH-AT:ODH-O2iM-002:AiBadValue"> <description>Oxygen level value is not valid</description> - <latching>true</latching> + <latching>false</latching> <annunciating>false</annunciating> <guidance> <title>[Operator Action]</title> @@ -881,7 +890,7 @@ Call cryo on call </pv> <pv name="AccODH-AT:ODH-O2iM-003:Maintenance"> <description>Monitor maintenance mode</description> - <latching>true</latching> + <latching>false</latching> <annunciating>false</annunciating> <guidance> <title>[Operator Action]</title> @@ -910,7 +919,7 @@ Call cryo on call </pv> <pv name="AccODH-AT:ODH-O2iM-003:AiBadValue"> <description>Oxygen level value is not valid</description> - <latching>true</latching> + <latching>false</latching> <annunciating>false</annunciating> <guidance> <title>[Operator Action]</title> @@ -948,7 +957,7 @@ Call cryo on call </pv> <pv name="AccODH-AT:ODH-O2iM-004:Maintenance"> <description>Monitor maintenance mode</description> - <latching>true</latching> + <latching>false</latching> <annunciating>false</annunciating> <guidance> <title>[Operator Action]</title> @@ -977,7 +986,7 @@ Call cryo on call </pv> <pv name="AccODH-AT:ODH-O2iM-004:AiBadValue"> <description>Oxygen level value is not valid</description> - <latching>true</latching> + <latching>false</latching> <annunciating>false</annunciating> <guidance> <title>[Operator Action]</title> @@ -1015,7 +1024,7 @@ Call cryo on call </pv> <pv name="AccODH-AT:ODH-O2iM-005:Maintenance"> <description>Monitor maintenance mode</description> - <latching>true</latching> + <latching>false</latching> <annunciating>false</annunciating> <guidance> <title>[Operator Action]</title> @@ -1044,7 +1053,7 @@ Call cryo on call </pv> <pv name="AccODH-AT:ODH-O2iM-005:AiBadValue"> <description>Oxygen level value is not valid</description> - <latching>true</latching> + <latching>false</latching> <annunciating>false</annunciating> <guidance> <title>[Operator Action]</title> @@ -1082,7 +1091,7 @@ Call cryo on call </pv> <pv name="AccODH-AT:ODH-O2iM-006:Maintenance"> <description>Monitor maintenance mode</description> - <latching>true</latching> + <latching>false</latching> <annunciating>false</annunciating> <guidance> <title>[Operator Action]</title> @@ -1111,7 +1120,7 @@ Call cryo on call </pv> <pv name="AccODH-AT:ODH-O2iM-006:AiBadValue"> <description>Oxygen level value is not valid</description> - <latching>true</latching> + <latching>false</latching> <annunciating>false</annunciating> <guidance> <title>[Operator Action]</title> @@ -1149,7 +1158,7 @@ Call cryo on call </pv> <pv name="AccODH-AT:ODH-O2iM-007:Maintenance"> <description>Monitor maintenance mode</description> - <latching>true</latching> + <latching>false</latching> <annunciating>false</annunciating> <guidance> <title>[Operator Action]</title> @@ -1178,7 +1187,7 @@ Call cryo on call </pv> <pv name="AccODH-AT:ODH-O2iM-007:AiBadValue"> <description>Oxygen level value is not valid</description> - <latching>true</latching> + <latching>false</latching> <annunciating>false</annunciating> <guidance> <title>[Operator Action]</title> @@ -1216,7 +1225,7 @@ Call cryo on call </pv> <pv name="AccODH-AT:ODH-O2iM-008:Maintenance"> <description>Monitor maintenance mode</description> - <latching>true</latching> + <latching>false</latching> <annunciating>false</annunciating> <guidance> <title>[Operator Action]</title> @@ -1245,7 +1254,7 @@ Call cryo on call </pv> <pv name="AccODH-AT:ODH-O2iM-008:AiBadValue"> <description>Oxygen level value is not valid</description> - <latching>true</latching> + <latching>false</latching> <annunciating>false</annunciating> <guidance> <title>[Operator Action]</title> @@ -1283,7 +1292,7 @@ Call cryo on call </pv> <pv name="AccODH-AT:ODH-O2iM-009:Maintenance"> <description>Monitor maintenance mode</description> - <latching>true</latching> + <latching>false</latching> <annunciating>false</annunciating> <guidance> <title>[Operator Action]</title> @@ -1312,7 +1321,7 @@ Call cryo on call </pv> <pv name="AccODH-AT:ODH-O2iM-009:AiBadValue"> <description>Oxygen level value is not valid</description> - <latching>true</latching> + <latching>false</latching> <annunciating>false</annunciating> <guidance> <title>[Operator Action]</title> @@ -1350,7 +1359,7 @@ Call cryo on call </pv> <pv name="AccODH-AT:ODH-O2iM-010:Maintenance"> <description>Monitor maintenance mode</description> - <latching>true</latching> + <latching>false</latching> <annunciating>false</annunciating> <guidance> <title>[Operator Action]</title> @@ -1379,7 +1388,7 @@ Call cryo on call </pv> <pv name="AccODH-AT:ODH-O2iM-010:AiBadValue"> <description>Oxygen level value is not valid</description> - <latching>true</latching> + <latching>false</latching> <annunciating>false</annunciating> <guidance> <title>[Operator Action]</title> @@ -1417,7 +1426,7 @@ Call cryo on call </pv> <pv name="AccODH-AT:ODH-O2iM-011:Maintenance"> <description>Monitor maintenance mode</description> - <latching>true</latching> + <latching>false</latching> <annunciating>false</annunciating> <guidance> <title>[Operator Action]</title> @@ -1446,7 +1455,7 @@ Call cryo on call </pv> <pv name="AccODH-AT:ODH-O2iM-011:AiBadValue"> <description>Oxygen level value is not valid</description> - <latching>true</latching> + <latching>false</latching> <annunciating>false</annunciating> <guidance> <title>[Operator Action]</title> @@ -1484,7 +1493,7 @@ Call cryo on call </pv> <pv name="AccODH-AT:ODH-O2iM-012:Maintenance"> <description>Monitor maintenance mode</description> - <latching>true</latching> + <latching>false</latching> <annunciating>false</annunciating> <guidance> <title>[Operator Action]</title> @@ -1513,7 +1522,7 @@ Call cryo on call </pv> <pv name="AccODH-AT:ODH-O2iM-012:AiBadValue"> <description>Oxygen level value is not valid</description> - <latching>true</latching> + <latching>false</latching> <annunciating>false</annunciating> <guidance> <title>[Operator Action]</title> @@ -1551,7 +1560,7 @@ Call cryo on call </pv> <pv name="AccODH-AT:ODH-O2iM-013:Maintenance"> <description>Monitor maintenance mode</description> - <latching>true</latching> + <latching>false</latching> <annunciating>false</annunciating> <guidance> <title>[Operator Action]</title> @@ -1580,7 +1589,7 @@ Call cryo on call </pv> <pv name="AccODH-AT:ODH-O2iM-013:AiBadValue"> <description>Oxygen level value is not valid</description> - <latching>true</latching> + <latching>false</latching> <annunciating>false</annunciating> <guidance> <title>[Operator Action]</title> @@ -1618,7 +1627,7 @@ Call cryo on call </pv> <pv name="AccODH-AT:ODH-O2iM-014:Maintenance"> <description>Monitor maintenance mode</description> - <latching>true</latching> + <latching>false</latching> <annunciating>false</annunciating> <guidance> <title>[Operator Action]</title> @@ -1647,7 +1656,7 @@ Call cryo on call </pv> <pv name="AccODH-AT:ODH-O2iM-014:AiBadValue"> <description>Oxygen level value is not valid</description> - <latching>true</latching> + <latching>false</latching> <annunciating>false</annunciating> <guidance> <title>[Operator Action]</title> @@ -2081,7 +2090,7 @@ Call cryo on call </pv> <pv name="CTLG-CS:ODH-Area:Attention"> <description>Zone minor issue</description> - <latching>true</latching> + <latching>false</latching> <annunciating>false</annunciating> <guidance> <title>[Operator Action]</title> @@ -2091,7 +2100,7 @@ Call cryo on call </pv> <pv name="CTLG-CS:ODH-Area:Maintenance"> <description>Zone oxygen monitor in maintenance mode</description> - <latching>true</latching> + <latching>false</latching> <annunciating>false</annunciating> <guidance> <title>[Operator Action]</title> @@ -2100,7 +2109,7 @@ Call cryo on call </pv> <pv name="CTLG-CS:ODH-Area:HwError"> <description>Zone PLC HW failure</description> - <latching>true</latching> + <latching>false</latching> <annunciating>false</annunciating> <guidance> <title>[Operator Action]</title> @@ -2110,7 +2119,7 @@ Call cryo on call </pv> <pv name="CTLG-CS:ODH-Area:ConfirmedAlrm"> <description>Zone ODH confirmed alarm</description> - <latching>true</latching> + <latching>false</latching> <annunciating>false</annunciating> <guidance> <title>[Operator Action]</title> @@ -2123,7 +2132,7 @@ Call cryo on call </pv> <pv name="CTLG-CS:ODH-Area:StartUp"> <description>Zone equipment starting-up</description> - <latching>true</latching> + <latching>false</latching> <annunciating>false</annunciating> <guidance> <title>[Operator Action]</title> @@ -2132,7 +2141,7 @@ Call cryo on call </pv> <pv name="CTLG-CS:ODH-Area:Muted"> <description>Zone audible alarm muted</description> - <latching>true</latching> + <latching>false</latching> <annunciating>false</annunciating> <guidance> <title>[Operator Action]</title> @@ -2169,7 +2178,7 @@ Call cryo on call </pv> <pv name="CTLG-CS:ODH-O2iM-20:Maintenance"> <description>Monitor maintenance mode</description> - <latching>true</latching> + <latching>false</latching> <annunciating>false</annunciating> <guidance> <title>[Operator Action]</title> @@ -2198,7 +2207,7 @@ Call cryo on call </pv> <pv name="CTLG-CS:ODH-O2iM-20:AiBadValue"> <description>Oxygen level value is not valid</description> - <latching>true</latching> + <latching>false</latching> <annunciating>false</annunciating> <guidance> <title>[Operator Action]</title> @@ -2236,7 +2245,7 @@ Call cryo on call </pv> <pv name="CTLG-CS:ODH-O2iM-21:Maintenance"> <description>Monitor maintenance mode</description> - <latching>true</latching> + <latching>false</latching> <annunciating>false</annunciating> <guidance> <title>[Operator Action]</title> @@ -2265,7 +2274,7 @@ Call cryo on call </pv> <pv name="CTLG-CS:ODH-O2iM-21:AiBadValue"> <description>Oxygen level value is not valid</description> - <latching>true</latching> + <latching>false</latching> <annunciating>false</annunciating> <guidance> <title>[Operator Action]</title> @@ -2303,7 +2312,7 @@ Call cryo on call </pv> <pv name="CTLG-CS:ODH-O2iM-22:Maintenance"> <description>Monitor maintenance mode</description> - <latching>true</latching> + <latching>false</latching> <annunciating>false</annunciating> <guidance> <title>[Operator Action]</title> @@ -2332,7 +2341,7 @@ Call cryo on call </pv> <pv name="CTLG-CS:ODH-O2iM-22:AiBadValue"> <description>Oxygen level value is not valid</description> - <latching>true</latching> + <latching>false</latching> <annunciating>false</annunciating> <guidance> <title>[Operator Action]</title> @@ -2382,7 +2391,7 @@ Call cryo on call </pv> <pv name="CXB-CXH:ODH-Area:Attention"> <description>Zone minor issue</description> - <latching>true</latching> + <latching>false</latching> <annunciating>false</annunciating> <guidance> <title>[Operator Action]</title> @@ -2392,7 +2401,7 @@ Call cryo on call </pv> <pv name="CXB-CXH:ODH-Area:Maintenance"> <description>Zone oxygen monitor in maintenance mode</description> - <latching>true</latching> + <latching>false</latching> <annunciating>false</annunciating> <guidance> <title>[Operator Action]</title> @@ -2401,7 +2410,7 @@ Call cryo on call </pv> <pv name="CXB-CXH:ODH-Area:HwError"> <description>Zone PLC HW failure</description> - <latching>true</latching> + <latching>false</latching> <annunciating>false</annunciating> <guidance> <title>[Operator Action]</title> @@ -2411,7 +2420,7 @@ Call cryo on call </pv> <pv name="CXB-CXH:ODH-Area:ConfirmedAlrm"> <description>Zone ODH confirmed alarm</description> - <latching>true</latching> + <latching>false</latching> <annunciating>false</annunciating> <guidance> <title>[Operator Action]</title> @@ -2424,7 +2433,7 @@ Call cryo on call </pv> <pv name="CXB-CXH:ODH-Area:StartUp"> <description>Zone equipment starting-up</description> - <latching>true</latching> + <latching>false</latching> <annunciating>false</annunciating> <guidance> <title>[Operator Action]</title> @@ -2433,7 +2442,7 @@ Call cryo on call </pv> <pv name="CXB-CXH:ODH-Area:Muted"> <description>Zone audible alarm muted</description> - <latching>true</latching> + <latching>false</latching> <annunciating>false</annunciating> <guidance> <title>[Operator Action]</title> @@ -2470,7 +2479,7 @@ Call cryo on call </pv> <pv name="CXB-CXH:ODH-O2iM-13:Maintenance"> <description>Monitor maintenance mode</description> - <latching>true</latching> + <latching>false</latching> <annunciating>false</annunciating> <guidance> <title>[Operator Action]</title> @@ -2499,7 +2508,7 @@ Call cryo on call </pv> <pv name="CXB-CXH:ODH-O2iM-13:AiBadValue"> <description>Oxygen level value is not valid</description> - <latching>true</latching> + <latching>false</latching> <annunciating>false</annunciating> <guidance> <title>[Operator Action]</title> @@ -2537,7 +2546,7 @@ Call cryo on call </pv> <pv name="CXB-CXH:ODH-O2iM-14:Maintenance"> <description>Monitor maintenance mode</description> - <latching>true</latching> + <latching>false</latching> <annunciating>false</annunciating> <guidance> <title>[Operator Action]</title> @@ -2566,7 +2575,7 @@ Call cryo on call </pv> <pv name="CXB-CXH:ODH-O2iM-14:AiBadValue"> <description>Oxygen level value is not valid</description> - <latching>true</latching> + <latching>false</latching> <annunciating>false</annunciating> <guidance> <title>[Operator Action]</title> @@ -2604,7 +2613,7 @@ Call cryo on call </pv> <pv name="CXB-CXH:ODH-O2iM-16:Maintenance"> <description>Monitor maintenance mode</description> - <latching>true</latching> + <latching>false</latching> <annunciating>false</annunciating> <guidance> <title>[Operator Action]</title> @@ -2633,7 +2642,7 @@ Call cryo on call </pv> <pv name="CXB-CXH:ODH-O2iM-16:AiBadValue"> <description>Oxygen level value is not valid</description> - <latching>true</latching> + <latching>false</latching> <annunciating>false</annunciating> <guidance> <title>[Operator Action]</title> @@ -2671,7 +2680,7 @@ Call cryo on call </pv> <pv name="CXB-CXH:ODH-O2iM-17:Maintenance"> <description>Monitor maintenance mode</description> - <latching>true</latching> + <latching>false</latching> <annunciating>false</annunciating> <guidance> <title>[Operator Action]</title> @@ -2700,7 +2709,7 @@ Call cryo on call </pv> <pv name="CXB-CXH:ODH-O2iM-17:AiBadValue"> <description>Oxygen level value is not valid</description> - <latching>true</latching> + <latching>false</latching> <annunciating>false</annunciating> <guidance> <title>[Operator Action]</title> @@ -2750,7 +2759,7 @@ Call cryo on call </pv> <pv name="HCB-DogSh:ODH-Area:Attention"> <description>Zone minor issue</description> - <latching>true</latching> + <latching>false</latching> <annunciating>false</annunciating> <guidance> <title>[Operator Action]</title> @@ -2760,7 +2769,7 @@ Call cryo on call </pv> <pv name="HCB-DogSh:ODH-Area:Maintenance"> <description>Zone oxygen monitor in maintenance mode</description> - <latching>true</latching> + <latching>false</latching> <annunciating>false</annunciating> <guidance> <title>[Operator Action]</title> @@ -2769,7 +2778,7 @@ Call cryo on call </pv> <pv name="HCB-DogSh:ODH-Area:HwError"> <description>Zone PLC HW failure</description> - <latching>true</latching> + <latching>false</latching> <annunciating>false</annunciating> <guidance> <title>[Operator Action]</title> @@ -2779,7 +2788,7 @@ Call cryo on call </pv> <pv name="HCB-DogSh:ODH-Area:ConfirmedAlrm"> <description>Zone ODH confirmed alarm</description> - <latching>true</latching> + <latching>false</latching> <annunciating>false</annunciating> <guidance> <title>[Operator Action]</title> @@ -2792,7 +2801,7 @@ Call cryo on call </pv> <pv name="HCB-DogSh:ODH-Area:StartUp"> <description>Zone equipment starting-up</description> - <latching>true</latching> + <latching>false</latching> <annunciating>false</annunciating> <guidance> <title>[Operator Action]</title> @@ -2801,7 +2810,7 @@ Call cryo on call </pv> <pv name="HCB-DogSh:ODH-Area:Muted"> <description>Zone audible alarm muted</description> - <latching>true</latching> + <latching>false</latching> <annunciating>false</annunciating> <guidance> <title>[Operator Action]</title> @@ -2838,7 +2847,7 @@ Call cryo on call </pv> <pv name="HCB-DogSh:ODH-O2iM-12:Maintenance"> <description>Monitor maintenance mode</description> - <latching>true</latching> + <latching>false</latching> <annunciating>false</annunciating> <guidance> <title>[Operator Action]</title> @@ -2867,7 +2876,7 @@ Call cryo on call </pv> <pv name="HCB-DogSh:ODH-O2iM-12:AiBadValue"> <description>Oxygen level value is not valid</description> - <latching>true</latching> + <latching>false</latching> <annunciating>false</annunciating> <guidance> <title>[Operator Action]</title> @@ -2917,7 +2926,7 @@ Call cryo on call </pv> <pv name="HCB-ACH:ODH-Area:Attention"> <description>Zone minor issue</description> - <latching>true</latching> + <latching>false</latching> <annunciating>false</annunciating> <guidance> <title>[Operator Action]</title> @@ -2927,7 +2936,7 @@ Call cryo on call </pv> <pv name="HCB-ACH:ODH-Area:Maintenance"> <description>Zone oxygen monitor in maintenance mode</description> - <latching>true</latching> + <latching>false</latching> <annunciating>false</annunciating> <guidance> <title>[Operator Action]</title> @@ -2936,7 +2945,7 @@ Call cryo on call </pv> <pv name="HCB-ACH:ODH-Area:HwError"> <description>Zone PLC HW failure</description> - <latching>true</latching> + <latching>false</latching> <annunciating>false</annunciating> <guidance> <title>[Operator Action]</title> @@ -2946,7 +2955,7 @@ Call cryo on call </pv> <pv name="HCB-ACH:ODH-Area:ConfirmedAlrm"> <description>Zone ODH confirmed alarm</description> - <latching>true</latching> + <latching>false</latching> <annunciating>false</annunciating> <guidance> <title>[Operator Action]</title> @@ -2959,7 +2968,7 @@ Call cryo on call </pv> <pv name="HCB-ACH:ODH-Area:StartUp"> <description>Zone equipment starting-up</description> - <latching>true</latching> + <latching>false</latching> <annunciating>false</annunciating> <guidance> <title>[Operator Action]</title> @@ -2968,7 +2977,7 @@ Call cryo on call </pv> <pv name="HCB-ACH:ODH-Area:Muted"> <description>Zone audible alarm muted</description> - <latching>true</latching> + <latching>false</latching> <annunciating>false</annunciating> <guidance> <title>[Operator Action]</title> @@ -3005,7 +3014,7 @@ Call cryo on call </pv> <pv name="HCB-ACH:ODH-O2iM-2:Maintenance"> <description>Monitor maintenance mode</description> - <latching>true</latching> + <latching>false</latching> <annunciating>false</annunciating> <guidance> <title>[Operator Action]</title> @@ -3034,7 +3043,7 @@ Call cryo on call </pv> <pv name="HCB-ACH:ODH-O2iM-2:AiBadValue"> <description>Oxygen level value is not valid</description> - <latching>true</latching> + <latching>false</latching> <annunciating>false</annunciating> <guidance> <title>[Operator Action]</title> @@ -3072,7 +3081,7 @@ Call cryo on call </pv> <pv name="HCB-ACH:ODH-O2iM-3:Maintenance"> <description>Monitor maintenance mode</description> - <latching>true</latching> + <latching>false</latching> <annunciating>false</annunciating> <guidance> <title>[Operator Action]</title> @@ -3101,7 +3110,7 @@ Call cryo on call </pv> <pv name="HCB-ACH:ODH-O2iM-3:AiBadValue"> <description>Oxygen level value is not valid</description> - <latching>true</latching> + <latching>false</latching> <annunciating>false</annunciating> <guidance> <title>[Operator Action]</title> @@ -3139,7 +3148,7 @@ Call cryo on call </pv> <pv name="HCB-ACH:ODH-O2iM-4:Maintenance"> <description>Monitor maintenance mode</description> - <latching>true</latching> + <latching>false</latching> <annunciating>false</annunciating> <guidance> <title>[Operator Action]</title> @@ -3168,7 +3177,7 @@ Call cryo on call </pv> <pv name="HCB-ACH:ODH-O2iM-4:AiBadValue"> <description>Oxygen level value is not valid</description> - <latching>true</latching> + <latching>false</latching> <annunciating>false</annunciating> <guidance> <title>[Operator Action]</title> @@ -3206,7 +3215,7 @@ Call cryo on call </pv> <pv name="HCB-ACH:ODH-O2iM-5:Maintenance"> <description>Monitor maintenance mode</description> - <latching>true</latching> + <latching>false</latching> <annunciating>false</annunciating> <guidance> <title>[Operator Action]</title> @@ -3235,7 +3244,7 @@ Call cryo on call </pv> <pv name="HCB-ACH:ODH-O2iM-5:AiBadValue"> <description>Oxygen level value is not valid</description> - <latching>true</latching> + <latching>false</latching> <annunciating>false</annunciating> <guidance> <title>[Operator Action]</title> @@ -3273,7 +3282,7 @@ Call cryo on call </pv> <pv name="HCB-TCH:ODH-O2iM-6:Maintenance"> <description>Monitor maintenance mode</description> - <latching>true</latching> + <latching>false</latching> <annunciating>false</annunciating> <guidance> <title>[Operator Action]</title> @@ -3302,7 +3311,7 @@ Call cryo on call </pv> <pv name="HCB-TCH:ODH-O2iM-6:AiBadValue"> <description>Oxygen level value is not valid</description> - <latching>true</latching> + <latching>false</latching> <annunciating>false</annunciating> <guidance> <title>[Operator Action]</title> @@ -3340,7 +3349,7 @@ Call cryo on call </pv> <pv name="HCB-TCH:ODH-O2iM-8:Maintenance"> <description>Monitor maintenance mode</description> - <latching>true</latching> + <latching>false</latching> <annunciating>false</annunciating> <guidance> <title>[Operator Action]</title> @@ -3369,7 +3378,7 @@ Call cryo on call </pv> <pv name="HCB-TCH:ODH-O2iM-8:AiBadValue"> <description>Oxygen level value is not valid</description> - <latching>true</latching> + <latching>false</latching> <annunciating>false</annunciating> <guidance> <title>[Operator Action]</title> @@ -3407,7 +3416,7 @@ Call cryo on call </pv> <pv name="HCB-TCH:ODH-O2iM-9:Maintenance"> <description>Monitor maintenance mode</description> - <latching>true</latching> + <latching>false</latching> <annunciating>false</annunciating> <guidance> <title>[Operator Action]</title> @@ -3436,7 +3445,7 @@ Call cryo on call </pv> <pv name="HCB-TCH:ODH-O2iM-9:AiBadValue"> <description>Oxygen level value is not valid</description> - <latching>true</latching> + <latching>false</latching> <annunciating>false</annunciating> <guidance> <title>[Operator Action]</title> @@ -3474,7 +3483,7 @@ Call cryo on call </pv> <pv name="HCB-HPGS:ODH-O2iM-10:Maintenance"> <description>Monitor maintenance mode</description> - <latching>true</latching> + <latching>false</latching> <annunciating>false</annunciating> <guidance> <title>[Operator Action]</title> @@ -3503,7 +3512,7 @@ Call cryo on call </pv> <pv name="HCB-HPGS:ODH-O2iM-10:AiBadValue"> <description>Oxygen level value is not valid</description> - <latching>true</latching> + <latching>false</latching> <annunciating>false</annunciating> <guidance> <title>[Operator Action]</title> @@ -3553,7 +3562,7 @@ Call cryo on call </pv> <pv name="KG-GTA:ODH-Area-001:Attention"> <description>Zone minor issue</description> - <latching>true</latching> + <latching>false</latching> <annunciating>false</annunciating> <guidance> <title>[Operator Action]</title> @@ -3563,7 +3572,7 @@ Call cryo on call </pv> <pv name="KG-GTA:ODH-Area-001:Maintenance"> <description>Zone oxygen monitor in maintenance mode</description> - <latching>true</latching> + <latching>false</latching> <annunciating>false</annunciating> <guidance> <title>[Operator Action]</title> @@ -3572,7 +3581,7 @@ Call cryo on call </pv> <pv name="KG-GTA:ODH-Area-001:HwError"> <description>Zone PLC HW failure</description> - <latching>true</latching> + <latching>false</latching> <annunciating>false</annunciating> <guidance> <title>[Operator Action]</title> @@ -3582,7 +3591,7 @@ Call cryo on call </pv> <pv name="KG-GTA:ODH-Area-001:ConfirmedAlrm"> <description>Zone ODH confirmed alarm</description> - <latching>true</latching> + <latching>false</latching> <annunciating>false</annunciating> <guidance> <title>[Operator Action]</title> @@ -3595,7 +3604,7 @@ Call cryo on call </pv> <pv name="KG-GTA:ODH-Area-001:StartUp"> <description>Zone equipment starting-up</description> - <latching>true</latching> + <latching>false</latching> <annunciating>false</annunciating> <guidance> <title>[Operator Action]</title> @@ -3604,7 +3613,7 @@ Call cryo on call </pv> <pv name="KG-GTA:ODH-Area-001:Muted"> <description>Zone audible alarm muted</description> - <latching>true</latching> + <latching>false</latching> <annunciating>false</annunciating> <guidance> <title>[Operator Action]</title> @@ -3641,7 +3650,7 @@ Call cryo on call </pv> <pv name="KG-GTA:ODH-O2iM-23:Maintenance"> <description>Monitor maintenance mode</description> - <latching>true</latching> + <latching>false</latching> <annunciating>false</annunciating> <guidance> <title>[Operator Action]</title> @@ -3670,7 +3679,7 @@ Call cryo on call </pv> <pv name="KG-GTA:ODH-O2iM-23:AiBadValue"> <description>Oxygen level value is not valid</description> - <latching>true</latching> + <latching>false</latching> <annunciating>false</annunciating> <guidance> <title>[Operator Action]</title> @@ -3708,7 +3717,7 @@ Call cryo on call </pv> <pv name="KG-GTA:ODH-O2iM-24:Maintenance"> <description>Monitor maintenance mode</description> - <latching>true</latching> + <latching>false</latching> <annunciating>false</annunciating> <guidance> <title>[Operator Action]</title> @@ -3737,7 +3746,7 @@ Call cryo on call </pv> <pv name="KG-GTA:ODH-O2iM-24:AiBadValue"> <description>Oxygen level value is not valid</description> - <latching>true</latching> + <latching>false</latching> <annunciating>false</annunciating> <guidance> <title>[Operator Action]</title> -- GitLab