diff --git a/alarm-01.tn.esss.lu.se/LCR.xml b/alarm-01.tn.esss.lu.se/LCR.xml index 279e3ca7590c8b0a67ba4394ae55170f8ef564e1..e4b16f3fa7ea6c21e35c55dc96d40a0603ae82e0 100644 --- a/alarm-01.tn.esss.lu.se/LCR.xml +++ b/alarm-01.tn.esss.lu.se/LCR.xml @@ -630,4 +630,6204 @@ </pv> </component> </component> + <component name="LINAC"> + <component name="CTL"> + <pv name="CrS-CTL::VacNotOK"> + <description>CTL ISO Vacuum is bad</description> + <latching>true</latching> + <annunciating>true</annunciating> + <guidance> + <title>[Cryo Operator Action]</title> + <details>contact CRYO on-call, bad iso-vacuum in the CTL</details> + </guidance> + </pv> + </component> + <component name="SHL"> + <pv name="CrS-SHC::GlobalAlarm"> + <description>Global alarm on Safety Helium Collector</description> + <latching>true</latching> + <annunciating>true</annunciating> + <guidance> + <title>[Cryo Operator Action]</title> + <details>contact CRYO on-call, Global alarm in Safety Helium Collector (check status of valves)</details> + </guidance> + </pv> + </component> + <component name="End Box"> + <pv name="Spk-000CDL:Cryo-LT-91:HIHI"> + <description>LT-91 helium level extremely high</description> + <latching>true</latching> + <annunciating>true</annunciating> + <guidance> + <title>[Cryo Operator Action]</title> + <details>contact CRYO on-call and inform SCL on-call, Cryomodule liquid level too high (check the other gauge LT-92). </details> + </guidance> + </pv> + <pv name="Spk-000CDL:Cryo-LT-92:HIHI"> + <description>LT-92 helium level extremely high</description> + <latching>true</latching> + <annunciating>true</annunciating> + <guidance> + <title>[Cryo Operator Action]</title> + <details>contact CRYO on-call and inform SCL on-call, Cryomodule liquid level too high (check the other gauge LT-91). </details> + </guidance> + </pv> + </component> + <component name="Cryomodules\SPK-010 Cryomodule"> + <pv name="Spk-010Crm:Cryo-LT-001:HIHI"> + <description>LT-001 helium level extremely high</description> + <latching>true</latching> + <annunciating>true</annunciating> + <guidance> + <title>[Cryo Operator Action]</title> + <details>contact CRYO on-call and inform SCL on-call, Cryomodule liquid level too high (check the other gauge LT-002). Close supply valve CV01, CV02</details> + </guidance> + </pv> + <pv name="Spk-010Crm:Cryo-LT-002:HIHI"> + <description>LT-002 helium level extremely high</description> + <latching>true</latching> + <annunciating>true</annunciating> + <guidance> + <title>[Cryo Operator Action]</title> + <details>contact CRYO on-call and inform SCL on-call, Cryomodule liquid level too high (check the other gauge LT-001). Close supply valve CV01, CV02</details> + </guidance> + </pv> + <pv name="Spk-010Crm:Cryo-LT-001:HI"> + <description>LT-001 helium level high</description> + <latching>true</latching> + <annunciating>true</annunciating> + <guidance> + <title>[Cryo Operator Action]</title> + <details>contact CRYO on-call and inform SCL on-call, Cryomodule liquid level high (check the other gauge LT-002). Check level regulation valve settings, if needed: adjust LMN_LO and if necessary: Close supply valve CV01, CV02</details> + </guidance> + </pv> + <pv name="Spk-010Crm:Cryo-LT-002:HI"> + <description>LT-002 helium level high</description> + <latching>true</latching> + <annunciating>true</annunciating> + <guidance> + <title>[Cryo Operator Action]</title> + <details>contact CRYO on-call and inform SCL on-call, Cryomodule liquid level high (check the other gauge LT-002). Check level regulation valve settings, if needed: adjust LMN_LO and if necessary: Close supply valve CV01, CV02</details> + </guidance> + </pv> + <pv name="Spk-010Crm:Cryo-LT-001:LO"> + <description>LT-001 helium level low</description> + <latching>true</latching> + <annunciating>true</annunciating> + <guidance> + <title>[Cryo Operator Action]</title> + <details>contact CRYO on-call and inform SCL on-call, Cryomodule liquid level low (check the other gauge LT-001). Check level regulation valve settings, if needed: adjust LMN_HI</details> + </guidance> + </pv> + <pv name="Spk-010Crm:Cryo-LT-002:LO"> + <description>LT-002 helium level low</description> + <latching>true</latching> + <annunciating>true</annunciating> + <guidance> + <title>[Cryo Operator Action]</title> + <details>contact CRYO on-call and inform SCL on-call, Cryomodule liquid level low (check the other gauge LT-002). Check level regulation valvesettings, if needed: adjust LMN_HI</details> + </guidance> + </pv> + <pv name="Spk-010Crm:Cryo-LT-001:LOLO"> + <description>LT-002 helium level extremely low</description> + <latching>true</latching> + <annunciating>true</annunciating> + <guidance> + <title>[Cryo Operator Action]</title> + <details>contact CRYO on-call and inform SCL on-call, Cryomodule liquid level too low (check the other gauge LT-001). Check level regulation valve settings, if needed: adjust LMN_HI</details> + </guidance> + </pv> + <pv name="Spk-010Crm:Cryo-LT-002:LOLO"> + <description>LT-002 helium level extremely low</description> + <latching>true</latching> + <annunciating>true</annunciating> + <guidance> + <title>[Cryo Operator Action]</title> + <details>contact CRYO on-call and inform SCL on-call, Cryomodule liquid level too low (check the other gauge LT-002). Check level regulation valvesettings, if needed: adjust LMN_HI</details> + </guidance> + </pv> + <pv name="Spk-010Crm:Cryo-PT-003:HIHI"> + <description>Cavity tanks pressure is too high (typical value is 31mbar in 2K mode and 1050mbar in 4K mode)</description> + <latching>true</latching> + <annunciating>true</annunciating> + <guidance> + <title>[Cryo Operator Action]</title> + <details>contact CRYO on-call and inform SCL on-call, Cryomodule bath pressure too high (check the other gauge PT002). Close supply valve CV01, CV02 if necessary</details> + </guidance> + </pv> + <pv name="Spk-010Crm:Cryo-PT-003:Cable_Error"> + <description>Cavity tanks Pressure Sensor cables are disconnected</description> + <latching>true</latching> + <annunciating>true</annunciating> + <guidance> + <title>[Cryo Operator Action]</title> + <details>contact CRYO on-call and inform SCL on-call, Cryomodule pressure cable seems disconnected (value gets stuck), assign PT002 as measuring device on CV04 and CV-090 </details> + </guidance> + </pv> + <pv name="Spk-010Crm:Cryo-PT-002:HIHI"> + <description>Cavity tanks pressure is too high (typical value is 31mbar in 2K mode and 1050mbar in 4K mode)</description> + <latching>true</latching> + <annunciating>true</annunciating> + <guidance> + <title>[Cryo Operator Action]</title> + <details>contact CRYO on-call and inform SCL on-call,, Cryomodule bath pressure too high (check the other gauge PT003). Close supply valve CV01, CV02 if necessary</details> + </guidance> + </pv> + <pv name="Spk-010Crm:Cryo-PT-002:Cable_Error"> + <description>Cavity tanks Pressure Sensor cables are disconnected</description> + <latching>true</latching> + <annunciating>true</annunciating> + <guidance> + <title>[Cryo Operator Action]</title> + <details>contact CRYO on-call and inform SCL on-call, Cryomodule pressure cable seems disconnected (value gets stuck), assign PT003 as measuring device on CV04 and CV-090 </details> + </guidance> + </pv> + <pv name="Spk-010Crm:Cryo-TT-120:P_Limit_LO"> + <description>Power coupler flange temperature low</description> + <latching>true</latching> + <annunciating>true</annunciating> + <guidance> + <title>[Cryo Operator Action]</title> + <details>contact CRYO on-call and inform SCL on-call, power coupler flange temperature is low, check heater output, if nominal then coupler flow needs to be adjusted (reduced)</details> + </guidance> + </pv> + <pv name="Spk-010Crm:Cryo-TT-120:P_Limit_LOLO"> + <description>Power coupler flange temperature too low</description> + <latching>true</latching> + <annunciating>true</annunciating> + <guidance> + <title>[Cryo Operator Action]</title> + <details>contact CRYO on-call and inform SCL on-call, power coupler flange temperature is too low, check heater output, if nominal then coupler flow needs to be adjusted (reduced)</details> + </guidance> + </pv> + <pv name="Spk-010Crm:Cryo-TT-120:P_Limit_HIHI"> + <description>Power coupler flange temperature too high</description> + <latching>true</latching> + <annunciating>true</annunciating> + <guidance> + <title>[Cryo Operator Action]</title> + <details>contact CRYO on-call and inform SCL on-call, power coupler flange temperature is too high, check heater output, if nominal then coupler flow needs to be adjusted (reduced)</details> + </guidance> + </pv> + <pv name="Spk-010Crm:Cryo-TT-220:P_Limit_LO"> + <description>Power coupler flange temperature low</description> + <latching>true</latching> + <annunciating>true</annunciating> + <guidance> + <title>[Cryo Operator Action]</title> + <details>contact CRYO on-call and inform SCL on-call, power coupler flange temperature is low, check heater output, if nominal then coupler flow needs to be adjusted (reduced)</details> + </guidance> + </pv> + <pv name="Spk-010Crm:Cryo-TT-220:P_Limit_LOLO"> + <description>Power coupler flange temperature too low</description> + <latching>true</latching> + <annunciating>true</annunciating> + <guidance> + <title>[Cryo Operator Action]</title> + <details>contact CRYO on-call and inform SCL on-call, power coupler flange temperature is too low, check heater output, if nominal then coupler flow needs to be adjusted (reduced)</details> + </guidance> + </pv> + <pv name="Spk-010Crm:Cryo-TT-220:P_Limit_HIHI"> + <description>Power coupler flange temperature too high</description> + <latching>true</latching> + <annunciating>true</annunciating> + <guidance> + <title>[Cryo Operator Action]</title> + <details>contact CRYO on-call and inform SCL on-call, power coupler flange temperature is too high, check heater output, if nominal then coupler flow needs to be adjusted (reduced)</details> + </guidance> + </pv> + <pv name="Spk-010Crm:WtrC-FS-013:Flow_OK_WF"> + <description>! Alarm when signal drops from 1 to zero. No Water Flow Antenna 1</description> + <latching>true</latching> + <annunciating>true</annunciating> + <guidance> + <title>[Cryo Operator Action]</title> + <details>contact CRYO on-call and inform SCL on-call, assure Flange temperature TT-120 is correct. Risk of Water freeze if no flow and temperature too low</details> + </guidance> + </pv> + <pv name="Spk-010Crm:WtrC-FS-014:Flow_OK_WF"> + <description>! Alarm when signal drops from 1 to zero. No Water Flow Window 1</description> + <latching>true</latching> + <annunciating>true</annunciating> + <guidance> + <title>[Cryo Operator Action]</title> + <details>contact CRYO on-call and inform SCL on-call, assure Flange temperature TT-120 is correct. Risk of Water freeze if no flow and temperature too low</details> + </guidance> + </pv> + <pv name="Spk-010Crm:WtrC-FS-023:Flow_OK_WF"> + <description>! Alarm when signal drops from 1 to zero. No Water Flow Antenna 2</description> + <latching>true</latching> + <annunciating>true</annunciating> + <guidance> + <title>[Cryo Operator Action]</title> + <details>contact CRYO on-call and inform SCL on-call, assure Flange temperature TT-120 is correct. Risk of Water freeze if no flow and temperature too low</details> + </guidance> + </pv> + <pv name="Spk-010Crm:WtrC-FS-024:Flow_OK_WF"> + <description>! Alarm when signal drops from 1 to zero. No Water Flow Window 2</description> + <latching>true</latching> + <annunciating>true</annunciating> + <guidance> + <title>[Cryo Operator Action]</title> + <details>contact CRYO on-call and inform SCL on-call, assure Flange temperature TT-120 is correct. Risk of Water freeze if no flow and temperature too low</details> + </guidance> + </pv> + </component> + <component name="Cryomodules\SPK-020 Cryomodule"> + <pv name="Spk-020Crm:Cryo-LT-001:HIHI"> + <description>LT-001 helium level extremely high</description> + <latching>true</latching> + <annunciating>true</annunciating> + <guidance> + <title>[Cryo Operator Action]</title> + <details>contact CRYO on-call and inform SCL on-call, Cryomodule liquid level too high (check the other gauge LT-002). Close supply valve CV01, CV02</details> + </guidance> + </pv> + <pv name="Spk-020Crm:Cryo-LT-002:HIHI"> + <description>LT-002 helium level extremely high</description> + <latching>true</latching> + <annunciating>true</annunciating> + <guidance> + <title>[Cryo Operator Action]</title> + <details>contact CRYO on-call and inform SCL on-call, Cryomodule liquid level too high (check the other gauge LT-001). Close supply valve CV01, CV02</details> + </guidance> + </pv> + <pv name="Spk-020Crm:Cryo-LT-001:HI"> + <description>LT-001 helium level high</description> + <latching>true</latching> + <annunciating>true</annunciating> + <guidance> + <title>[Cryo Operator Action]</title> + <details>contact CRYO on-call and inform SCL on-call, Cryomodule liquid level high (check the other gauge LT-002). Check level regulation valve settings, if needed: adjust LMN_LO and if necessary: Close supply valve CV01, CV02</details> + </guidance> + </pv> + <pv name="Spk-020Crm:Cryo-LT-002:HI"> + <description>LT-002 helium level high</description> + <latching>true</latching> + <annunciating>true</annunciating> + <guidance> + <title>[Cryo Operator Action]</title> + <details>contact CRYO on-call and inform SCL on-call, Cryomodule liquid level high (check the other gauge LT-002). Check level regulation valve settings, if needed: adjust LMN_LO and if necessary: Close supply valve CV01, CV02</details> + </guidance> + </pv> + <pv name="Spk-020Crm:Cryo-LT-001:LO"> + <description>LT-001 helium level low</description> + <latching>true</latching> + <annunciating>true</annunciating> + <guidance> + <title>[Cryo Operator Action]</title> + <details>contact CRYO on-call and inform SCL on-call, Cryomodule liquid level low (check the other gauge LT-001). Check level regulation valve settings, if needed: adjust LMN_HI</details> + </guidance> + </pv> + <pv name="Spk-020Crm:Cryo-LT-002:LO"> + <description>LT-002 helium level low</description> + <latching>true</latching> + <annunciating>true</annunciating> + <guidance> + <title>[Cryo Operator Action]</title> + <details>contact CRYO on-call and inform SCL on-call, Cryomodule liquid level low (check the other gauge LT-002). Check level regulation valvesettings, if needed: adjust LMN_HI</details> + </guidance> + </pv> + <pv name="Spk-020Crm:Cryo-LT-001:LOLO"> + <description>LT-002 helium level extremely low</description> + <latching>true</latching> + <annunciating>true</annunciating> + <guidance> + <title>[Cryo Operator Action]</title> + <details>contact CRYO on-call and inform SCL on-call, Cryomodule liquid level too low (check the other gauge LT-001). Check level regulation valve settings, if needed: adjust LMN_HI</details> + </guidance> + </pv> + <pv name="Spk-020Crm:Cryo-LT-002:LOLO"> + <description>LT-002 helium level extremely low</description> + <latching>true</latching> + <annunciating>true</annunciating> + <guidance> + <title>[Cryo Operator Action]</title> + <details>contact CRYO on-call and inform SCL on-call, Cryomodule liquid level too low (check the other gauge LT-002). Check level regulation valvesettings, if needed: adjust LMN_HI</details> + </guidance> + </pv> + <pv name="Spk-020Crm:Cryo-PT-003:HIHI"> + <description>Cavity tanks pressure is too high (typical value is 31mbar in 2K mode and 1050mbar in 4K mode)</description> + <latching>true</latching> + <annunciating>true</annunciating> + <guidance> + <title>[Cryo Operator Action]</title> + <details>contact CRYO on-call and inform SCL on-call, Cryomodule bath pressure too high (check the other gauge PT002). Close supply valve CV01, CV02 if necessary</details> + </guidance> + </pv> + <pv name="Spk-020Crm:Cryo-PT-003:Cable_Error"> + <description>Cavity tanks Pressure Sensor cables are disconnected</description> + <latching>true</latching> + <annunciating>true</annunciating> + <guidance> + <title>[Cryo Operator Action]</title> + <details>contact CRYO on-call and inform SCL on-call, Cryomodule pressure cable seems disconnected (value gets stuck), assign PT002 as measuring device on CV04 and CV-090 </details> + </guidance> + </pv> + <pv name="Spk-020Crm:Cryo-PT-002:HIHI"> + <description>Cavity tanks pressure is too high (typical value is 31mbar in 2K mode and 1050mbar in 4K mode)</description> + <latching>true</latching> + <annunciating>true</annunciating> + <guidance> + <title>[Cryo Operator Action]</title> + <details>contact CRYO on-call and inform SCL on-call,, Cryomodule bath pressure too high (check the other gauge PT003). Close supply valve CV01, CV02 if necessary</details> + </guidance> + </pv> + <pv name="Spk-020Crm:Cryo-PT-002:Cable_Error"> + <description>Cavity tanks Pressure Sensor cables are disconnected</description> + <latching>true</latching> + <annunciating>true</annunciating> + <guidance> + <title>[Cryo Operator Action]</title> + <details>contact CRYO on-call and inform SCL on-call, Cryomodule pressure cable seems disconnected (value gets stuck), assign PT003 as measuring device on CV04 and CV-090 </details> + </guidance> + </pv> + <pv name="Spk-020Crm:Cryo-TT-120:P_Limit_LO"> + <description>Power coupler flange temperature low</description> + <latching>true</latching> + <annunciating>true</annunciating> + <guidance> + <title>[Cryo Operator Action]</title> + <details>contact CRYO on-call and inform SCL on-call, power coupler flange temperature is low, check heater output, if nominal then coupler flow needs to be adjusted (reduced)</details> + </guidance> + </pv> + <pv name="Spk-020Crm:Cryo-TT-120:P_Limit_LOLO"> + <description>Power coupler flange temperature too low</description> + <latching>true</latching> + <annunciating>true</annunciating> + <guidance> + <title>[Cryo Operator Action]</title> + <details>contact CRYO on-call and inform SCL on-call, power coupler flange temperature is too low, check heater output, if nominal then coupler flow needs to be adjusted (reduced)</details> + </guidance> + </pv> + <pv name="Spk-020Crm:Cryo-TT-120:P_Limit_HIHI"> + <description>Power coupler flange temperature too high</description> + <latching>true</latching> + <annunciating>true</annunciating> + <guidance> + <title>[Cryo Operator Action]</title> + <details>contact CRYO on-call and inform SCL on-call, power coupler flange temperature is too high, check heater output, if nominal then coupler flow needs to be adjusted (reduced)</details> + </guidance> + </pv> + <pv name="Spk-020Crm:Cryo-TT-220:P_Limit_LO"> + <description>Power coupler flange temperature low</description> + <latching>true</latching> + <annunciating>true</annunciating> + <guidance> + <title>[Cryo Operator Action]</title> + <details>contact CRYO on-call and inform SCL on-call, power coupler flange temperature is low, check heater output, if nominal then coupler flow needs to be adjusted (reduced)</details> + </guidance> + </pv> + <pv name="Spk-020Crm:Cryo-TT-220:P_Limit_LOLO"> + <description>Power coupler flange temperature too low</description> + <latching>true</latching> + <annunciating>true</annunciating> + <guidance> + <title>[Cryo Operator Action]</title> + <details>contact CRYO on-call and inform SCL on-call, power coupler flange temperature is too low, check heater output, if nominal then coupler flow needs to be adjusted (reduced)</details> + </guidance> + </pv> + <pv name="Spk-020Crm:Cryo-TT-220:P_Limit_HIHI"> + <description>Power coupler flange temperature too high</description> + <latching>true</latching> + <annunciating>true</annunciating> + <guidance> + <title>[Cryo Operator Action]</title> + <details>contact CRYO on-call and inform SCL on-call, power coupler flange temperature is too high, check heater output, if nominal then coupler flow needs to be adjusted (reduced)</details> + </guidance> + </pv> + <pv name="Spk-020Crm:WtrC-FS-013:Flow_OK_WF"> + <description>! Alarm when signal drops from 1 to zero. No Water Flow Antenna 1</description> + <latching>true</latching> + <annunciating>true</annunciating> + <guidance> + <title>[Cryo Operator Action]</title> + <details>contact CRYO on-call and inform SCL on-call, assure Flange temperature TT-120 is correct. Risk of Water freeze if no flow and temperature too low</details> + </guidance> + </pv> + <pv name="Spk-020Crm:WtrC-FS-014:Flow_OK_WF"> + <description>! Alarm when signal drops from 1 to zero. No Water Flow Window 1</description> + <latching>true</latching> + <annunciating>true</annunciating> + <guidance> + <title>[Cryo Operator Action]</title> + <details>contact CRYO on-call and inform SCL on-call, assure Flange temperature TT-120 is correct. Risk of Water freeze if no flow and temperature too low</details> + </guidance> + </pv> + <pv name="Spk-020Crm:WtrC-FS-023:Flow_OK_WF"> + <description>! Alarm when signal drops from 1 to zero. No Water Flow Antenna 2</description> + <latching>true</latching> + <annunciating>true</annunciating> + <guidance> + <title>[Cryo Operator Action]</title> + <details>contact CRYO on-call and inform SCL on-call, assure Flange temperature TT-120 is correct. Risk of Water freeze if no flow and temperature too low</details> + </guidance> + </pv> + <pv name="Spk-020Crm:WtrC-FS-024:Flow_OK_WF"> + <description>! Alarm when signal drops from 1 to zero. No Water Flow Window 2</description> + <latching>true</latching> + <annunciating>true</annunciating> + <guidance> + <title>[Cryo Operator Action]</title> + <details>contact CRYO on-call and inform SCL on-call, assure Flange temperature TT-120 is correct. Risk of Water freeze if no flow and temperature too low</details> + </guidance> + </pv> + </component> + <component name="Cryomodules\SPK-030 Cryomodule"> + <pv name="Spk-030Crm:Cryo-LT-001:HIHI"> + <description>LT-001 helium level extremely high</description> + <latching>true</latching> + <annunciating>true</annunciating> + <guidance> + <title>[Cryo Operator Action]</title> + <details>contact CRYO on-call and inform SCL on-call, Cryomodule liquid level too high (check the other gauge LT-002). Close supply valve CV01, CV02</details> + </guidance> + </pv> + <pv name="Spk-030Crm:Cryo-LT-002:HIHI"> + <description>LT-002 helium level extremely high</description> + <latching>true</latching> + <annunciating>true</annunciating> + <guidance> + <title>[Cryo Operator Action]</title> + <details>contact CRYO on-call and inform SCL on-call, Cryomodule liquid level too high (check the other gauge LT-001). Close supply valve CV01, CV02</details> + </guidance> + </pv> + <pv name="Spk-030Crm:Cryo-LT-001:HI"> + <description>LT-001 helium level high</description> + <latching>true</latching> + <annunciating>true</annunciating> + <guidance> + <title>[Cryo Operator Action]</title> + <details>contact CRYO on-call and inform SCL on-call, Cryomodule liquid level high (check the other gauge LT-002). Check level regulation valve settings, if needed: adjust LMN_LO and if necessary: Close supply valve CV01, CV02</details> + </guidance> + </pv> + <pv name="Spk-030Crm:Cryo-LT-002:HI"> + <description>LT-002 helium level high</description> + <latching>true</latching> + <annunciating>true</annunciating> + <guidance> + <title>[Cryo Operator Action]</title> + <details>contact CRYO on-call and inform SCL on-call, Cryomodule liquid level high (check the other gauge LT-002). Check level regulation valve settings, if needed: adjust LMN_LO and if necessary: Close supply valve CV01, CV02</details> + </guidance> + </pv> + <pv name="Spk-030Crm:Cryo-LT-001:LO"> + <description>LT-001 helium level low</description> + <latching>true</latching> + <annunciating>true</annunciating> + <guidance> + <title>[Cryo Operator Action]</title> + <details>contact CRYO on-call and inform SCL on-call, Cryomodule liquid level low (check the other gauge LT-001). Check level regulation valve settings, if needed: adjust LMN_HI</details> + </guidance> + </pv> + <pv name="Spk-030Crm:Cryo-LT-002:LO"> + <description>LT-002 helium level low</description> + <latching>true</latching> + <annunciating>true</annunciating> + <guidance> + <title>[Cryo Operator Action]</title> + <details>contact CRYO on-call and inform SCL on-call, Cryomodule liquid level low (check the other gauge LT-002). Check level regulation valvesettings, if needed: adjust LMN_HI</details> + </guidance> + </pv> + <pv name="Spk-030Crm:Cryo-LT-001:LOLO"> + <description>LT-002 helium level extremely low</description> + <latching>true</latching> + <annunciating>true</annunciating> + <guidance> + <title>[Cryo Operator Action]</title> + <details>contact CRYO on-call and inform SCL on-call, Cryomodule liquid level too low (check the other gauge LT-001). Check level regulation valve settings, if needed: adjust LMN_HI</details> + </guidance> + </pv> + <pv name="Spk-030Crm:Cryo-LT-002:LOLO"> + <description>LT-002 helium level extremely low</description> + <latching>true</latching> + <annunciating>true</annunciating> + <guidance> + <title>[Cryo Operator Action]</title> + <details>contact CRYO on-call and inform SCL on-call, Cryomodule liquid level too low (check the other gauge LT-002). Check level regulation valvesettings, if needed: adjust LMN_HI</details> + </guidance> + </pv> + <pv name="Spk-030Crm:Cryo-PT-003:HIHI"> + <description>Cavity tanks pressure is too high (typical value is 31mbar in 2K mode and 1050mbar in 4K mode)</description> + <latching>true</latching> + <annunciating>true</annunciating> + <guidance> + <title>[Cryo Operator Action]</title> + <details>contact CRYO on-call and inform SCL on-call, Cryomodule bath pressure too high (check the other gauge PT002). Close supply valve CV01, CV02 if necessary</details> + </guidance> + </pv> + <pv name="Spk-030Crm:Cryo-PT-003:Cable_Error"> + <description>Cavity tanks Pressure Sensor cables are disconnected</description> + <latching>true</latching> + <annunciating>true</annunciating> + <guidance> + <title>[Cryo Operator Action]</title> + <details>contact CRYO on-call and inform SCL on-call, Cryomodule pressure cable seems disconnected (value gets stuck), assign PT002 as measuring device on CV04 and CV-090 </details> + </guidance> + </pv> + <pv name="Spk-030Crm:Cryo-PT-002:HIHI"> + <description>Cavity tanks pressure is too high (typical value is 31mbar in 2K mode and 1050mbar in 4K mode)</description> + <latching>true</latching> + <annunciating>true</annunciating> + <guidance> + <title>[Cryo Operator Action]</title> + <details>contact CRYO on-call and inform SCL on-call,, Cryomodule bath pressure too high (check the other gauge PT003). Close supply valve CV01, CV02 if necessary</details> + </guidance> + </pv> + <pv name="Spk-030Crm:Cryo-PT-002:Cable_Error"> + <description>Cavity tanks Pressure Sensor cables are disconnected</description> + <latching>true</latching> + <annunciating>true</annunciating> + <guidance> + <title>[Cryo Operator Action]</title> + <details>contact CRYO on-call and inform SCL on-call, Cryomodule pressure cable seems disconnected (value gets stuck), assign PT003 as measuring device on CV04 and CV-090 </details> + </guidance> + </pv> + <pv name="Spk-030Crm:Cryo-TT-120:P_Limit_LO"> + <description>Power coupler flange temperature low</description> + <latching>true</latching> + <annunciating>true</annunciating> + <guidance> + <title>[Cryo Operator Action]</title> + <details>contact CRYO on-call and inform SCL on-call, power coupler flange temperature is low, check heater output, if nominal then coupler flow needs to be adjusted (reduced)</details> + </guidance> + </pv> + <pv name="Spk-030Crm:Cryo-TT-120:P_Limit_LOLO"> + <description>Power coupler flange temperature too low</description> + <latching>true</latching> + <annunciating>true</annunciating> + <guidance> + <title>[Cryo Operator Action]</title> + <details>contact CRYO on-call and inform SCL on-call, power coupler flange temperature is too low, check heater output, if nominal then coupler flow needs to be adjusted (reduced)</details> + </guidance> + </pv> + <pv name="Spk-030Crm:Cryo-TT-120:P_Limit_HIHI"> + <description>Power coupler flange temperature too high</description> + <latching>true</latching> + <annunciating>true</annunciating> + <guidance> + <title>[Cryo Operator Action]</title> + <details>contact CRYO on-call and inform SCL on-call, power coupler flange temperature is too high, check heater output, if nominal then coupler flow needs to be adjusted (reduced)</details> + </guidance> + </pv> + <pv name="Spk-030Crm:Cryo-TT-220:P_Limit_LO"> + <description>Power coupler flange temperature low</description> + <latching>true</latching> + <annunciating>true</annunciating> + <guidance> + <title>[Cryo Operator Action]</title> + <details>contact CRYO on-call and inform SCL on-call, power coupler flange temperature is low, check heater output, if nominal then coupler flow needs to be adjusted (reduced)</details> + </guidance> + </pv> + <pv name="Spk-030Crm:Cryo-TT-220:P_Limit_LOLO"> + <description>Power coupler flange temperature too low</description> + <latching>true</latching> + <annunciating>true</annunciating> + <guidance> + <title>[Cryo Operator Action]</title> + <details>contact CRYO on-call and inform SCL on-call, power coupler flange temperature is too low, check heater output, if nominal then coupler flow needs to be adjusted (reduced)</details> + </guidance> + </pv> + <pv name="Spk-030Crm:Cryo-TT-220:P_Limit_HIHI"> + <description>Power coupler flange temperature too high</description> + <latching>true</latching> + <annunciating>true</annunciating> + <guidance> + <title>[Cryo Operator Action]</title> + <details>contact CRYO on-call and inform SCL on-call, power coupler flange temperature is too high, check heater output, if nominal then coupler flow needs to be adjusted (reduced)</details> + </guidance> + </pv> + <pv name="Spk-030Crm:WtrC-FS-013:Flow_OK_WF"> + <description>! Alarm when signal drops from 1 to zero. No Water Flow Antenna 1</description> + <latching>true</latching> + <annunciating>true</annunciating> + <guidance> + <title>[Cryo Operator Action]</title> + <details>contact CRYO on-call and inform SCL on-call, assure Flange temperature TT-120 is correct. Risk of Water freeze if no flow and temperature too low</details> + </guidance> + </pv> + <pv name="Spk-030Crm:WtrC-FS-014:Flow_OK_WF"> + <description>! Alarm when signal drops from 1 to zero. No Water Flow Window 1</description> + <latching>true</latching> + <annunciating>true</annunciating> + <guidance> + <title>[Cryo Operator Action]</title> + <details>contact CRYO on-call and inform SCL on-call, assure Flange temperature TT-120 is correct. Risk of Water freeze if no flow and temperature too low</details> + </guidance> + </pv> + <pv name="Spk-030Crm:WtrC-FS-023:Flow_OK_WF"> + <description>! Alarm when signal drops from 1 to zero. No Water Flow Antenna 2</description> + <latching>true</latching> + <annunciating>true</annunciating> + <guidance> + <title>[Cryo Operator Action]</title> + <details>contact CRYO on-call and inform SCL on-call, assure Flange temperature TT-120 is correct. Risk of Water freeze if no flow and temperature too low</details> + </guidance> + </pv> + <pv name="Spk-030Crm:WtrC-FS-024:Flow_OK_WF"> + <description>! Alarm when signal drops from 1 to zero. No Water Flow Window 2</description> + <latching>true</latching> + <annunciating>true</annunciating> + <guidance> + <title>[Cryo Operator Action]</title> + <details>contact CRYO on-call and inform SCL on-call, assure Flange temperature TT-120 is correct. Risk of Water freeze if no flow and temperature too low</details> + </guidance> + </pv> + </component> + <component name="Cryomodules\SPK-040 Cryomodule"> + <pv name="Spk-040Crm:Cryo-LT-001:HIHI"> + <description>LT-001 helium level extremely high</description> + <latching>true</latching> + <annunciating>true</annunciating> + <guidance> + <title>[Cryo Operator Action]</title> + <details>contact CRYO on-call and inform SCL on-call, Cryomodule liquid level too high (check the other gauge LT-002). Close supply valve CV01, CV02</details> + </guidance> + </pv> + <pv name="Spk-040Crm:Cryo-LT-002:HIHI"> + <description>LT-002 helium level extremely high</description> + <latching>true</latching> + <annunciating>true</annunciating> + <guidance> + <title>[Cryo Operator Action]</title> + <details>contact CRYO on-call and inform SCL on-call, Cryomodule liquid level too high (check the other gauge LT-001). Close supply valve CV01, CV02</details> + </guidance> + </pv> + <pv name="Spk-040Crm:Cryo-LT-001:HI"> + <description>LT-001 helium level high</description> + <latching>true</latching> + <annunciating>true</annunciating> + <guidance> + <title>[Cryo Operator Action]</title> + <details>contact CRYO on-call and inform SCL on-call, Cryomodule liquid level high (check the other gauge LT-002). Check level regulation valve settings, if needed: adjust LMN_LO and if necessary: Close supply valve CV01, CV02</details> + </guidance> + </pv> + <pv name="Spk-040Crm:Cryo-LT-002:HI"> + <description>LT-002 helium level high</description> + <latching>true</latching> + <annunciating>true</annunciating> + <guidance> + <title>[Cryo Operator Action]</title> + <details>contact CRYO on-call and inform SCL on-call, Cryomodule liquid level high (check the other gauge LT-002). Check level regulation valve settings, if needed: adjust LMN_LO and if necessary: Close supply valve CV01, CV02</details> + </guidance> + </pv> + <pv name="Spk-040Crm:Cryo-LT-001:LO"> + <description>LT-001 helium level low</description> + <latching>true</latching> + <annunciating>true</annunciating> + <guidance> + <title>[Cryo Operator Action]</title> + <details>contact CRYO on-call and inform SCL on-call, Cryomodule liquid level low (check the other gauge LT-001). Check level regulation valve settings, if needed: adjust LMN_HI</details> + </guidance> + </pv> + <pv name="Spk-040Crm:Cryo-LT-002:LO"> + <description>LT-002 helium level low</description> + <latching>true</latching> + <annunciating>true</annunciating> + <guidance> + <title>[Cryo Operator Action]</title> + <details>contact CRYO on-call and inform SCL on-call, Cryomodule liquid level low (check the other gauge LT-002). Check level regulation valvesettings, if needed: adjust LMN_HI</details> + </guidance> + </pv> + <pv name="Spk-040Crm:Cryo-LT-001:LOLO"> + <description>LT-002 helium level extremely low</description> + <latching>true</latching> + <annunciating>true</annunciating> + <guidance> + <title>[Cryo Operator Action]</title> + <details>contact CRYO on-call and inform SCL on-call, Cryomodule liquid level too low (check the other gauge LT-001). Check level regulation valve settings, if needed: adjust LMN_HI</details> + </guidance> + </pv> + <pv name="Spk-040Crm:Cryo-LT-002:LOLO"> + <description>LT-002 helium level extremely low</description> + <latching>true</latching> + <annunciating>true</annunciating> + <guidance> + <title>[Cryo Operator Action]</title> + <details>contact CRYO on-call and inform SCL on-call, Cryomodule liquid level too low (check the other gauge LT-002). Check level regulation valvesettings, if needed: adjust LMN_HI</details> + </guidance> + </pv> + <pv name="Spk-040Crm:Cryo-PT-003:HIHI"> + <description>Cavity tanks pressure is too high (typical value is 31mbar in 2K mode and 1050mbar in 4K mode)</description> + <latching>true</latching> + <annunciating>true</annunciating> + <guidance> + <title>[Cryo Operator Action]</title> + <details>contact CRYO on-call and inform SCL on-call, Cryomodule bath pressure too high (check the other gauge PT002). Close supply valve CV01, CV02 if necessary</details> + </guidance> + </pv> + <pv name="Spk-040Crm:Cryo-PT-003:Cable_Error"> + <description>Cavity tanks Pressure Sensor cables are disconnected</description> + <latching>true</latching> + <annunciating>true</annunciating> + <guidance> + <title>[Cryo Operator Action]</title> + <details>contact CRYO on-call and inform SCL on-call, Cryomodule pressure cable seems disconnected (value gets stuck), assign PT002 as measuring device on CV04 and CV-090 </details> + </guidance> + </pv> + <pv name="Spk-040Crm:Cryo-PT-002:HIHI"> + <description>Cavity tanks pressure is too high (typical value is 31mbar in 2K mode and 1050mbar in 4K mode)</description> + <latching>true</latching> + <annunciating>true</annunciating> + <guidance> + <title>[Cryo Operator Action]</title> + <details>contact CRYO on-call and inform SCL on-call,, Cryomodule bath pressure too high (check the other gauge PT003). Close supply valve CV01, CV02 if necessary</details> + </guidance> + </pv> + <pv name="Spk-040Crm:Cryo-PT-002:Cable_Error"> + <description>Cavity tanks Pressure Sensor cables are disconnected</description> + <latching>true</latching> + <annunciating>true</annunciating> + <guidance> + <title>[Cryo Operator Action]</title> + <details>contact CRYO on-call and inform SCL on-call, Cryomodule pressure cable seems disconnected (value gets stuck), assign PT003 as measuring device on CV04 and CV-090 </details> + </guidance> + </pv> + <pv name="Spk-040Crm:Cryo-TT-120:P_Limit_LO"> + <description>Power coupler flange temperature low</description> + <latching>true</latching> + <annunciating>true</annunciating> + <guidance> + <title>[Cryo Operator Action]</title> + <details>contact CRYO on-call and inform SCL on-call, power coupler flange temperature is low, check heater output, if nominal then coupler flow needs to be adjusted (reduced)</details> + </guidance> + </pv> + <pv name="Spk-040Crm:Cryo-TT-120:P_Limit_LOLO"> + <description>Power coupler flange temperature too low</description> + <latching>true</latching> + <annunciating>true</annunciating> + <guidance> + <title>[Cryo Operator Action]</title> + <details>contact CRYO on-call and inform SCL on-call, power coupler flange temperature is too low, check heater output, if nominal then coupler flow needs to be adjusted (reduced)</details> + </guidance> + </pv> + <pv name="Spk-040Crm:Cryo-TT-120:P_Limit_HIHI"> + <description>Power coupler flange temperature too high</description> + <latching>true</latching> + <annunciating>true</annunciating> + <guidance> + <title>[Cryo Operator Action]</title> + <details>contact CRYO on-call and inform SCL on-call, power coupler flange temperature is too high, check heater output, if nominal then coupler flow needs to be adjusted (reduced)</details> + </guidance> + </pv> + <pv name="Spk-040Crm:Cryo-TT-220:P_Limit_LO"> + <description>Power coupler flange temperature low</description> + <latching>true</latching> + <annunciating>true</annunciating> + <guidance> + <title>[Cryo Operator Action]</title> + <details>contact CRYO on-call and inform SCL on-call, power coupler flange temperature is low, check heater output, if nominal then coupler flow needs to be adjusted (reduced)</details> + </guidance> + </pv> + <pv name="Spk-040Crm:Cryo-TT-220:P_Limit_LOLO"> + <description>Power coupler flange temperature too low</description> + <latching>true</latching> + <annunciating>true</annunciating> + <guidance> + <title>[Cryo Operator Action]</title> + <details>contact CRYO on-call and inform SCL on-call, power coupler flange temperature is too low, check heater output, if nominal then coupler flow needs to be adjusted (reduced)</details> + </guidance> + </pv> + <pv name="Spk-040Crm:Cryo-TT-220:P_Limit_HIHI"> + <description>Power coupler flange temperature too high</description> + <latching>true</latching> + <annunciating>true</annunciating> + <guidance> + <title>[Cryo Operator Action]</title> + <details>contact CRYO on-call and inform SCL on-call, power coupler flange temperature is too high, check heater output, if nominal then coupler flow needs to be adjusted (reduced)</details> + </guidance> + </pv> + <pv name="Spk-040Crm:WtrC-FS-013:Flow_OK_WF"> + <description>! Alarm when signal drops from 1 to zero. No Water Flow Antenna 1</description> + <latching>true</latching> + <annunciating>true</annunciating> + <guidance> + <title>[Cryo Operator Action]</title> + <details>contact CRYO on-call and inform SCL on-call, assure Flange temperature TT-120 is correct. Risk of Water freeze if no flow and temperature too low</details> + </guidance> + </pv> + <pv name="Spk-040Crm:WtrC-FS-014:Flow_OK_WF"> + <description>! Alarm when signal drops from 1 to zero. No Water Flow Window 1</description> + <latching>true</latching> + <annunciating>true</annunciating> + <guidance> + <title>[Cryo Operator Action]</title> + <details>contact CRYO on-call and inform SCL on-call, assure Flange temperature TT-120 is correct. Risk of Water freeze if no flow and temperature too low</details> + </guidance> + </pv> + <pv name="Spk-040Crm:WtrC-FS-023:Flow_OK_WF"> + <description>! Alarm when signal drops from 1 to zero. No Water Flow Antenna 2</description> + <latching>true</latching> + <annunciating>true</annunciating> + <guidance> + <title>[Cryo Operator Action]</title> + <details>contact CRYO on-call and inform SCL on-call, assure Flange temperature TT-120 is correct. Risk of Water freeze if no flow and temperature too low</details> + </guidance> + </pv> + <pv name="Spk-040Crm:WtrC-FS-024:Flow_OK_WF"> + <description>! Alarm when signal drops from 1 to zero. No Water Flow Window 2</description> + <latching>true</latching> + <annunciating>true</annunciating> + <guidance> + <title>[Cryo Operator Action]</title> + <details>contact CRYO on-call and inform SCL on-call, assure Flange temperature TT-120 is correct. Risk of Water freeze if no flow and temperature too low</details> + </guidance> + </pv> + </component> + <component name="Cryomodules\SPK-050 Cryomodule"> + <pv name="Spk-050Crm:Cryo-LT-001:HIHI"> + <description>LT-001 helium level extremely high</description> + <latching>true</latching> + <annunciating>true</annunciating> + <guidance> + <title>[Cryo Operator Action]</title> + <details>contact CRYO on-call and inform SCL on-call, Cryomodule liquid level too high (check the other gauge LT-002). Close supply valve CV01, CV02</details> + </guidance> + </pv> + <pv name="Spk-050Crm:Cryo-LT-002:HIHI"> + <description>LT-002 helium level extremely high</description> + <latching>true</latching> + <annunciating>true</annunciating> + <guidance> + <title>[Cryo Operator Action]</title> + <details>contact CRYO on-call and inform SCL on-call, Cryomodule liquid level too high (check the other gauge LT-001). Close supply valve CV01, CV02</details> + </guidance> + </pv> + <pv name="Spk-050Crm:Cryo-LT-001:HI"> + <description>LT-001 helium level high</description> + <latching>true</latching> + <annunciating>true</annunciating> + <guidance> + <title>[Cryo Operator Action]</title> + <details>contact CRYO on-call and inform SCL on-call, Cryomodule liquid level high (check the other gauge LT-002). Check level regulation valve settings, if needed: adjust LMN_LO and if necessary: Close supply valve CV01, CV02</details> + </guidance> + </pv> + <pv name="Spk-050Crm:Cryo-LT-002:HI"> + <description>LT-002 helium level high</description> + <latching>true</latching> + <annunciating>true</annunciating> + <guidance> + <title>[Cryo Operator Action]</title> + <details>contact CRYO on-call and inform SCL on-call, Cryomodule liquid level high (check the other gauge LT-002). Check level regulation valve settings, if needed: adjust LMN_LO and if necessary: Close supply valve CV01, CV02</details> + </guidance> + </pv> + <pv name="Spk-050Crm:Cryo-LT-001:LO"> + <description>LT-001 helium level low</description> + <latching>true</latching> + <annunciating>true</annunciating> + <guidance> + <title>[Cryo Operator Action]</title> + <details>contact CRYO on-call and inform SCL on-call, Cryomodule liquid level low (check the other gauge LT-001). Check level regulation valve settings, if needed: adjust LMN_HI</details> + </guidance> + </pv> + <pv name="Spk-050Crm:Cryo-LT-002:LO"> + <description>LT-002 helium level low</description> + <latching>true</latching> + <annunciating>true</annunciating> + <guidance> + <title>[Cryo Operator Action]</title> + <details>contact CRYO on-call and inform SCL on-call, Cryomodule liquid level low (check the other gauge LT-002). Check level regulation valvesettings, if needed: adjust LMN_HI</details> + </guidance> + </pv> + <pv name="Spk-050Crm:Cryo-LT-001:LOLO"> + <description>LT-002 helium level extremely low</description> + <latching>true</latching> + <annunciating>true</annunciating> + <guidance> + <title>[Cryo Operator Action]</title> + <details>contact CRYO on-call and inform SCL on-call, Cryomodule liquid level too low (check the other gauge LT-001). Check level regulation valve settings, if needed: adjust LMN_HI</details> + </guidance> + </pv> + <pv name="Spk-050Crm:Cryo-LT-002:LOLO"> + <description>LT-002 helium level extremely low</description> + <latching>true</latching> + <annunciating>true</annunciating> + <guidance> + <title>[Cryo Operator Action]</title> + <details>contact CRYO on-call and inform SCL on-call, Cryomodule liquid level too low (check the other gauge LT-002). Check level regulation valvesettings, if needed: adjust LMN_HI</details> + </guidance> + </pv> + <pv name="Spk-050Crm:Cryo-PT-003:HIHI"> + <description>Cavity tanks pressure is too high (typical value is 31mbar in 2K mode and 1050mbar in 4K mode)</description> + <latching>true</latching> + <annunciating>true</annunciating> + <guidance> + <title>[Cryo Operator Action]</title> + <details>contact CRYO on-call and inform SCL on-call, Cryomodule bath pressure too high (check the other gauge PT002). Close supply valve CV01, CV02 if necessary</details> + </guidance> + </pv> + <pv name="Spk-050Crm:Cryo-PT-003:Cable_Error"> + <description>Cavity tanks Pressure Sensor cables are disconnected</description> + <latching>true</latching> + <annunciating>true</annunciating> + <guidance> + <title>[Cryo Operator Action]</title> + <details>contact CRYO on-call and inform SCL on-call, Cryomodule pressure cable seems disconnected (value gets stuck), assign PT002 as measuring device on CV04 and CV-090 </details> + </guidance> + </pv> + <pv name="Spk-050Crm:Cryo-PT-002:HIHI"> + <description>Cavity tanks pressure is too high (typical value is 31mbar in 2K mode and 1050mbar in 4K mode)</description> + <latching>true</latching> + <annunciating>true</annunciating> + <guidance> + <title>[Cryo Operator Action]</title> + <details>contact CRYO on-call and inform SCL on-call,, Cryomodule bath pressure too high (check the other gauge PT003). Close supply valve CV01, CV02 if necessary</details> + </guidance> + </pv> + <pv name="Spk-050Crm:Cryo-PT-002:Cable_Error"> + <description>Cavity tanks Pressure Sensor cables are disconnected</description> + <latching>true</latching> + <annunciating>true</annunciating> + <guidance> + <title>[Cryo Operator Action]</title> + <details>contact CRYO on-call and inform SCL on-call, Cryomodule pressure cable seems disconnected (value gets stuck), assign PT003 as measuring device on CV04 and CV-090 </details> + </guidance> + </pv> + <pv name="Spk-050Crm:Cryo-TT-120:P_Limit_LO"> + <description>Power coupler flange temperature low</description> + <latching>true</latching> + <annunciating>true</annunciating> + <guidance> + <title>[Cryo Operator Action]</title> + <details>contact CRYO on-call and inform SCL on-call, power coupler flange temperature is low, check heater output, if nominal then coupler flow needs to be adjusted (reduced)</details> + </guidance> + </pv> + <pv name="Spk-050Crm:Cryo-TT-120:P_Limit_LOLO"> + <description>Power coupler flange temperature too low</description> + <latching>true</latching> + <annunciating>true</annunciating> + <guidance> + <title>[Cryo Operator Action]</title> + <details>contact CRYO on-call and inform SCL on-call, power coupler flange temperature is too low, check heater output, if nominal then coupler flow needs to be adjusted (reduced)</details> + </guidance> + </pv> + <pv name="Spk-050Crm:Cryo-TT-120:P_Limit_HIHI"> + <description>Power coupler flange temperature too high</description> + <latching>true</latching> + <annunciating>true</annunciating> + <guidance> + <title>[Cryo Operator Action]</title> + <details>contact CRYO on-call and inform SCL on-call, power coupler flange temperature is too high, check heater output, if nominal then coupler flow needs to be adjusted (reduced)</details> + </guidance> + </pv> + <pv name="Spk-050Crm:Cryo-TT-220:P_Limit_LO"> + <description>Power coupler flange temperature low</description> + <latching>true</latching> + <annunciating>true</annunciating> + <guidance> + <title>[Cryo Operator Action]</title> + <details>contact CRYO on-call and inform SCL on-call, power coupler flange temperature is low, check heater output, if nominal then coupler flow needs to be adjusted (reduced)</details> + </guidance> + </pv> + <pv name="Spk-050Crm:Cryo-TT-220:P_Limit_LOLO"> + <description>Power coupler flange temperature too low</description> + <latching>true</latching> + <annunciating>true</annunciating> + <guidance> + <title>[Cryo Operator Action]</title> + <details>contact CRYO on-call and inform SCL on-call, power coupler flange temperature is too low, check heater output, if nominal then coupler flow needs to be adjusted (reduced)</details> + </guidance> + </pv> + <pv name="Spk-050Crm:Cryo-TT-220:P_Limit_HIHI"> + <description>Power coupler flange temperature too high</description> + <latching>true</latching> + <annunciating>true</annunciating> + <guidance> + <title>[Cryo Operator Action]</title> + <details>contact CRYO on-call and inform SCL on-call, power coupler flange temperature is too high, check heater output, if nominal then coupler flow needs to be adjusted (reduced)</details> + </guidance> + </pv> + <pv name="Spk-050Crm:WtrC-FS-013:Flow_OK_WF"> + <description>! Alarm when signal drops from 1 to zero. No Water Flow Antenna 1</description> + <latching>true</latching> + <annunciating>true</annunciating> + <guidance> + <title>[Cryo Operator Action]</title> + <details>contact CRYO on-call and inform SCL on-call, assure Flange temperature TT-120 is correct. Risk of Water freeze if no flow and temperature too low</details> + </guidance> + </pv> + <pv name="Spk-050Crm:WtrC-FS-014:Flow_OK_WF"> + <description>! Alarm when signal drops from 1 to zero. No Water Flow Window 1</description> + <latching>true</latching> + <annunciating>true</annunciating> + <guidance> + <title>[Cryo Operator Action]</title> + <details>contact CRYO on-call and inform SCL on-call, assure Flange temperature TT-120 is correct. Risk of Water freeze if no flow and temperature too low</details> + </guidance> + </pv> + <pv name="Spk-050Crm:WtrC-FS-023:Flow_OK_WF"> + <description>! Alarm when signal drops from 1 to zero. No Water Flow Antenna 2</description> + <latching>true</latching> + <annunciating>true</annunciating> + <guidance> + <title>[Cryo Operator Action]</title> + <details>contact CRYO on-call and inform SCL on-call, assure Flange temperature TT-120 is correct. Risk of Water freeze if no flow and temperature too low</details> + </guidance> + </pv> + <pv name="Spk-050Crm:WtrC-FS-024:Flow_OK_WF"> + <description>! Alarm when signal drops from 1 to zero. No Water Flow Window 2</description> + <latching>true</latching> + <annunciating>true</annunciating> + <guidance> + <title>[Cryo Operator Action]</title> + <details>contact CRYO on-call and inform SCL on-call, assure Flange temperature TT-120 is correct. Risk of Water freeze if no flow and temperature too low</details> + </guidance> + </pv> + </component> + <component name="Cryomodules\SPK-060 Cryomodule"> + <pv name="Spk-060Crm:Cryo-LT-001:HIHI"> + <description>LT-001 helium level extremely high</description> + <latching>true</latching> + <annunciating>true</annunciating> + <guidance> + <title>[Cryo Operator Action]</title> + <details>contact CRYO on-call and inform SCL on-call, Cryomodule liquid level too high (check the other gauge LT-002). Close supply valve CV01, CV02</details> + </guidance> + </pv> + <pv name="Spk-060Crm:Cryo-LT-002:HIHI"> + <description>LT-002 helium level extremely high</description> + <latching>true</latching> + <annunciating>true</annunciating> + <guidance> + <title>[Cryo Operator Action]</title> + <details>contact CRYO on-call and inform SCL on-call, Cryomodule liquid level too high (check the other gauge LT-001). Close supply valve CV01, CV02</details> + </guidance> + </pv> + <pv name="Spk-060Crm:Cryo-LT-001:HI"> + <description>LT-001 helium level high</description> + <latching>true</latching> + <annunciating>true</annunciating> + <guidance> + <title>[Cryo Operator Action]</title> + <details>contact CRYO on-call and inform SCL on-call, Cryomodule liquid level high (check the other gauge LT-002). Check level regulation valve settings, if needed: adjust LMN_LO and if necessary: Close supply valve CV01, CV02</details> + </guidance> + </pv> + <pv name="Spk-060Crm:Cryo-LT-002:HI"> + <description>LT-002 helium level high</description> + <latching>true</latching> + <annunciating>true</annunciating> + <guidance> + <title>[Cryo Operator Action]</title> + <details>contact CRYO on-call and inform SCL on-call, Cryomodule liquid level high (check the other gauge LT-002). Check level regulation valve settings, if needed: adjust LMN_LO and if necessary: Close supply valve CV01, CV02</details> + </guidance> + </pv> + <pv name="Spk-060Crm:Cryo-LT-001:LO"> + <description>LT-001 helium level low</description> + <latching>true</latching> + <annunciating>true</annunciating> + <guidance> + <title>[Cryo Operator Action]</title> + <details>contact CRYO on-call and inform SCL on-call, Cryomodule liquid level low (check the other gauge LT-001). Check level regulation valve settings, if needed: adjust LMN_HI</details> + </guidance> + </pv> + <pv name="Spk-060Crm:Cryo-LT-002:LO"> + <description>LT-002 helium level low</description> + <latching>true</latching> + <annunciating>true</annunciating> + <guidance> + <title>[Cryo Operator Action]</title> + <details>contact CRYO on-call and inform SCL on-call, Cryomodule liquid level low (check the other gauge LT-002). Check level regulation valvesettings, if needed: adjust LMN_HI</details> + </guidance> + </pv> + <pv name="Spk-060Crm:Cryo-LT-001:LOLO"> + <description>LT-002 helium level extremely low</description> + <latching>true</latching> + <annunciating>true</annunciating> + <guidance> + <title>[Cryo Operator Action]</title> + <details>contact CRYO on-call and inform SCL on-call, Cryomodule liquid level too low (check the other gauge LT-001). Check level regulation valve settings, if needed: adjust LMN_HI</details> + </guidance> + </pv> + <pv name="Spk-060Crm:Cryo-LT-002:LOLO"> + <description>LT-002 helium level extremely low</description> + <latching>true</latching> + <annunciating>true</annunciating> + <guidance> + <title>[Cryo Operator Action]</title> + <details>contact CRYO on-call and inform SCL on-call, Cryomodule liquid level too low (check the other gauge LT-002). Check level regulation valvesettings, if needed: adjust LMN_HI</details> + </guidance> + </pv> + <pv name="Spk-060Crm:Cryo-PT-003:HIHI"> + <description>Cavity tanks pressure is too high (typical value is 31mbar in 2K mode and 1050mbar in 4K mode)</description> + <latching>true</latching> + <annunciating>true</annunciating> + <guidance> + <title>[Cryo Operator Action]</title> + <details>contact CRYO on-call and inform SCL on-call, Cryomodule bath pressure too high (check the other gauge PT002). Close supply valve CV01, CV02 if necessary</details> + </guidance> + </pv> + <pv name="Spk-060Crm:Cryo-PT-003:Cable_Error"> + <description>Cavity tanks Pressure Sensor cables are disconnected</description> + <latching>true</latching> + <annunciating>true</annunciating> + <guidance> + <title>[Cryo Operator Action]</title> + <details>contact CRYO on-call and inform SCL on-call, Cryomodule pressure cable seems disconnected (value gets stuck), assign PT002 as measuring device on CV04 and CV-090 </details> + </guidance> + </pv> + <pv name="Spk-060Crm:Cryo-PT-002:HIHI"> + <description>Cavity tanks pressure is too high (typical value is 31mbar in 2K mode and 1050mbar in 4K mode)</description> + <latching>true</latching> + <annunciating>true</annunciating> + <guidance> + <title>[Cryo Operator Action]</title> + <details>contact CRYO on-call and inform SCL on-call,, Cryomodule bath pressure too high (check the other gauge PT003). Close supply valve CV01, CV02 if necessary</details> + </guidance> + </pv> + <pv name="Spk-060Crm:Cryo-PT-002:Cable_Error"> + <description>Cavity tanks Pressure Sensor cables are disconnected</description> + <latching>true</latching> + <annunciating>true</annunciating> + <guidance> + <title>[Cryo Operator Action]</title> + <details>contact CRYO on-call and inform SCL on-call, Cryomodule pressure cable seems disconnected (value gets stuck), assign PT003 as measuring device on CV04 and CV-090 </details> + </guidance> + </pv> + <pv name="Spk-060Crm:Cryo-TT-120:P_Limit_LO"> + <description>Power coupler flange temperature low</description> + <latching>true</latching> + <annunciating>true</annunciating> + <guidance> + <title>[Cryo Operator Action]</title> + <details>contact CRYO on-call and inform SCL on-call, power coupler flange temperature is low, check heater output, if nominal then coupler flow needs to be adjusted (reduced)</details> + </guidance> + </pv> + <pv name="Spk-060Crm:Cryo-TT-120:P_Limit_LOLO"> + <description>Power coupler flange temperature too low</description> + <latching>true</latching> + <annunciating>true</annunciating> + <guidance> + <title>[Cryo Operator Action]</title> + <details>contact CRYO on-call and inform SCL on-call, power coupler flange temperature is too low, check heater output, if nominal then coupler flow needs to be adjusted (reduced)</details> + </guidance> + </pv> + <pv name="Spk-060Crm:Cryo-TT-120:P_Limit_HIHI"> + <description>Power coupler flange temperature too high</description> + <latching>true</latching> + <annunciating>true</annunciating> + <guidance> + <title>[Cryo Operator Action]</title> + <details>contact CRYO on-call and inform SCL on-call, power coupler flange temperature is too high, check heater output, if nominal then coupler flow needs to be adjusted (reduced)</details> + </guidance> + </pv> + <pv name="Spk-060Crm:Cryo-TT-220:P_Limit_LO"> + <description>Power coupler flange temperature low</description> + <latching>true</latching> + <annunciating>true</annunciating> + <guidance> + <title>[Cryo Operator Action]</title> + <details>contact CRYO on-call and inform SCL on-call, power coupler flange temperature is low, check heater output, if nominal then coupler flow needs to be adjusted (reduced)</details> + </guidance> + </pv> + <pv name="Spk-060Crm:Cryo-TT-220:P_Limit_LOLO"> + <description>Power coupler flange temperature too low</description> + <latching>true</latching> + <annunciating>true</annunciating> + <guidance> + <title>[Cryo Operator Action]</title> + <details>contact CRYO on-call and inform SCL on-call, power coupler flange temperature is too low, check heater output, if nominal then coupler flow needs to be adjusted (reduced)</details> + </guidance> + </pv> + <pv name="Spk-060Crm:Cryo-TT-220:P_Limit_HIHI"> + <description>Power coupler flange temperature too high</description> + <latching>true</latching> + <annunciating>true</annunciating> + <guidance> + <title>[Cryo Operator Action]</title> + <details>contact CRYO on-call and inform SCL on-call, power coupler flange temperature is too high, check heater output, if nominal then coupler flow needs to be adjusted (reduced)</details> + </guidance> + </pv> + <pv name="Spk-060Crm:WtrC-FS-013:Flow_OK_WF"> + <description>! Alarm when signal drops from 1 to zero. No Water Flow Antenna 1</description> + <latching>true</latching> + <annunciating>true</annunciating> + <guidance> + <title>[Cryo Operator Action]</title> + <details>contact CRYO on-call and inform SCL on-call, assure Flange temperature TT-120 is correct. Risk of Water freeze if no flow and temperature too low</details> + </guidance> + </pv> + <pv name="Spk-060Crm:WtrC-FS-014:Flow_OK_WF"> + <description>! Alarm when signal drops from 1 to zero. No Water Flow Window 1</description> + <latching>true</latching> + <annunciating>true</annunciating> + <guidance> + <title>[Cryo Operator Action]</title> + <details>contact CRYO on-call and inform SCL on-call, assure Flange temperature TT-120 is correct. Risk of Water freeze if no flow and temperature too low</details> + </guidance> + </pv> + <pv name="Spk-060Crm:WtrC-FS-023:Flow_OK_WF"> + <description>! Alarm when signal drops from 1 to zero. No Water Flow Antenna 2</description> + <latching>true</latching> + <annunciating>true</annunciating> + <guidance> + <title>[Cryo Operator Action]</title> + <details>contact CRYO on-call and inform SCL on-call, assure Flange temperature TT-120 is correct. Risk of Water freeze if no flow and temperature too low</details> + </guidance> + </pv> + <pv name="Spk-060Crm:WtrC-FS-024:Flow_OK_WF"> + <description>! Alarm when signal drops from 1 to zero. No Water Flow Window 2</description> + <latching>true</latching> + <annunciating>true</annunciating> + <guidance> + <title>[Cryo Operator Action]</title> + <details>contact CRYO on-call and inform SCL on-call, assure Flange temperature TT-120 is correct. Risk of Water freeze if no flow and temperature too low</details> + </guidance> + </pv> + </component> + <component name="Cryomodules\SPK-070 Cryomodule"> + <pv name="Spk-070Crm:Cryo-LT-001:HIHI"> + <description>LT-001 helium level extremely high</description> + <latching>true</latching> + <annunciating>true</annunciating> + <guidance> + <title>[Cryo Operator Action]</title> + <details>contact CRYO on-call and inform SCL on-call, Cryomodule liquid level too high (check the other gauge LT-002). Close supply valve CV01, CV02</details> + </guidance> + </pv> + <pv name="Spk-070Crm:Cryo-LT-002:HIHI"> + <description>LT-002 helium level extremely high</description> + <latching>true</latching> + <annunciating>true</annunciating> + <guidance> + <title>[Cryo Operator Action]</title> + <details>contact CRYO on-call and inform SCL on-call, Cryomodule liquid level too high (check the other gauge LT-001). Close supply valve CV01, CV02</details> + </guidance> + </pv> + <pv name="Spk-070Crm:Cryo-LT-001:HI"> + <description>LT-001 helium level high</description> + <latching>true</latching> + <annunciating>true</annunciating> + <guidance> + <title>[Cryo Operator Action]</title> + <details>contact CRYO on-call and inform SCL on-call, Cryomodule liquid level high (check the other gauge LT-002). Check level regulation valve settings, if needed: adjust LMN_LO and if necessary: Close supply valve CV01, CV02</details> + </guidance> + </pv> + <pv name="Spk-070Crm:Cryo-LT-002:HI"> + <description>LT-002 helium level high</description> + <latching>true</latching> + <annunciating>true</annunciating> + <guidance> + <title>[Cryo Operator Action]</title> + <details>contact CRYO on-call and inform SCL on-call, Cryomodule liquid level high (check the other gauge LT-002). Check level regulation valve settings, if needed: adjust LMN_LO and if necessary: Close supply valve CV01, CV02</details> + </guidance> + </pv> + <pv name="Spk-070Crm:Cryo-LT-001:LO"> + <description>LT-001 helium level low</description> + <latching>true</latching> + <annunciating>true</annunciating> + <guidance> + <title>[Cryo Operator Action]</title> + <details>contact CRYO on-call and inform SCL on-call, Cryomodule liquid level low (check the other gauge LT-001). Check level regulation valve settings, if needed: adjust LMN_HI</details> + </guidance> + </pv> + <pv name="Spk-070Crm:Cryo-LT-002:LO"> + <description>LT-002 helium level low</description> + <latching>true</latching> + <annunciating>true</annunciating> + <guidance> + <title>[Cryo Operator Action]</title> + <details>contact CRYO on-call and inform SCL on-call, Cryomodule liquid level low (check the other gauge LT-002). Check level regulation valvesettings, if needed: adjust LMN_HI</details> + </guidance> + </pv> + <pv name="Spk-070Crm:Cryo-LT-001:LOLO"> + <description>LT-002 helium level extremely low</description> + <latching>true</latching> + <annunciating>true</annunciating> + <guidance> + <title>[Cryo Operator Action]</title> + <details>contact CRYO on-call and inform SCL on-call, Cryomodule liquid level too low (check the other gauge LT-001). Check level regulation valve settings, if needed: adjust LMN_HI</details> + </guidance> + </pv> + <pv name="Spk-070Crm:Cryo-LT-002:LOLO"> + <description>LT-002 helium level extremely low</description> + <latching>true</latching> + <annunciating>true</annunciating> + <guidance> + <title>[Cryo Operator Action]</title> + <details>contact CRYO on-call and inform SCL on-call, Cryomodule liquid level too low (check the other gauge LT-002). Check level regulation valvesettings, if needed: adjust LMN_HI</details> + </guidance> + </pv> + <pv name="Spk-070Crm:Cryo-PT-003:HIHI"> + <description>Cavity tanks pressure is too high (typical value is 31mbar in 2K mode and 1050mbar in 4K mode)</description> + <latching>true</latching> + <annunciating>true</annunciating> + <guidance> + <title>[Cryo Operator Action]</title> + <details>contact CRYO on-call and inform SCL on-call, Cryomodule bath pressure too high (check the other gauge PT002). Close supply valve CV01, CV02 if necessary</details> + </guidance> + </pv> + <pv name="Spk-070Crm:Cryo-PT-003:Cable_Error"> + <description>Cavity tanks Pressure Sensor cables are disconnected</description> + <latching>true</latching> + <annunciating>true</annunciating> + <guidance> + <title>[Cryo Operator Action]</title> + <details>contact CRYO on-call and inform SCL on-call, Cryomodule pressure cable seems disconnected (value gets stuck), assign PT002 as measuring device on CV04 and CV-090 </details> + </guidance> + </pv> + <pv name="Spk-070Crm:Cryo-PT-002:HIHI"> + <description>Cavity tanks pressure is too high (typical value is 31mbar in 2K mode and 1050mbar in 4K mode)</description> + <latching>true</latching> + <annunciating>true</annunciating> + <guidance> + <title>[Cryo Operator Action]</title> + <details>contact CRYO on-call and inform SCL on-call,, Cryomodule bath pressure too high (check the other gauge PT003). Close supply valve CV01, CV02 if necessary</details> + </guidance> + </pv> + <pv name="Spk-070Crm:Cryo-PT-002:Cable_Error"> + <description>Cavity tanks Pressure Sensor cables are disconnected</description> + <latching>true</latching> + <annunciating>true</annunciating> + <guidance> + <title>[Cryo Operator Action]</title> + <details>contact CRYO on-call and inform SCL on-call, Cryomodule pressure cable seems disconnected (value gets stuck), assign PT003 as measuring device on CV04 and CV-090 </details> + </guidance> + </pv> + <pv name="Spk-070Crm:Cryo-TT-120:P_Limit_LO"> + <description>Power coupler flange temperature low</description> + <latching>true</latching> + <annunciating>true</annunciating> + <guidance> + <title>[Cryo Operator Action]</title> + <details>contact CRYO on-call and inform SCL on-call, power coupler flange temperature is low, check heater output, if nominal then coupler flow needs to be adjusted (reduced)</details> + </guidance> + </pv> + <pv name="Spk-070Crm:Cryo-TT-120:P_Limit_LOLO"> + <description>Power coupler flange temperature too low</description> + <latching>true</latching> + <annunciating>true</annunciating> + <guidance> + <title>[Cryo Operator Action]</title> + <details>contact CRYO on-call and inform SCL on-call, power coupler flange temperature is too low, check heater output, if nominal then coupler flow needs to be adjusted (reduced)</details> + </guidance> + </pv> + <pv name="Spk-070Crm:Cryo-TT-120:P_Limit_HIHI"> + <description>Power coupler flange temperature too high</description> + <latching>true</latching> + <annunciating>true</annunciating> + <guidance> + <title>[Cryo Operator Action]</title> + <details>contact CRYO on-call and inform SCL on-call, power coupler flange temperature is too high, check heater output, if nominal then coupler flow needs to be adjusted (reduced)</details> + </guidance> + </pv> + <pv name="Spk-070Crm:Cryo-TT-220:P_Limit_LO"> + <description>Power coupler flange temperature low</description> + <latching>true</latching> + <annunciating>true</annunciating> + <guidance> + <title>[Cryo Operator Action]</title> + <details>contact CRYO on-call and inform SCL on-call, power coupler flange temperature is low, check heater output, if nominal then coupler flow needs to be adjusted (reduced)</details> + </guidance> + </pv> + <pv name="Spk-070Crm:Cryo-TT-220:P_Limit_LOLO"> + <description>Power coupler flange temperature too low</description> + <latching>true</latching> + <annunciating>true</annunciating> + <guidance> + <title>[Cryo Operator Action]</title> + <details>contact CRYO on-call and inform SCL on-call, power coupler flange temperature is too low, check heater output, if nominal then coupler flow needs to be adjusted (reduced)</details> + </guidance> + </pv> + <pv name="Spk-070Crm:Cryo-TT-220:P_Limit_HIHI"> + <description>Power coupler flange temperature too high</description> + <latching>true</latching> + <annunciating>true</annunciating> + <guidance> + <title>[Cryo Operator Action]</title> + <details>contact CRYO on-call and inform SCL on-call, power coupler flange temperature is too high, check heater output, if nominal then coupler flow needs to be adjusted (reduced)</details> + </guidance> + </pv> + <pv name="Spk-070Crm:WtrC-FS-013:Flow_OK_WF"> + <description>! Alarm when signal drops from 1 to zero. No Water Flow Antenna 1</description> + <latching>true</latching> + <annunciating>true</annunciating> + <guidance> + <title>[Cryo Operator Action]</title> + <details>contact CRYO on-call and inform SCL on-call, assure Flange temperature TT-120 is correct. Risk of Water freeze if no flow and temperature too low</details> + </guidance> + </pv> + <pv name="Spk-070Crm:WtrC-FS-014:Flow_OK_WF"> + <description>! Alarm when signal drops from 1 to zero. No Water Flow Window 1</description> + <latching>true</latching> + <annunciating>true</annunciating> + <guidance> + <title>[Cryo Operator Action]</title> + <details>contact CRYO on-call and inform SCL on-call, assure Flange temperature TT-120 is correct. Risk of Water freeze if no flow and temperature too low</details> + </guidance> + </pv> + <pv name="Spk-070Crm:WtrC-FS-023:Flow_OK_WF"> + <description>! Alarm when signal drops from 1 to zero. No Water Flow Antenna 2</description> + <latching>true</latching> + <annunciating>true</annunciating> + <guidance> + <title>[Cryo Operator Action]</title> + <details>contact CRYO on-call and inform SCL on-call, assure Flange temperature TT-120 is correct. Risk of Water freeze if no flow and temperature too low</details> + </guidance> + </pv> + <pv name="Spk-070Crm:WtrC-FS-024:Flow_OK_WF"> + <description>! Alarm when signal drops from 1 to zero. No Water Flow Window 2</description> + <latching>true</latching> + <annunciating>true</annunciating> + <guidance> + <title>[Cryo Operator Action]</title> + <details>contact CRYO on-call and inform SCL on-call, assure Flange temperature TT-120 is correct. Risk of Water freeze if no flow and temperature too low</details> + </guidance> + </pv> + </component> + <component name="Cryomodules\SPK-080 Cryomodule"> + <pv name="Spk-080Crm:Cryo-LT-001:HIHI"> + <description>LT-001 helium level extremely high</description> + <latching>true</latching> + <annunciating>true</annunciating> + <guidance> + <title>[Cryo Operator Action]</title> + <details>contact CRYO on-call and inform SCL on-call, Cryomodule liquid level too high (check the other gauge LT-002). Close supply valve CV01, CV02</details> + </guidance> + </pv> + <pv name="Spk-080Crm:Cryo-LT-002:HIHI"> + <description>LT-002 helium level extremely high</description> + <latching>true</latching> + <annunciating>true</annunciating> + <guidance> + <title>[Cryo Operator Action]</title> + <details>contact CRYO on-call and inform SCL on-call, Cryomodule liquid level too high (check the other gauge LT-001). Close supply valve CV01, CV02</details> + </guidance> + </pv> + <pv name="Spk-080Crm:Cryo-LT-001:HI"> + <description>LT-001 helium level high</description> + <latching>true</latching> + <annunciating>true</annunciating> + <guidance> + <title>[Cryo Operator Action]</title> + <details>contact CRYO on-call and inform SCL on-call, Cryomodule liquid level high (check the other gauge LT-002). Check level regulation valve settings, if needed: adjust LMN_LO and if necessary: Close supply valve CV01, CV02</details> + </guidance> + </pv> + <pv name="Spk-080Crm:Cryo-LT-002:HI"> + <description>LT-002 helium level high</description> + <latching>true</latching> + <annunciating>true</annunciating> + <guidance> + <title>[Cryo Operator Action]</title> + <details>contact CRYO on-call and inform SCL on-call, Cryomodule liquid level high (check the other gauge LT-002). Check level regulation valve settings, if needed: adjust LMN_LO and if necessary: Close supply valve CV01, CV02</details> + </guidance> + </pv> + <pv name="Spk-080Crm:Cryo-LT-001:LO"> + <description>LT-001 helium level low</description> + <latching>true</latching> + <annunciating>true</annunciating> + <guidance> + <title>[Cryo Operator Action]</title> + <details>contact CRYO on-call and inform SCL on-call, Cryomodule liquid level low (check the other gauge LT-001). Check level regulation valve settings, if needed: adjust LMN_HI</details> + </guidance> + </pv> + <pv name="Spk-080Crm:Cryo-LT-002:LO"> + <description>LT-002 helium level low</description> + <latching>true</latching> + <annunciating>true</annunciating> + <guidance> + <title>[Cryo Operator Action]</title> + <details>contact CRYO on-call and inform SCL on-call, Cryomodule liquid level low (check the other gauge LT-002). Check level regulation valvesettings, if needed: adjust LMN_HI</details> + </guidance> + </pv> + <pv name="Spk-080Crm:Cryo-LT-001:LOLO"> + <description>LT-002 helium level extremely low</description> + <latching>true</latching> + <annunciating>true</annunciating> + <guidance> + <title>[Cryo Operator Action]</title> + <details>contact CRYO on-call and inform SCL on-call, Cryomodule liquid level too low (check the other gauge LT-001). Check level regulation valve settings, if needed: adjust LMN_HI</details> + </guidance> + </pv> + <pv name="Spk-080Crm:Cryo-LT-002:LOLO"> + <description>LT-002 helium level extremely low</description> + <latching>true</latching> + <annunciating>true</annunciating> + <guidance> + <title>[Cryo Operator Action]</title> + <details>contact CRYO on-call and inform SCL on-call, Cryomodule liquid level too low (check the other gauge LT-002). Check level regulation valvesettings, if needed: adjust LMN_HI</details> + </guidance> + </pv> + <pv name="Spk-080Crm:Cryo-PT-003:HIHI"> + <description>Cavity tanks pressure is too high (typical value is 31mbar in 2K mode and 1050mbar in 4K mode)</description> + <latching>true</latching> + <annunciating>true</annunciating> + <guidance> + <title>[Cryo Operator Action]</title> + <details>contact CRYO on-call and inform SCL on-call, Cryomodule bath pressure too high (check the other gauge PT002). Close supply valve CV01, CV02 if necessary</details> + </guidance> + </pv> + <pv name="Spk-080Crm:Cryo-PT-003:Cable_Error"> + <description>Cavity tanks Pressure Sensor cables are disconnected</description> + <latching>true</latching> + <annunciating>true</annunciating> + <guidance> + <title>[Cryo Operator Action]</title> + <details>contact CRYO on-call and inform SCL on-call, Cryomodule pressure cable seems disconnected (value gets stuck), assign PT002 as measuring device on CV04 and CV-090 </details> + </guidance> + </pv> + <pv name="Spk-080Crm:Cryo-PT-002:HIHI"> + <description>Cavity tanks pressure is too high (typical value is 31mbar in 2K mode and 1050mbar in 4K mode)</description> + <latching>true</latching> + <annunciating>true</annunciating> + <guidance> + <title>[Cryo Operator Action]</title> + <details>contact CRYO on-call and inform SCL on-call,, Cryomodule bath pressure too high (check the other gauge PT003). Close supply valve CV01, CV02 if necessary</details> + </guidance> + </pv> + <pv name="Spk-080Crm:Cryo-PT-002:Cable_Error"> + <description>Cavity tanks Pressure Sensor cables are disconnected</description> + <latching>true</latching> + <annunciating>true</annunciating> + <guidance> + <title>[Cryo Operator Action]</title> + <details>contact CRYO on-call and inform SCL on-call, Cryomodule pressure cable seems disconnected (value gets stuck), assign PT003 as measuring device on CV04 and CV-090 </details> + </guidance> + </pv> + <pv name="Spk-080Crm:Cryo-TT-120:P_Limit_LO"> + <description>Power coupler flange temperature low</description> + <latching>true</latching> + <annunciating>true</annunciating> + <guidance> + <title>[Cryo Operator Action]</title> + <details>contact CRYO on-call and inform SCL on-call, power coupler flange temperature is low, check heater output, if nominal then coupler flow needs to be adjusted (reduced)</details> + </guidance> + </pv> + <pv name="Spk-080Crm:Cryo-TT-120:P_Limit_LOLO"> + <description>Power coupler flange temperature too low</description> + <latching>true</latching> + <annunciating>true</annunciating> + <guidance> + <title>[Cryo Operator Action]</title> + <details>contact CRYO on-call and inform SCL on-call, power coupler flange temperature is too low, check heater output, if nominal then coupler flow needs to be adjusted (reduced)</details> + </guidance> + </pv> + <pv name="Spk-080Crm:Cryo-TT-120:P_Limit_HIHI"> + <description>Power coupler flange temperature too high</description> + <latching>true</latching> + <annunciating>true</annunciating> + <guidance> + <title>[Cryo Operator Action]</title> + <details>contact CRYO on-call and inform SCL on-call, power coupler flange temperature is too high, check heater output, if nominal then coupler flow needs to be adjusted (reduced)</details> + </guidance> + </pv> + <pv name="Spk-080Crm:Cryo-TT-220:P_Limit_LO"> + <description>Power coupler flange temperature low</description> + <latching>true</latching> + <annunciating>true</annunciating> + <guidance> + <title>[Cryo Operator Action]</title> + <details>contact CRYO on-call and inform SCL on-call, power coupler flange temperature is low, check heater output, if nominal then coupler flow needs to be adjusted (reduced)</details> + </guidance> + </pv> + <pv name="Spk-080Crm:Cryo-TT-220:P_Limit_LOLO"> + <description>Power coupler flange temperature too low</description> + <latching>true</latching> + <annunciating>true</annunciating> + <guidance> + <title>[Cryo Operator Action]</title> + <details>contact CRYO on-call and inform SCL on-call, power coupler flange temperature is too low, check heater output, if nominal then coupler flow needs to be adjusted (reduced)</details> + </guidance> + </pv> + <pv name="Spk-080Crm:Cryo-TT-220:P_Limit_HIHI"> + <description>Power coupler flange temperature too high</description> + <latching>true</latching> + <annunciating>true</annunciating> + <guidance> + <title>[Cryo Operator Action]</title> + <details>contact CRYO on-call and inform SCL on-call, power coupler flange temperature is too high, check heater output, if nominal then coupler flow needs to be adjusted (reduced)</details> + </guidance> + </pv> + <pv name="Spk-080Crm:WtrC-FS-013:Flow_OK_WF"> + <description>! Alarm when signal drops from 1 to zero. No Water Flow Antenna 1</description> + <latching>true</latching> + <annunciating>true</annunciating> + <guidance> + <title>[Cryo Operator Action]</title> + <details>contact CRYO on-call and inform SCL on-call, assure Flange temperature TT-120 is correct. Risk of Water freeze if no flow and temperature too low</details> + </guidance> + </pv> + <pv name="Spk-080Crm:WtrC-FS-014:Flow_OK_WF"> + <description>! Alarm when signal drops from 1 to zero. No Water Flow Window 1</description> + <latching>true</latching> + <annunciating>true</annunciating> + <guidance> + <title>[Cryo Operator Action]</title> + <details>contact CRYO on-call and inform SCL on-call, assure Flange temperature TT-120 is correct. Risk of Water freeze if no flow and temperature too low</details> + </guidance> + </pv> + <pv name="Spk-080Crm:WtrC-FS-023:Flow_OK_WF"> + <description>! Alarm when signal drops from 1 to zero. No Water Flow Antenna 2</description> + <latching>true</latching> + <annunciating>true</annunciating> + <guidance> + <title>[Cryo Operator Action]</title> + <details>contact CRYO on-call and inform SCL on-call, assure Flange temperature TT-120 is correct. Risk of Water freeze if no flow and temperature too low</details> + </guidance> + </pv> + <pv name="Spk-080Crm:WtrC-FS-024:Flow_OK_WF"> + <description>! Alarm when signal drops from 1 to zero. No Water Flow Window 2</description> + <latching>true</latching> + <annunciating>true</annunciating> + <guidance> + <title>[Cryo Operator Action]</title> + <details>contact CRYO on-call and inform SCL on-call, assure Flange temperature TT-120 is correct. Risk of Water freeze if no flow and temperature too low</details> + </guidance> + </pv> + </component> + <component name="Cryomodules\SPK-090 Cryomodule"> + <pv name="Spk-090Crm:Cryo-LT-001:HIHI"> + <description>LT-001 helium level extremely high</description> + <latching>true</latching> + <annunciating>true</annunciating> + <guidance> + <title>[Cryo Operator Action]</title> + <details>contact CRYO on-call and inform SCL on-call, Cryomodule liquid level too high (check the other gauge LT-002). Close supply valve CV01, CV02</details> + </guidance> + </pv> + <pv name="Spk-090Crm:Cryo-LT-002:HIHI"> + <description>LT-002 helium level extremely high</description> + <latching>true</latching> + <annunciating>true</annunciating> + <guidance> + <title>[Cryo Operator Action]</title> + <details>contact CRYO on-call and inform SCL on-call, Cryomodule liquid level too high (check the other gauge LT-001). Close supply valve CV01, CV02</details> + </guidance> + </pv> + <pv name="Spk-090Crm:Cryo-LT-001:HI"> + <description>LT-001 helium level high</description> + <latching>true</latching> + <annunciating>true</annunciating> + <guidance> + <title>[Cryo Operator Action]</title> + <details>contact CRYO on-call and inform SCL on-call, Cryomodule liquid level high (check the other gauge LT-002). Check level regulation valve settings, if needed: adjust LMN_LO and if necessary: Close supply valve CV01, CV02</details> + </guidance> + </pv> + <pv name="Spk-090Crm:Cryo-LT-002:HI"> + <description>LT-002 helium level high</description> + <latching>true</latching> + <annunciating>true</annunciating> + <guidance> + <title>[Cryo Operator Action]</title> + <details>contact CRYO on-call and inform SCL on-call, Cryomodule liquid level high (check the other gauge LT-002). Check level regulation valve settings, if needed: adjust LMN_LO and if necessary: Close supply valve CV01, CV02</details> + </guidance> + </pv> + <pv name="Spk-090Crm:Cryo-LT-001:LO"> + <description>LT-001 helium level low</description> + <latching>true</latching> + <annunciating>true</annunciating> + <guidance> + <title>[Cryo Operator Action]</title> + <details>contact CRYO on-call and inform SCL on-call, Cryomodule liquid level low (check the other gauge LT-001). Check level regulation valve settings, if needed: adjust LMN_HI</details> + </guidance> + </pv> + <pv name="Spk-090Crm:Cryo-LT-002:LO"> + <description>LT-002 helium level low</description> + <latching>true</latching> + <annunciating>true</annunciating> + <guidance> + <title>[Cryo Operator Action]</title> + <details>contact CRYO on-call and inform SCL on-call, Cryomodule liquid level low (check the other gauge LT-002). Check level regulation valvesettings, if needed: adjust LMN_HI</details> + </guidance> + </pv> + <pv name="Spk-090Crm:Cryo-LT-001:LOLO"> + <description>LT-002 helium level extremely low</description> + <latching>true</latching> + <annunciating>true</annunciating> + <guidance> + <title>[Cryo Operator Action]</title> + <details>contact CRYO on-call and inform SCL on-call, Cryomodule liquid level too low (check the other gauge LT-001). Check level regulation valve settings, if needed: adjust LMN_HI</details> + </guidance> + </pv> + <pv name="Spk-090Crm:Cryo-LT-002:LOLO"> + <description>LT-002 helium level extremely low</description> + <latching>true</latching> + <annunciating>true</annunciating> + <guidance> + <title>[Cryo Operator Action]</title> + <details>contact CRYO on-call and inform SCL on-call, Cryomodule liquid level too low (check the other gauge LT-002). Check level regulation valvesettings, if needed: adjust LMN_HI</details> + </guidance> + </pv> + <pv name="Spk-090Crm:Cryo-PT-003:HIHI"> + <description>Cavity tanks pressure is too high (typical value is 31mbar in 2K mode and 1050mbar in 4K mode)</description> + <latching>true</latching> + <annunciating>true</annunciating> + <guidance> + <title>[Cryo Operator Action]</title> + <details>contact CRYO on-call and inform SCL on-call, Cryomodule bath pressure too high (check the other gauge PT002). Close supply valve CV01, CV02 if necessary</details> + </guidance> + </pv> + <pv name="Spk-090Crm:Cryo-PT-003:Cable_Error"> + <description>Cavity tanks Pressure Sensor cables are disconnected</description> + <latching>true</latching> + <annunciating>true</annunciating> + <guidance> + <title>[Cryo Operator Action]</title> + <details>contact CRYO on-call and inform SCL on-call, Cryomodule pressure cable seems disconnected (value gets stuck), assign PT002 as measuring device on CV04 and CV-090 </details> + </guidance> + </pv> + <pv name="Spk-090Crm:Cryo-PT-002:HIHI"> + <description>Cavity tanks pressure is too high (typical value is 31mbar in 2K mode and 1050mbar in 4K mode)</description> + <latching>true</latching> + <annunciating>true</annunciating> + <guidance> + <title>[Cryo Operator Action]</title> + <details>contact CRYO on-call and inform SCL on-call,, Cryomodule bath pressure too high (check the other gauge PT003). Close supply valve CV01, CV02 if necessary</details> + </guidance> + </pv> + <pv name="Spk-090Crm:Cryo-PT-002:Cable_Error"> + <description>Cavity tanks Pressure Sensor cables are disconnected</description> + <latching>true</latching> + <annunciating>true</annunciating> + <guidance> + <title>[Cryo Operator Action]</title> + <details>contact CRYO on-call and inform SCL on-call, Cryomodule pressure cable seems disconnected (value gets stuck), assign PT003 as measuring device on CV04 and CV-090 </details> + </guidance> + </pv> + <pv name="Spk-090Crm:Cryo-TT-120:P_Limit_LO"> + <description>Power coupler flange temperature low</description> + <latching>true</latching> + <annunciating>true</annunciating> + <guidance> + <title>[Cryo Operator Action]</title> + <details>contact CRYO on-call and inform SCL on-call, power coupler flange temperature is low, check heater output, if nominal then coupler flow needs to be adjusted (reduced)</details> + </guidance> + </pv> + <pv name="Spk-090Crm:Cryo-TT-120:P_Limit_LOLO"> + <description>Power coupler flange temperature too low</description> + <latching>true</latching> + <annunciating>true</annunciating> + <guidance> + <title>[Cryo Operator Action]</title> + <details>contact CRYO on-call and inform SCL on-call, power coupler flange temperature is too low, check heater output, if nominal then coupler flow needs to be adjusted (reduced)</details> + </guidance> + </pv> + <pv name="Spk-090Crm:Cryo-TT-120:P_Limit_HIHI"> + <description>Power coupler flange temperature too high</description> + <latching>true</latching> + <annunciating>true</annunciating> + <guidance> + <title>[Cryo Operator Action]</title> + <details>contact CRYO on-call and inform SCL on-call, power coupler flange temperature is too high, check heater output, if nominal then coupler flow needs to be adjusted (reduced)</details> + </guidance> + </pv> + <pv name="Spk-090Crm:Cryo-TT-220:P_Limit_LO"> + <description>Power coupler flange temperature low</description> + <latching>true</latching> + <annunciating>true</annunciating> + <guidance> + <title>[Cryo Operator Action]</title> + <details>contact CRYO on-call and inform SCL on-call, power coupler flange temperature is low, check heater output, if nominal then coupler flow needs to be adjusted (reduced)</details> + </guidance> + </pv> + <pv name="Spk-090Crm:Cryo-TT-220:P_Limit_LOLO"> + <description>Power coupler flange temperature too low</description> + <latching>true</latching> + <annunciating>true</annunciating> + <guidance> + <title>[Cryo Operator Action]</title> + <details>contact CRYO on-call and inform SCL on-call, power coupler flange temperature is too low, check heater output, if nominal then coupler flow needs to be adjusted (reduced)</details> + </guidance> + </pv> + <pv name="Spk-090Crm:Cryo-TT-220:P_Limit_HIHI"> + <description>Power coupler flange temperature too high</description> + <latching>true</latching> + <annunciating>true</annunciating> + <guidance> + <title>[Cryo Operator Action]</title> + <details>contact CRYO on-call and inform SCL on-call, power coupler flange temperature is too high, check heater output, if nominal then coupler flow needs to be adjusted (reduced)</details> + </guidance> + </pv> + <pv name="Spk-090Crm:WtrC-FS-013:Flow_OK_WF"> + <description>! Alarm when signal drops from 1 to zero. No Water Flow Antenna 1</description> + <latching>true</latching> + <annunciating>true</annunciating> + <guidance> + <title>[Cryo Operator Action]</title> + <details>contact CRYO on-call and inform SCL on-call, assure Flange temperature TT-120 is correct. Risk of Water freeze if no flow and temperature too low</details> + </guidance> + </pv> + <pv name="Spk-090Crm:WtrC-FS-014:Flow_OK_WF"> + <description>! Alarm when signal drops from 1 to zero. No Water Flow Window 1</description> + <latching>true</latching> + <annunciating>true</annunciating> + <guidance> + <title>[Cryo Operator Action]</title> + <details>contact CRYO on-call and inform SCL on-call, assure Flange temperature TT-120 is correct. Risk of Water freeze if no flow and temperature too low</details> + </guidance> + </pv> + <pv name="Spk-090Crm:WtrC-FS-023:Flow_OK_WF"> + <description>! Alarm when signal drops from 1 to zero. No Water Flow Antenna 2</description> + <latching>true</latching> + <annunciating>true</annunciating> + <guidance> + <title>[Cryo Operator Action]</title> + <details>contact CRYO on-call and inform SCL on-call, assure Flange temperature TT-120 is correct. Risk of Water freeze if no flow and temperature too low</details> + </guidance> + </pv> + <pv name="Spk-090Crm:WtrC-FS-024:Flow_OK_WF"> + <description>! Alarm when signal drops from 1 to zero. No Water Flow Window 2</description> + <latching>true</latching> + <annunciating>true</annunciating> + <guidance> + <title>[Cryo Operator Action]</title> + <details>contact CRYO on-call and inform SCL on-call, assure Flange temperature TT-120 is correct. Risk of Water freeze if no flow and temperature too low</details> + </guidance> + </pv> + </component> + <component name="Cryomodules\SPK-100 Cryomodule"> + <pv name="Spk-100Crm:Cryo-LT-001:HIHI"> + <description>LT-001 helium level extremely high</description> + <latching>true</latching> + <annunciating>true</annunciating> + <guidance> + <title>[Cryo Operator Action]</title> + <details>contact CRYO on-call and inform SCL on-call, Cryomodule liquid level too high (check the other gauge LT-002). Close supply valve CV01, CV02</details> + </guidance> + </pv> + <pv name="Spk-100Crm:Cryo-LT-002:HIHI"> + <description>LT-002 helium level extremely high</description> + <latching>true</latching> + <annunciating>true</annunciating> + <guidance> + <title>[Cryo Operator Action]</title> + <details>contact CRYO on-call and inform SCL on-call, Cryomodule liquid level too high (check the other gauge LT-001). Close supply valve CV01, CV02</details> + </guidance> + </pv> + <pv name="Spk-100Crm:Cryo-LT-001:HI"> + <description>LT-001 helium level high</description> + <latching>true</latching> + <annunciating>true</annunciating> + <guidance> + <title>[Cryo Operator Action]</title> + <details>contact CRYO on-call and inform SCL on-call, Cryomodule liquid level high (check the other gauge LT-002). Check level regulation valve settings, if needed: adjust LMN_LO and if necessary: Close supply valve CV01, CV02</details> + </guidance> + </pv> + <pv name="Spk-100Crm:Cryo-LT-002:HI"> + <description>LT-002 helium level high</description> + <latching>true</latching> + <annunciating>true</annunciating> + <guidance> + <title>[Cryo Operator Action]</title> + <details>contact CRYO on-call and inform SCL on-call, Cryomodule liquid level high (check the other gauge LT-002). Check level regulation valve settings, if needed: adjust LMN_LO and if necessary: Close supply valve CV01, CV02</details> + </guidance> + </pv> + <pv name="Spk-100Crm:Cryo-LT-001:LO"> + <description>LT-001 helium level low</description> + <latching>true</latching> + <annunciating>true</annunciating> + <guidance> + <title>[Cryo Operator Action]</title> + <details>contact CRYO on-call and inform SCL on-call, Cryomodule liquid level low (check the other gauge LT-001). Check level regulation valve settings, if needed: adjust LMN_HI</details> + </guidance> + </pv> + <pv name="Spk-100Crm:Cryo-LT-002:LO"> + <description>LT-002 helium level low</description> + <latching>true</latching> + <annunciating>true</annunciating> + <guidance> + <title>[Cryo Operator Action]</title> + <details>contact CRYO on-call and inform SCL on-call, Cryomodule liquid level low (check the other gauge LT-002). Check level regulation valvesettings, if needed: adjust LMN_HI</details> + </guidance> + </pv> + <pv name="Spk-100Crm:Cryo-LT-001:LOLO"> + <description>LT-002 helium level extremely low</description> + <latching>true</latching> + <annunciating>true</annunciating> + <guidance> + <title>[Cryo Operator Action]</title> + <details>contact CRYO on-call and inform SCL on-call, Cryomodule liquid level too low (check the other gauge LT-001). Check level regulation valve settings, if needed: adjust LMN_HI</details> + </guidance> + </pv> + <pv name="Spk-100Crm:Cryo-LT-002:LOLO"> + <description>LT-002 helium level extremely low</description> + <latching>true</latching> + <annunciating>true</annunciating> + <guidance> + <title>[Cryo Operator Action]</title> + <details>contact CRYO on-call and inform SCL on-call, Cryomodule liquid level too low (check the other gauge LT-002). Check level regulation valvesettings, if needed: adjust LMN_HI</details> + </guidance> + </pv> + <pv name="Spk-100Crm:Cryo-PT-003:HIHI"> + <description>Cavity tanks pressure is too high (typical value is 31mbar in 2K mode and 1050mbar in 4K mode)</description> + <latching>true</latching> + <annunciating>true</annunciating> + <guidance> + <title>[Cryo Operator Action]</title> + <details>contact CRYO on-call and inform SCL on-call, Cryomodule bath pressure too high (check the other gauge PT002). Close supply valve CV01, CV02 if necessary</details> + </guidance> + </pv> + <pv name="Spk-100Crm:Cryo-PT-003:Cable_Error"> + <description>Cavity tanks Pressure Sensor cables are disconnected</description> + <latching>true</latching> + <annunciating>true</annunciating> + <guidance> + <title>[Cryo Operator Action]</title> + <details>contact CRYO on-call and inform SCL on-call, Cryomodule pressure cable seems disconnected (value gets stuck), assign PT002 as measuring device on CV04 and CV-090 </details> + </guidance> + </pv> + <pv name="Spk-100Crm:Cryo-PT-002:HIHI"> + <description>Cavity tanks pressure is too high (typical value is 31mbar in 2K mode and 1050mbar in 4K mode)</description> + <latching>true</latching> + <annunciating>true</annunciating> + <guidance> + <title>[Cryo Operator Action]</title> + <details>contact CRYO on-call and inform SCL on-call,, Cryomodule bath pressure too high (check the other gauge PT003). Close supply valve CV01, CV02 if necessary</details> + </guidance> + </pv> + <pv name="Spk-100Crm:Cryo-PT-002:Cable_Error"> + <description>Cavity tanks Pressure Sensor cables are disconnected</description> + <latching>true</latching> + <annunciating>true</annunciating> + <guidance> + <title>[Cryo Operator Action]</title> + <details>contact CRYO on-call and inform SCL on-call, Cryomodule pressure cable seems disconnected (value gets stuck), assign PT003 as measuring device on CV04 and CV-090 </details> + </guidance> + </pv> + <pv name="Spk-100Crm:Cryo-TT-120:P_Limit_LO"> + <description>Power coupler flange temperature low</description> + <latching>true</latching> + <annunciating>true</annunciating> + <guidance> + <title>[Cryo Operator Action]</title> + <details>contact CRYO on-call and inform SCL on-call, power coupler flange temperature is low, check heater output, if nominal then coupler flow needs to be adjusted (reduced)</details> + </guidance> + </pv> + <pv name="Spk-100Crm:Cryo-TT-120:P_Limit_LOLO"> + <description>Power coupler flange temperature too low</description> + <latching>true</latching> + <annunciating>true</annunciating> + <guidance> + <title>[Cryo Operator Action]</title> + <details>contact CRYO on-call and inform SCL on-call, power coupler flange temperature is too low, check heater output, if nominal then coupler flow needs to be adjusted (reduced)</details> + </guidance> + </pv> + <pv name="Spk-100Crm:Cryo-TT-120:P_Limit_HIHI"> + <description>Power coupler flange temperature too high</description> + <latching>true</latching> + <annunciating>true</annunciating> + <guidance> + <title>[Cryo Operator Action]</title> + <details>contact CRYO on-call and inform SCL on-call, power coupler flange temperature is too high, check heater output, if nominal then coupler flow needs to be adjusted (reduced)</details> + </guidance> + </pv> + <pv name="Spk-100Crm:Cryo-TT-220:P_Limit_LO"> + <description>Power coupler flange temperature low</description> + <latching>true</latching> + <annunciating>true</annunciating> + <guidance> + <title>[Cryo Operator Action]</title> + <details>contact CRYO on-call and inform SCL on-call, power coupler flange temperature is low, check heater output, if nominal then coupler flow needs to be adjusted (reduced)</details> + </guidance> + </pv> + <pv name="Spk-100Crm:Cryo-TT-220:P_Limit_LOLO"> + <description>Power coupler flange temperature too low</description> + <latching>true</latching> + <annunciating>true</annunciating> + <guidance> + <title>[Cryo Operator Action]</title> + <details>contact CRYO on-call and inform SCL on-call, power coupler flange temperature is too low, check heater output, if nominal then coupler flow needs to be adjusted (reduced)</details> + </guidance> + </pv> + <pv name="Spk-100Crm:Cryo-TT-220:P_Limit_HIHI"> + <description>Power coupler flange temperature too high</description> + <latching>true</latching> + <annunciating>true</annunciating> + <guidance> + <title>[Cryo Operator Action]</title> + <details>contact CRYO on-call and inform SCL on-call, power coupler flange temperature is too high, check heater output, if nominal then coupler flow needs to be adjusted (reduced)</details> + </guidance> + </pv> + <pv name="Spk-100Crm:WtrC-FS-013:Flow_OK_WF"> + <description>! Alarm when signal drops from 1 to zero. No Water Flow Antenna 1</description> + <latching>true</latching> + <annunciating>true</annunciating> + <guidance> + <title>[Cryo Operator Action]</title> + <details>contact CRYO on-call and inform SCL on-call, assure Flange temperature TT-120 is correct. Risk of Water freeze if no flow and temperature too low</details> + </guidance> + </pv> + <pv name="Spk-100Crm:WtrC-FS-014:Flow_OK_WF"> + <description>! Alarm when signal drops from 1 to zero. No Water Flow Window 1</description> + <latching>true</latching> + <annunciating>true</annunciating> + <guidance> + <title>[Cryo Operator Action]</title> + <details>contact CRYO on-call and inform SCL on-call, assure Flange temperature TT-120 is correct. Risk of Water freeze if no flow and temperature too low</details> + </guidance> + </pv> + <pv name="Spk-100Crm:WtrC-FS-023:Flow_OK_WF"> + <description>! Alarm when signal drops from 1 to zero. No Water Flow Antenna 2</description> + <latching>true</latching> + <annunciating>true</annunciating> + <guidance> + <title>[Cryo Operator Action]</title> + <details>contact CRYO on-call and inform SCL on-call, assure Flange temperature TT-120 is correct. Risk of Water freeze if no flow and temperature too low</details> + </guidance> + </pv> + <pv name="Spk-100Crm:WtrC-FS-024:Flow_OK_WF"> + <description>! Alarm when signal drops from 1 to zero. No Water Flow Window 2</description> + <latching>true</latching> + <annunciating>true</annunciating> + <guidance> + <title>[Cryo Operator Action]</title> + <details>contact CRYO on-call and inform SCL on-call, assure Flange temperature TT-120 is correct. Risk of Water freeze if no flow and temperature too low</details> + </guidance> + </pv> + </component> + <component name="Cryomodules\SPK-110 Cryomodule"> + <pv name="Spk-110Crm:Cryo-LT-001:HIHI"> + <description>LT-001 helium level extremely high</description> + <latching>true</latching> + <annunciating>true</annunciating> + <guidance> + <title>[Cryo Operator Action]</title> + <details>contact CRYO on-call and inform SCL on-call, Cryomodule liquid level too high (check the other gauge LT-002). Close supply valve CV01, CV02</details> + </guidance> + </pv> + <pv name="Spk-110Crm:Cryo-LT-002:HIHI"> + <description>LT-002 helium level extremely high</description> + <latching>true</latching> + <annunciating>true</annunciating> + <guidance> + <title>[Cryo Operator Action]</title> + <details>contact CRYO on-call and inform SCL on-call, Cryomodule liquid level too high (check the other gauge LT-001). Close supply valve CV01, CV02</details> + </guidance> + </pv> + <pv name="Spk-110Crm:Cryo-LT-001:HI"> + <description>LT-001 helium level high</description> + <latching>true</latching> + <annunciating>true</annunciating> + <guidance> + <title>[Cryo Operator Action]</title> + <details>contact CRYO on-call and inform SCL on-call, Cryomodule liquid level high (check the other gauge LT-002). Check level regulation valve settings, if needed: adjust LMN_LO and if necessary: Close supply valve CV01, CV02</details> + </guidance> + </pv> + <pv name="Spk-110Crm:Cryo-LT-002:HI"> + <description>LT-002 helium level high</description> + <latching>true</latching> + <annunciating>true</annunciating> + <guidance> + <title>[Cryo Operator Action]</title> + <details>contact CRYO on-call and inform SCL on-call, Cryomodule liquid level high (check the other gauge LT-002). Check level regulation valve settings, if needed: adjust LMN_LO and if necessary: Close supply valve CV01, CV02</details> + </guidance> + </pv> + <pv name="Spk-110Crm:Cryo-LT-001:LO"> + <description>LT-001 helium level low</description> + <latching>true</latching> + <annunciating>true</annunciating> + <guidance> + <title>[Cryo Operator Action]</title> + <details>contact CRYO on-call and inform SCL on-call, Cryomodule liquid level low (check the other gauge LT-001). Check level regulation valve settings, if needed: adjust LMN_HI</details> + </guidance> + </pv> + <pv name="Spk-110Crm:Cryo-LT-002:LO"> + <description>LT-002 helium level low</description> + <latching>true</latching> + <annunciating>true</annunciating> + <guidance> + <title>[Cryo Operator Action]</title> + <details>contact CRYO on-call and inform SCL on-call, Cryomodule liquid level low (check the other gauge LT-002). Check level regulation valvesettings, if needed: adjust LMN_HI</details> + </guidance> + </pv> + <pv name="Spk-110Crm:Cryo-LT-001:LOLO"> + <description>LT-002 helium level extremely low</description> + <latching>true</latching> + <annunciating>true</annunciating> + <guidance> + <title>[Cryo Operator Action]</title> + <details>contact CRYO on-call and inform SCL on-call, Cryomodule liquid level too low (check the other gauge LT-001). Check level regulation valve settings, if needed: adjust LMN_HI</details> + </guidance> + </pv> + <pv name="Spk-110Crm:Cryo-LT-002:LOLO"> + <description>LT-002 helium level extremely low</description> + <latching>true</latching> + <annunciating>true</annunciating> + <guidance> + <title>[Cryo Operator Action]</title> + <details>contact CRYO on-call and inform SCL on-call, Cryomodule liquid level too low (check the other gauge LT-002). Check level regulation valvesettings, if needed: adjust LMN_HI</details> + </guidance> + </pv> + <pv name="Spk-110Crm:Cryo-PT-003:HIHI"> + <description>Cavity tanks pressure is too high (typical value is 31mbar in 2K mode and 1050mbar in 4K mode)</description> + <latching>true</latching> + <annunciating>true</annunciating> + <guidance> + <title>[Cryo Operator Action]</title> + <details>contact CRYO on-call and inform SCL on-call, Cryomodule bath pressure too high (check the other gauge PT002). Close supply valve CV01, CV02 if necessary</details> + </guidance> + </pv> + <pv name="Spk-110Crm:Cryo-PT-003:Cable_Error"> + <description>Cavity tanks Pressure Sensor cables are disconnected</description> + <latching>true</latching> + <annunciating>true</annunciating> + <guidance> + <title>[Cryo Operator Action]</title> + <details>contact CRYO on-call and inform SCL on-call, Cryomodule pressure cable seems disconnected (value gets stuck), assign PT002 as measuring device on CV04 and CV-090 </details> + </guidance> + </pv> + <pv name="Spk-110Crm:Cryo-PT-002:HIHI"> + <description>Cavity tanks pressure is too high (typical value is 31mbar in 2K mode and 1050mbar in 4K mode)</description> + <latching>true</latching> + <annunciating>true</annunciating> + <guidance> + <title>[Cryo Operator Action]</title> + <details>contact CRYO on-call and inform SCL on-call,, Cryomodule bath pressure too high (check the other gauge PT003). Close supply valve CV01, CV02 if necessary</details> + </guidance> + </pv> + <pv name="Spk-110Crm:Cryo-PT-002:Cable_Error"> + <description>Cavity tanks Pressure Sensor cables are disconnected</description> + <latching>true</latching> + <annunciating>true</annunciating> + <guidance> + <title>[Cryo Operator Action]</title> + <details>contact CRYO on-call and inform SCL on-call, Cryomodule pressure cable seems disconnected (value gets stuck), assign PT003 as measuring device on CV04 and CV-090 </details> + </guidance> + </pv> + <pv name="Spk-110Crm:Cryo-TT-120:P_Limit_LO"> + <description>Power coupler flange temperature low</description> + <latching>true</latching> + <annunciating>true</annunciating> + <guidance> + <title>[Cryo Operator Action]</title> + <details>contact CRYO on-call and inform SCL on-call, power coupler flange temperature is low, check heater output, if nominal then coupler flow needs to be adjusted (reduced)</details> + </guidance> + </pv> + <pv name="Spk-110Crm:Cryo-TT-120:P_Limit_LOLO"> + <description>Power coupler flange temperature too low</description> + <latching>true</latching> + <annunciating>true</annunciating> + <guidance> + <title>[Cryo Operator Action]</title> + <details>contact CRYO on-call and inform SCL on-call, power coupler flange temperature is too low, check heater output, if nominal then coupler flow needs to be adjusted (reduced)</details> + </guidance> + </pv> + <pv name="Spk-110Crm:Cryo-TT-120:P_Limit_HIHI"> + <description>Power coupler flange temperature too high</description> + <latching>true</latching> + <annunciating>true</annunciating> + <guidance> + <title>[Cryo Operator Action]</title> + <details>contact CRYO on-call and inform SCL on-call, power coupler flange temperature is too high, check heater output, if nominal then coupler flow needs to be adjusted (reduced)</details> + </guidance> + </pv> + <pv name="Spk-110Crm:Cryo-TT-220:P_Limit_LO"> + <description>Power coupler flange temperature low</description> + <latching>true</latching> + <annunciating>true</annunciating> + <guidance> + <title>[Cryo Operator Action]</title> + <details>contact CRYO on-call and inform SCL on-call, power coupler flange temperature is low, check heater output, if nominal then coupler flow needs to be adjusted (reduced)</details> + </guidance> + </pv> + <pv name="Spk-110Crm:Cryo-TT-220:P_Limit_LOLO"> + <description>Power coupler flange temperature too low</description> + <latching>true</latching> + <annunciating>true</annunciating> + <guidance> + <title>[Cryo Operator Action]</title> + <details>contact CRYO on-call and inform SCL on-call, power coupler flange temperature is too low, check heater output, if nominal then coupler flow needs to be adjusted (reduced)</details> + </guidance> + </pv> + <pv name="Spk-110Crm:Cryo-TT-220:P_Limit_HIHI"> + <description>Power coupler flange temperature too high</description> + <latching>true</latching> + <annunciating>true</annunciating> + <guidance> + <title>[Cryo Operator Action]</title> + <details>contact CRYO on-call and inform SCL on-call, power coupler flange temperature is too high, check heater output, if nominal then coupler flow needs to be adjusted (reduced)</details> + </guidance> + </pv> + <pv name="Spk-110Crm:WtrC-FS-013:Flow_OK_WF"> + <description>! Alarm when signal drops from 1 to zero. No Water Flow Antenna 1</description> + <latching>true</latching> + <annunciating>true</annunciating> + <guidance> + <title>[Cryo Operator Action]</title> + <details>contact CRYO on-call and inform SCL on-call, assure Flange temperature TT-120 is correct. Risk of Water freeze if no flow and temperature too low</details> + </guidance> + </pv> + <pv name="Spk-110Crm:WtrC-FS-014:Flow_OK_WF"> + <description>! Alarm when signal drops from 1 to zero. No Water Flow Window 1</description> + <latching>true</latching> + <annunciating>true</annunciating> + <guidance> + <title>[Cryo Operator Action]</title> + <details>contact CRYO on-call and inform SCL on-call, assure Flange temperature TT-120 is correct. Risk of Water freeze if no flow and temperature too low</details> + </guidance> + </pv> + <pv name="Spk-110Crm:WtrC-FS-023:Flow_OK_WF"> + <description>! Alarm when signal drops from 1 to zero. No Water Flow Antenna 2</description> + <latching>true</latching> + <annunciating>true</annunciating> + <guidance> + <title>[Cryo Operator Action]</title> + <details>contact CRYO on-call and inform SCL on-call, assure Flange temperature TT-120 is correct. Risk of Water freeze if no flow and temperature too low</details> + </guidance> + </pv> + <pv name="Spk-110Crm:WtrC-FS-024:Flow_OK_WF"> + <description>! Alarm when signal drops from 1 to zero. No Water Flow Window 2</description> + <latching>true</latching> + <annunciating>true</annunciating> + <guidance> + <title>[Cryo Operator Action]</title> + <details>contact CRYO on-call and inform SCL on-call, assure Flange temperature TT-120 is correct. Risk of Water freeze if no flow and temperature too low</details> + </guidance> + </pv> + </component> + <component name="Cryomodules\SPK-120 Cryomodule"> + <pv name="Spk-120Crm:Cryo-LT-001:HIHI"> + <description>LT-001 helium level extremely high</description> + <latching>true</latching> + <annunciating>true</annunciating> + <guidance> + <title>[Cryo Operator Action]</title> + <details>contact CRYO on-call and inform SCL on-call, Cryomodule liquid level too high (check the other gauge LT-002). Close supply valve CV01, CV02</details> + </guidance> + </pv> + <pv name="Spk-120Crm:Cryo-LT-002:HIHI"> + <description>LT-002 helium level extremely high</description> + <latching>true</latching> + <annunciating>true</annunciating> + <guidance> + <title>[Cryo Operator Action]</title> + <details>contact CRYO on-call and inform SCL on-call, Cryomodule liquid level too high (check the other gauge LT-001). Close supply valve CV01, CV02</details> + </guidance> + </pv> + <pv name="Spk-120Crm:Cryo-LT-001:HI"> + <description>LT-001 helium level high</description> + <latching>true</latching> + <annunciating>true</annunciating> + <guidance> + <title>[Cryo Operator Action]</title> + <details>contact CRYO on-call and inform SCL on-call, Cryomodule liquid level high (check the other gauge LT-002). Check level regulation valve settings, if needed: adjust LMN_LO and if necessary: Close supply valve CV01, CV02</details> + </guidance> + </pv> + <pv name="Spk-120Crm:Cryo-LT-002:HI"> + <description>LT-002 helium level high</description> + <latching>true</latching> + <annunciating>true</annunciating> + <guidance> + <title>[Cryo Operator Action]</title> + <details>contact CRYO on-call and inform SCL on-call, Cryomodule liquid level high (check the other gauge LT-002). Check level regulation valve settings, if needed: adjust LMN_LO and if necessary: Close supply valve CV01, CV02</details> + </guidance> + </pv> + <pv name="Spk-120Crm:Cryo-LT-001:LO"> + <description>LT-001 helium level low</description> + <latching>true</latching> + <annunciating>true</annunciating> + <guidance> + <title>[Cryo Operator Action]</title> + <details>contact CRYO on-call and inform SCL on-call, Cryomodule liquid level low (check the other gauge LT-001). Check level regulation valve settings, if needed: adjust LMN_HI</details> + </guidance> + </pv> + <pv name="Spk-120Crm:Cryo-LT-002:LO"> + <description>LT-002 helium level low</description> + <latching>true</latching> + <annunciating>true</annunciating> + <guidance> + <title>[Cryo Operator Action]</title> + <details>contact CRYO on-call and inform SCL on-call, Cryomodule liquid level low (check the other gauge LT-002). Check level regulation valvesettings, if needed: adjust LMN_HI</details> + </guidance> + </pv> + <pv name="Spk-120Crm:Cryo-LT-001:LOLO"> + <description>LT-002 helium level extremely low</description> + <latching>true</latching> + <annunciating>true</annunciating> + <guidance> + <title>[Cryo Operator Action]</title> + <details>contact CRYO on-call and inform SCL on-call, Cryomodule liquid level too low (check the other gauge LT-001). Check level regulation valve settings, if needed: adjust LMN_HI</details> + </guidance> + </pv> + <pv name="Spk-120Crm:Cryo-LT-002:LOLO"> + <description>LT-002 helium level extremely low</description> + <latching>true</latching> + <annunciating>true</annunciating> + <guidance> + <title>[Cryo Operator Action]</title> + <details>contact CRYO on-call and inform SCL on-call, Cryomodule liquid level too low (check the other gauge LT-002). Check level regulation valvesettings, if needed: adjust LMN_HI</details> + </guidance> + </pv> + <pv name="Spk-120Crm:Cryo-PT-003:HIHI"> + <description>Cavity tanks pressure is too high (typical value is 31mbar in 2K mode and 1050mbar in 4K mode)</description> + <latching>true</latching> + <annunciating>true</annunciating> + <guidance> + <title>[Cryo Operator Action]</title> + <details>contact CRYO on-call and inform SCL on-call, Cryomodule bath pressure too high (check the other gauge PT002). Close supply valve CV01, CV02 if necessary</details> + </guidance> + </pv> + <pv name="Spk-120Crm:Cryo-PT-003:Cable_Error"> + <description>Cavity tanks Pressure Sensor cables are disconnected</description> + <latching>true</latching> + <annunciating>true</annunciating> + <guidance> + <title>[Cryo Operator Action]</title> + <details>contact CRYO on-call and inform SCL on-call, Cryomodule pressure cable seems disconnected (value gets stuck), assign PT002 as measuring device on CV04 and CV-090 </details> + </guidance> + </pv> + <pv name="Spk-120Crm:Cryo-PT-002:HIHI"> + <description>Cavity tanks pressure is too high (typical value is 31mbar in 2K mode and 1050mbar in 4K mode)</description> + <latching>true</latching> + <annunciating>true</annunciating> + <guidance> + <title>[Cryo Operator Action]</title> + <details>contact CRYO on-call and inform SCL on-call,, Cryomodule bath pressure too high (check the other gauge PT003). Close supply valve CV01, CV02 if necessary</details> + </guidance> + </pv> + <pv name="Spk-120Crm:Cryo-PT-002:Cable_Error"> + <description>Cavity tanks Pressure Sensor cables are disconnected</description> + <latching>true</latching> + <annunciating>true</annunciating> + <guidance> + <title>[Cryo Operator Action]</title> + <details>contact CRYO on-call and inform SCL on-call, Cryomodule pressure cable seems disconnected (value gets stuck), assign PT003 as measuring device on CV04 and CV-090 </details> + </guidance> + </pv> + <pv name="Spk-120Crm:Cryo-TT-120:P_Limit_LO"> + <description>Power coupler flange temperature low</description> + <latching>true</latching> + <annunciating>true</annunciating> + <guidance> + <title>[Cryo Operator Action]</title> + <details>contact CRYO on-call and inform SCL on-call, power coupler flange temperature is low, check heater output, if nominal then coupler flow needs to be adjusted (reduced)</details> + </guidance> + </pv> + <pv name="Spk-120Crm:Cryo-TT-120:P_Limit_LOLO"> + <description>Power coupler flange temperature too low</description> + <latching>true</latching> + <annunciating>true</annunciating> + <guidance> + <title>[Cryo Operator Action]</title> + <details>contact CRYO on-call and inform SCL on-call, power coupler flange temperature is too low, check heater output, if nominal then coupler flow needs to be adjusted (reduced)</details> + </guidance> + </pv> + <pv name="Spk-120Crm:Cryo-TT-120:P_Limit_HIHI"> + <description>Power coupler flange temperature too high</description> + <latching>true</latching> + <annunciating>true</annunciating> + <guidance> + <title>[Cryo Operator Action]</title> + <details>contact CRYO on-call and inform SCL on-call, power coupler flange temperature is too high, check heater output, if nominal then coupler flow needs to be adjusted (reduced)</details> + </guidance> + </pv> + <pv name="Spk-120Crm:Cryo-TT-220:P_Limit_LO"> + <description>Power coupler flange temperature low</description> + <latching>true</latching> + <annunciating>true</annunciating> + <guidance> + <title>[Cryo Operator Action]</title> + <details>contact CRYO on-call and inform SCL on-call, power coupler flange temperature is low, check heater output, if nominal then coupler flow needs to be adjusted (reduced)</details> + </guidance> + </pv> + <pv name="Spk-120Crm:Cryo-TT-220:P_Limit_LOLO"> + <description>Power coupler flange temperature too low</description> + <latching>true</latching> + <annunciating>true</annunciating> + <guidance> + <title>[Cryo Operator Action]</title> + <details>contact CRYO on-call and inform SCL on-call, power coupler flange temperature is too low, check heater output, if nominal then coupler flow needs to be adjusted (reduced)</details> + </guidance> + </pv> + <pv name="Spk-120Crm:Cryo-TT-220:P_Limit_HIHI"> + <description>Power coupler flange temperature too high</description> + <latching>true</latching> + <annunciating>true</annunciating> + <guidance> + <title>[Cryo Operator Action]</title> + <details>contact CRYO on-call and inform SCL on-call, power coupler flange temperature is too high, check heater output, if nominal then coupler flow needs to be adjusted (reduced)</details> + </guidance> + </pv> + <pv name="Spk-120Crm:WtrC-FS-013:Flow_OK_WF"> + <description>! Alarm when signal drops from 1 to zero. No Water Flow Antenna 1</description> + <latching>true</latching> + <annunciating>true</annunciating> + <guidance> + <title>[Cryo Operator Action]</title> + <details>contact CRYO on-call and inform SCL on-call, assure Flange temperature TT-120 is correct. Risk of Water freeze if no flow and temperature too low</details> + </guidance> + </pv> + <pv name="Spk-120Crm:WtrC-FS-014:Flow_OK_WF"> + <description>! Alarm when signal drops from 1 to zero. No Water Flow Window 1</description> + <latching>true</latching> + <annunciating>true</annunciating> + <guidance> + <title>[Cryo Operator Action]</title> + <details>contact CRYO on-call and inform SCL on-call, assure Flange temperature TT-120 is correct. Risk of Water freeze if no flow and temperature too low</details> + </guidance> + </pv> + <pv name="Spk-120Crm:WtrC-FS-023:Flow_OK_WF"> + <description>! Alarm when signal drops from 1 to zero. No Water Flow Antenna 2</description> + <latching>true</latching> + <annunciating>true</annunciating> + <guidance> + <title>[Cryo Operator Action]</title> + <details>contact CRYO on-call and inform SCL on-call, assure Flange temperature TT-120 is correct. Risk of Water freeze if no flow and temperature too low</details> + </guidance> + </pv> + <pv name="Spk-120Crm:WtrC-FS-024:Flow_OK_WF"> + <description>! Alarm when signal drops from 1 to zero. No Water Flow Window 2</description> + <latching>true</latching> + <annunciating>true</annunciating> + <guidance> + <title>[Cryo Operator Action]</title> + <details>contact CRYO on-call and inform SCL on-call, assure Flange temperature TT-120 is correct. Risk of Water freeze if no flow and temperature too low</details> + </guidance> + </pv> + </component> + <component name="Cryomodules\SPK-130 Cryomodule"> + <pv name="Spk-130Crm:Cryo-LT-001:HIHI"> + <description>LT-001 helium level extremely high</description> + <latching>true</latching> + <annunciating>true</annunciating> + <guidance> + <title>[Cryo Operator Action]</title> + <details>contact CRYO on-call and inform SCL on-call, Cryomodule liquid level too high (check the other gauge LT-002). Close supply valve CV01, CV02</details> + </guidance> + </pv> + <pv name="Spk-130Crm:Cryo-LT-002:HIHI"> + <description>LT-002 helium level extremely high</description> + <latching>true</latching> + <annunciating>true</annunciating> + <guidance> + <title>[Cryo Operator Action]</title> + <details>contact CRYO on-call and inform SCL on-call, Cryomodule liquid level too high (check the other gauge LT-001). Close supply valve CV01, CV02</details> + </guidance> + </pv> + <pv name="Spk-130Crm:Cryo-LT-001:HI"> + <description>LT-001 helium level high</description> + <latching>true</latching> + <annunciating>true</annunciating> + <guidance> + <title>[Cryo Operator Action]</title> + <details>contact CRYO on-call and inform SCL on-call, Cryomodule liquid level high (check the other gauge LT-002). Check level regulation valve settings, if needed: adjust LMN_LO and if necessary: Close supply valve CV01, CV02</details> + </guidance> + </pv> + <pv name="Spk-130Crm:Cryo-LT-002:HI"> + <description>LT-002 helium level high</description> + <latching>true</latching> + <annunciating>true</annunciating> + <guidance> + <title>[Cryo Operator Action]</title> + <details>contact CRYO on-call and inform SCL on-call, Cryomodule liquid level high (check the other gauge LT-002). Check level regulation valve settings, if needed: adjust LMN_LO and if necessary: Close supply valve CV01, CV02</details> + </guidance> + </pv> + <pv name="Spk-130Crm:Cryo-LT-001:LO"> + <description>LT-001 helium level low</description> + <latching>true</latching> + <annunciating>true</annunciating> + <guidance> + <title>[Cryo Operator Action]</title> + <details>contact CRYO on-call and inform SCL on-call, Cryomodule liquid level low (check the other gauge LT-001). Check level regulation valve settings, if needed: adjust LMN_HI</details> + </guidance> + </pv> + <pv name="Spk-130Crm:Cryo-LT-002:LO"> + <description>LT-002 helium level low</description> + <latching>true</latching> + <annunciating>true</annunciating> + <guidance> + <title>[Cryo Operator Action]</title> + <details>contact CRYO on-call and inform SCL on-call, Cryomodule liquid level low (check the other gauge LT-002). Check level regulation valvesettings, if needed: adjust LMN_HI</details> + </guidance> + </pv> + <pv name="Spk-130Crm:Cryo-LT-001:LOLO"> + <description>LT-002 helium level extremely low</description> + <latching>true</latching> + <annunciating>true</annunciating> + <guidance> + <title>[Cryo Operator Action]</title> + <details>contact CRYO on-call and inform SCL on-call, Cryomodule liquid level too low (check the other gauge LT-001). Check level regulation valve settings, if needed: adjust LMN_HI</details> + </guidance> + </pv> + <pv name="Spk-130Crm:Cryo-LT-002:LOLO"> + <description>LT-002 helium level extremely low</description> + <latching>true</latching> + <annunciating>true</annunciating> + <guidance> + <title>[Cryo Operator Action]</title> + <details>contact CRYO on-call and inform SCL on-call, Cryomodule liquid level too low (check the other gauge LT-002). Check level regulation valvesettings, if needed: adjust LMN_HI</details> + </guidance> + </pv> + <pv name="Spk-130Crm:Cryo-PT-003:HIHI"> + <description>Cavity tanks pressure is too high (typical value is 31mbar in 2K mode and 1050mbar in 4K mode)</description> + <latching>true</latching> + <annunciating>true</annunciating> + <guidance> + <title>[Cryo Operator Action]</title> + <details>contact CRYO on-call and inform SCL on-call, Cryomodule bath pressure too high (check the other gauge PT002). Close supply valve CV01, CV02 if necessary</details> + </guidance> + </pv> + <pv name="Spk-130Crm:Cryo-PT-003:Cable_Error"> + <description>Cavity tanks Pressure Sensor cables are disconnected</description> + <latching>true</latching> + <annunciating>true</annunciating> + <guidance> + <title>[Cryo Operator Action]</title> + <details>contact CRYO on-call and inform SCL on-call, Cryomodule pressure cable seems disconnected (value gets stuck), assign PT002 as measuring device on CV04 and CV-090 </details> + </guidance> + </pv> + <pv name="Spk-130Crm:Cryo-PT-002:HIHI"> + <description>Cavity tanks pressure is too high (typical value is 31mbar in 2K mode and 1050mbar in 4K mode)</description> + <latching>true</latching> + <annunciating>true</annunciating> + <guidance> + <title>[Cryo Operator Action]</title> + <details>contact CRYO on-call and inform SCL on-call,, Cryomodule bath pressure too high (check the other gauge PT003). Close supply valve CV01, CV02 if necessary</details> + </guidance> + </pv> + <pv name="Spk-130Crm:Cryo-PT-002:Cable_Error"> + <description>Cavity tanks Pressure Sensor cables are disconnected</description> + <latching>true</latching> + <annunciating>true</annunciating> + <guidance> + <title>[Cryo Operator Action]</title> + <details>contact CRYO on-call and inform SCL on-call, Cryomodule pressure cable seems disconnected (value gets stuck), assign PT003 as measuring device on CV04 and CV-090 </details> + </guidance> + </pv> + <pv name="Spk-130Crm:Cryo-TT-120:P_Limit_LO"> + <description>Power coupler flange temperature low</description> + <latching>true</latching> + <annunciating>true</annunciating> + <guidance> + <title>[Cryo Operator Action]</title> + <details>contact CRYO on-call and inform SCL on-call, power coupler flange temperature is low, check heater output, if nominal then coupler flow needs to be adjusted (reduced)</details> + </guidance> + </pv> + <pv name="Spk-130Crm:Cryo-TT-120:P_Limit_LOLO"> + <description>Power coupler flange temperature too low</description> + <latching>true</latching> + <annunciating>true</annunciating> + <guidance> + <title>[Cryo Operator Action]</title> + <details>contact CRYO on-call and inform SCL on-call, power coupler flange temperature is too low, check heater output, if nominal then coupler flow needs to be adjusted (reduced)</details> + </guidance> + </pv> + <pv name="Spk-130Crm:Cryo-TT-120:P_Limit_HIHI"> + <description>Power coupler flange temperature too high</description> + <latching>true</latching> + <annunciating>true</annunciating> + <guidance> + <title>[Cryo Operator Action]</title> + <details>contact CRYO on-call and inform SCL on-call, power coupler flange temperature is too high, check heater output, if nominal then coupler flow needs to be adjusted (increased)</details> + </guidance> + </pv> + <pv name="Spk-130Crm:Cryo-TT-220:P_Limit_LO"> + <description>Power coupler flange temperature low</description> + <latching>true</latching> + <annunciating>true</annunciating> + <guidance> + <title>[Cryo Operator Action]</title> + <details>contact CRYO on-call and inform SCL on-call, power coupler flange temperature is low, check heater output, if nominal then coupler flow needs to be adjusted (reduced)</details> + </guidance> + </pv> + <pv name="Spk-130Crm:Cryo-TT-220:P_Limit_LOLO"> + <description>Power coupler flange temperature too low</description> + <latching>true</latching> + <annunciating>true</annunciating> + <guidance> + <title>[Cryo Operator Action]</title> + <details>contact CRYO on-call and inform SCL on-call, power coupler flange temperature is too low, check heater output, if nominal then coupler flow needs to be adjusted (reduced)</details> + </guidance> + </pv> + <pv name="Spk-130Crm:Cryo-TT-220:P_Limit_HIHI"> + <description>Power coupler flange temperature too high</description> + <latching>true</latching> + <annunciating>true</annunciating> + <guidance> + <title>[Cryo Operator Action]</title> + <details>contact CRYO on-call and inform SCL on-call, power coupler flange temperature is too high, check heater output, if nominal then coupler flow needs to be adjusted (increased)</details> + </guidance> + </pv> + <pv name="Spk-130Crm:WtrC-FS-013:Flow_OK_WF"> + <description>! Alarm when signal drops from 1 to zero. No Water Flow Antenna 1</description> + <latching>true</latching> + <annunciating>true</annunciating> + <guidance> + <title>[Cryo Operator Action]</title> + <details>contact CRYO on-call and inform SCL on-call, assure Flange temperature TT-120 is correct. Risk of Water freeze if no flow and temperature too low</details> + </guidance> + </pv> + <pv name="Spk-130Crm:WtrC-FS-014:Flow_OK_WF"> + <description>! Alarm when signal drops from 1 to zero. No Water Flow Window 1</description> + <latching>true</latching> + <annunciating>true</annunciating> + <guidance> + <title>[Cryo Operator Action]</title> + <details>contact CRYO on-call and inform SCL on-call, assure Flange temperature TT-120 is correct. Risk of Water freeze if no flow and temperature too low</details> + </guidance> + </pv> + <pv name="Spk-130Crm:WtrC-FS-023:Flow_OK_WF"> + <description>! Alarm when signal drops from 1 to zero. No Water Flow Antenna 2</description> + <latching>true</latching> + <annunciating>true</annunciating> + <guidance> + <title>[Cryo Operator Action]</title> + <details>contact CRYO on-call and inform SCL on-call, assure Flange temperature TT-120 is correct. Risk of Water freeze if no flow and temperature too low</details> + </guidance> + </pv> + <pv name="Spk-130Crm:WtrC-FS-024:Flow_OK_WF"> + <description>! Alarm when signal drops from 1 to zero. No Water Flow Window 2</description> + <latching>true</latching> + <annunciating>true</annunciating> + <guidance> + <title>[Cryo Operator Action]</title> + <details>contact CRYO on-call and inform SCL on-call, assure Flange temperature TT-120 is correct. Risk of Water freeze if no flow and temperature too low</details> + </guidance> + </pv> + </component> + <component name="Cryomodules\MBL-010 Cryomodule"> + <pv name="MBL-010Crm:Cryo-LT-001:HIHI"> + <description>LT-001 helium level extremely high</description> + <latching>true</latching> + <annunciating>true</annunciating> + <guidance> + <title>[Cryo Operator Action]</title> + <details>contact CRYO on-call and inform SCL on-call, Cryomodule liquid level too high (check the other gauge LT-002). Close supply valve CV01, CV02</details> + </guidance> + </pv> + <pv name="MBL-010Crm:Cryo-LT-002:HIHI"> + <description>LT-002 helium level extremely high</description> + <latching>true</latching> + <annunciating>true</annunciating> + <guidance> + <title>[Cryo Operator Action]</title> + <details>contact CRYO on-call and inform SCL on-call, Cryomodule liquid level too high (check the other gauge LT-001). Close supply valve CV01, CV02</details> + </guidance> + </pv> + <pv name="MBL-010Crm:Cryo-LT-001:HI"> + <description>LT-001 helium level high</description> + <latching>true</latching> + <annunciating>true</annunciating> + <guidance> + <title>[Cryo Operator Action]</title> + <details>contact CRYO on-call and inform SCL on-call, Cryomodule liquid level high (check the other gauge LT-002). Check level regulation valve settings, if needed: adjust LMN_LO and if necessary: Close supply valve CV01, CV02</details> + </guidance> + </pv> + <pv name="MBL-010Crm:Cryo-LT-002:HI"> + <description>LT-002 helium level high</description> + <latching>true</latching> + <annunciating>true</annunciating> + <guidance> + <title>[Cryo Operator Action]</title> + <details>contact CRYO on-call and inform SCL on-call, Cryomodule liquid level high (check the other gauge LT-002). Check level regulation valve settings, if needed: adjust LMN_LO and if necessary: Close supply valve CV01, CV02</details> + </guidance> + </pv> + <pv name="MBL-010Crm:Cryo-LT-001:LO"> + <description>LT-001 helium level low</description> + <latching>true</latching> + <annunciating>true</annunciating> + <guidance> + <title>[Cryo Operator Action]</title> + <details>contact CRYO on-call and inform SCL on-call, Cryomodule liquid level low (check the other gauge LT-001). Check level regulation valve settings, if needed: adjust LMN_HI</details> + </guidance> + </pv> + <pv name="MBL-010Crm:Cryo-LT-002:LO"> + <description>LT-002 helium level low</description> + <latching>true</latching> + <annunciating>true</annunciating> + <guidance> + <title>[Cryo Operator Action]</title> + <details>contact CRYO on-call and inform SCL on-call, Cryomodule liquid level low (check the other gauge LT-002). Check level regulation valvesettings, if needed: adjust LMN_HI</details> + </guidance> + </pv> + <pv name="MBL-010Crm:Cryo-LT-001:LOLO"> + <description>LT-002 helium level extremely low</description> + <latching>true</latching> + <annunciating>true</annunciating> + <guidance> + <title>[Cryo Operator Action]</title> + <details>contact CRYO on-call and inform SCL on-call, Cryomodule liquid level too low (check the other gauge LT-001). Check level regulation valve settings, if needed: adjust LMN_HI</details> + </guidance> + </pv> + <pv name="MBL-010Crm:Cryo-LT-002:LOLO"> + <description>LT-002 helium level extremely low</description> + <latching>true</latching> + <annunciating>true</annunciating> + <guidance> + <title>[Cryo Operator Action]</title> + <details>contact CRYO on-call and inform SCL on-call, Cryomodule liquid level too low (check the other gauge LT-002). Check level regulation valvesettings, if needed: adjust LMN_HI</details> + </guidance> + </pv> + <pv name="MBL-010Crm:Cryo-PT-003:HIHI"> + <description>Cavity tanks pressure is too high (typical value is 31mbar in 2K mode and 1050mbar in 4K mode)</description> + <latching>true</latching> + <annunciating>true</annunciating> + <guidance> + <title>[Cryo Operator Action]</title> + <details>contact CRYO on-call and inform SCL on-call, Cryomodule bath pressure too high (check the other gauge PT002). Close supply valve CV01, CV02 if necessary</details> + </guidance> + </pv> + <pv name="MBL-010Crm:Cryo-PT-003:Cable_Error"> + <description>Cavity tanks Pressure Sensor cables are disconnected</description> + <latching>true</latching> + <annunciating>true</annunciating> + <guidance> + <title>[Cryo Operator Action]</title> + <details>contact CRYO on-call and inform SCL on-call, Cryomodule pressure cable seems disconnected (value gets stuck), assign PT002 as measuring device on CV04 and CV-090 </details> + </guidance> + </pv> + <pv name="MBL-010Crm:Cryo-PT-004:HIHI"> + <description>Cavity tanks pressure is too high (typical value is 31mbar in 2K mode and 1050mbar in 4K mode)</description> + <latching>true</latching> + <annunciating>true</annunciating> + <guidance> + <title>[Cryo Operator Action]</title> + <details>contact CRYO on-call and inform SCL on-call,, Cryomodule bath pressure too high (check the other gauge PT003). Close supply valve CV01, CV02 if necessary</details> + </guidance> + </pv> + <pv name="MBL-010Crm:Cryo-PT-004:Cable_Error"> + <description>Cavity tanks Pressure Sensor cables are disconnected</description> + <latching>true</latching> + <annunciating>true</annunciating> + <guidance> + <title>[Cryo Operator Action]</title> + <details>contact CRYO on-call and inform SCL on-call, Cryomodule pressure cable seems disconnected (value gets stuck), assign PT003 as measuring device on CV04 and CV-090 </details> + </guidance> + </pv> + <pv name="MBL-010Crm:Cryo-TT-014:P_Limit_HIHI"> + <description>Power coupler flange temperature too high</description> + <latching>true</latching> + <annunciating>true</annunciating> + <guidance> + <title>[Cryo Operator Action]</title> + <details>contact CRYO on-call and inform SCL on-call, power coupler flange temperature is too high, check heater output, if nominal then coupler flow needs to be adjusted (increased)</details> + </guidance> + </pv> + <pv name="MBL-010Crm:Cryo-TT-014:P_Limit_LO"> + <description>Power coupler flange temperature too low</description> + <latching>true</latching> + <annunciating>true</annunciating> + <guidance> + <title>[Cryo Operator Action]</title> + <details>contact CRYO on-call and inform SCL on-call, power coupler flange temperature is too low, check heater output, if nominal then coupler flow needs to be adjusted (reduced)</details> + </guidance> + </pv> + <pv name="MBL-010Crm:Cryo-TT-014:P_Limit_LOLO"> + <description>Power coupler flange temperature too low</description> + <latching>true</latching> + <annunciating>true</annunciating> + <guidance> + <title>[Cryo Operator Action]</title> + <details>contact CRYO on-call and inform SCL on-call, power coupler flange temperature is too low, check heater output, if nominal then coupler flow needs to be adjusted (reduced)</details> + </guidance> + </pv> + <pv name="MBL-010Crm:Cryo-TT-024:P_Limit_HIHI"> + <description>Power coupler flange temperature low</description> + <latching>true</latching> + <annunciating>true</annunciating> + <guidance> + <title>[Cryo Operator Action]</title> + <details>contact CRYO on-call and inform SCL on-call, power coupler flange temperature is too high, check heater output, if nominal then coupler flow needs to be adjusted (increased)</details> + </guidance> + </pv> + <pv name="MBL-010Crm:Cryo-TT-024:P_Limit_LO"> + <description>Power coupler flange temperature too low</description> + <latching>true</latching> + <annunciating>true</annunciating> + <guidance> + <title>[Cryo Operator Action]</title> + <details>contact CRYO on-call and inform SCL on-call, power coupler flange temperature is too low, check heater output, if nominal then coupler flow needs to be adjusted (reduced)</details> + </guidance> + </pv> + <pv name="MBL-010Crm:Cryo-TT-024:P_Limit_LOLO"> + <description>Power coupler flange temperature too high</description> + <latching>true</latching> + <annunciating>true</annunciating> + <guidance> + <title>[Cryo Operator Action]</title> + <details>contact CRYO on-call and inform SCL on-call, power coupler flange temperature is too low, check heater output, if nominal then coupler flow needs to be adjusted (reduced)</details> + </guidance> + </pv> + <pv name="MBL-010Crm:Cryo-TT-034:P_Limit_HIHI"> + <description>Power coupler flange temperature low</description> + <latching>true</latching> + <annunciating>true</annunciating> + <guidance> + <title>[Cryo Operator Action]</title> + <details>contact CRYO on-call and inform SCL on-call, power coupler flange temperature is too high, check heater output, if nominal then coupler flow needs to be adjusted (increased)</details> + </guidance> + </pv> + <pv name="MBL-010Crm:Cryo-TT-034:P_Limit_LO"> + <description>Power coupler flange temperature too low</description> + <latching>true</latching> + <annunciating>true</annunciating> + <guidance> + <title>[Cryo Operator Action]</title> + <details>contact CRYO on-call and inform SCL on-call, power coupler flange temperature is too low, check heater output, if nominal then coupler flow needs to be adjusted (reduced)</details> + </guidance> + </pv> + <pv name="MBL-010Crm:Cryo-TT-034:P_Limit_LOLO"> + <description>Power coupler flange temperature too high</description> + <latching>true</latching> + <annunciating>true</annunciating> + <guidance> + <title>[Cryo Operator Action]</title> + <details>contact CRYO on-call and inform SCL on-call, power coupler flange temperature is too low, check heater output, if nominal then coupler flow needs to be adjusted (reduced)</details> + </guidance> + </pv> + <pv name="MBL-010Crm:Cryo-TT-044:P_Limit_HIHI"> + <description>Power coupler flange temperature low</description> + <latching>true</latching> + <annunciating>true</annunciating> + <guidance> + <title>[Cryo Operator Action]</title> + <details>contact CRYO on-call and inform SCL on-call, power coupler flange temperature is too high, check heater output, if nominal then coupler flow needs to be adjusted (increased)</details> + </guidance> + </pv> + <pv name="MBL-010Crm:Cryo-TT-044:P_Limit_LO"> + <description>Power coupler flange temperature too low</description> + <latching>true</latching> + <annunciating>true</annunciating> + <guidance> + <title>[Cryo Operator Action]</title> + <details>contact CRYO on-call and inform SCL on-call, power coupler flange temperature is too low, check heater output, if nominal then coupler flow needs to be adjusted (reduced)</details> + </guidance> + </pv> + <pv name="MBL-010Crm:Cryo-TT-043:P_Limit_LOLO"> + <description>Power coupler flange temperature too high</description> + <latching>true</latching> + <annunciating>true</annunciating> + <guidance> + <title>[Cryo Operator Action]</title> + <details>contact CRYO on-call and inform SCL on-call, power coupler flange temperature is too low, check heater output, if nominal then coupler flow needs to be adjusted (reduced)</details> + </guidance> + </pv> + <pv name="MBL-010Crm:WtrC-FS-012:Flow_OK_WF"> + <description>! Alarm when signal drops from 1 to zero. No Water Flow Antenna 1</description> + <latching>true</latching> + <annunciating>true</annunciating> + <guidance> + <title>[Cryo Operator Action]</title> + <details>contact CRYO on-call and inform SCL on-call, assure Flange temperature TT-014 is correct. Risk of Water freeze if no flow and temperature too low</details> + </guidance> + </pv> + <pv name="MBL-010Crm:WtrC-FS-022:Flow_OK_WF"> + <description>! Alarm when signal drops from 1 to zero. No Water Flow Antenna 2</description> + <latching>true</latching> + <annunciating>true</annunciating> + <guidance> + <title>[Cryo Operator Action]</title> + <details>contact CRYO on-call and inform SCL on-call, assure Flange temperature TT-024 is correct. Risk of Water freeze if no flow and temperature too low</details> + </guidance> + </pv> + <pv name="MBL-010Crm:WtrC-FS-032:Flow_OK_WF"> + <description>! Alarm when signal drops from 1 to zero. No Water Flow Antenna 3</description> + <latching>true</latching> + <annunciating>true</annunciating> + <guidance> + <title>[Cryo Operator Action]</title> + <details>contact CRYO on-call and inform SCL on-call, assure Flange temperature TT-034 is correct. Risk of Water freeze if no flow and temperature too low</details> + </guidance> + </pv> + <pv name="MBL-010Crm:WtrC-FS-042:Flow_OK_WF"> + <description>! Alarm when signal drops from 1 to zero. No Water Flow Antenna 4</description> + <latching>true</latching> + <annunciating>true</annunciating> + <guidance> + <title>[Cryo Operator Action]</title> + <details>contact CRYO on-call and inform SCL on-call, assure Flange temperature TT-044 is correct. Risk of Water freeze if no flow and temperature too low</details> + </guidance> + </pv> + </component> + <component name="Cryomodules\MBL-020 Cryomodule"> + <pv name="MBL-020Crm:Cryo-LT-001:HIHI"> + <description>LT-001 helium level extremely high</description> + <latching>true</latching> + <annunciating>true</annunciating> + <guidance> + <title>[Cryo Operator Action]</title> + <details>contact CRYO on-call and inform SCL on-call, Cryomodule liquid level too high (check the other gauge LT-002). Close supply valve CV01, CV02</details> + </guidance> + </pv> + <pv name="MBL-020Crm:Cryo-LT-002:HIHI"> + <description>LT-002 helium level extremely high</description> + <latching>true</latching> + <annunciating>true</annunciating> + <guidance> + <title>[Cryo Operator Action]</title> + <details>contact CRYO on-call and inform SCL on-call, Cryomodule liquid level too high (check the other gauge LT-001). Close supply valve CV01, CV02</details> + </guidance> + </pv> + <pv name="MBL-020Crm:Cryo-LT-001:HI"> + <description>LT-001 helium level high</description> + <latching>true</latching> + <annunciating>true</annunciating> + <guidance> + <title>[Cryo Operator Action]</title> + <details>contact CRYO on-call and inform SCL on-call, Cryomodule liquid level high (check the other gauge LT-002). Check level regulation valve settings, if needed: adjust LMN_LO and if necessary: Close supply valve CV01, CV02</details> + </guidance> + </pv> + <pv name="MBL-020Crm:Cryo-LT-002:HI"> + <description>LT-002 helium level high</description> + <latching>true</latching> + <annunciating>true</annunciating> + <guidance> + <title>[Cryo Operator Action]</title> + <details>contact CRYO on-call and inform SCL on-call, Cryomodule liquid level high (check the other gauge LT-002). Check level regulation valve settings, if needed: adjust LMN_LO and if necessary: Close supply valve CV01, CV02</details> + </guidance> + </pv> + <pv name="MBL-020Crm:Cryo-LT-001:LO"> + <description>LT-001 helium level low</description> + <latching>true</latching> + <annunciating>true</annunciating> + <guidance> + <title>[Cryo Operator Action]</title> + <details>contact CRYO on-call and inform SCL on-call, Cryomodule liquid level low (check the other gauge LT-001). Check level regulation valve settings, if needed: adjust LMN_HI</details> + </guidance> + </pv> + <pv name="MBL-020Crm:Cryo-LT-002:LO"> + <description>LT-002 helium level low</description> + <latching>true</latching> + <annunciating>true</annunciating> + <guidance> + <title>[Cryo Operator Action]</title> + <details>contact CRYO on-call and inform SCL on-call, Cryomodule liquid level low (check the other gauge LT-002). Check level regulation valvesettings, if needed: adjust LMN_HI</details> + </guidance> + </pv> + <pv name="MBL-020Crm:Cryo-LT-001:LOLO"> + <description>LT-002 helium level extremely low</description> + <latching>true</latching> + <annunciating>true</annunciating> + <guidance> + <title>[Cryo Operator Action]</title> + <details>contact CRYO on-call and inform SCL on-call, Cryomodule liquid level too low (check the other gauge LT-001). Check level regulation valve settings, if needed: adjust LMN_HI</details> + </guidance> + </pv> + <pv name="MBL-020Crm:Cryo-LT-002:LOLO"> + <description>LT-002 helium level extremely low</description> + <latching>true</latching> + <annunciating>true</annunciating> + <guidance> + <title>[Cryo Operator Action]</title> + <details>contact CRYO on-call and inform SCL on-call, Cryomodule liquid level too low (check the other gauge LT-002). Check level regulation valvesettings, if needed: adjust LMN_HI</details> + </guidance> + </pv> + <pv name="MBL-020Crm:Cryo-PT-003:HIHI"> + <description>Cavity tanks pressure is too high (typical value is 31mbar in 2K mode and 1050mbar in 4K mode)</description> + <latching>true</latching> + <annunciating>true</annunciating> + <guidance> + <title>[Cryo Operator Action]</title> + <details>contact CRYO on-call and inform SCL on-call, Cryomodule bath pressure too high (check the other gauge PT002). Close supply valve CV01, CV02 if necessary</details> + </guidance> + </pv> + <pv name="MBL-020Crm:Cryo-PT-003:Cable_Error"> + <description>Cavity tanks Pressure Sensor cables are disconnected</description> + <latching>true</latching> + <annunciating>true</annunciating> + <guidance> + <title>[Cryo Operator Action]</title> + <details>contact CRYO on-call and inform SCL on-call, Cryomodule pressure cable seems disconnected (value gets stuck), assign PT002 as measuring device on CV04 and CV-090 </details> + </guidance> + </pv> + <pv name="MBL-020Crm:Cryo-PT-004:HIHI"> + <description>Cavity tanks pressure is too high (typical value is 31mbar in 2K mode and 1050mbar in 4K mode)</description> + <latching>true</latching> + <annunciating>true</annunciating> + <guidance> + <title>[Cryo Operator Action]</title> + <details>contact CRYO on-call and inform SCL on-call,, Cryomodule bath pressure too high (check the other gauge PT003). Close supply valve CV01, CV02 if necessary</details> + </guidance> + </pv> + <pv name="MBL-020Crm:Cryo-PT-004:Cable_Error"> + <description>Cavity tanks Pressure Sensor cables are disconnected</description> + <latching>true</latching> + <annunciating>true</annunciating> + <guidance> + <title>[Cryo Operator Action]</title> + <details>contact CRYO on-call and inform SCL on-call, Cryomodule pressure cable seems disconnected (value gets stuck), assign PT003 as measuring device on CV04 and CV-090 </details> + </guidance> + </pv> + <pv name="MBL-020Crm:Cryo-TT-014:P_Limit_HIHI"> + <description>Power coupler flange temperature too high</description> + <latching>true</latching> + <annunciating>true</annunciating> + <guidance> + <title>[Cryo Operator Action]</title> + <details>contact CRYO on-call and inform SCL on-call, power coupler flange temperature is too high, check heater output, if nominal then coupler flow needs to be adjusted (increased)</details> + </guidance> + </pv> + <pv name="MBL-020Crm:Cryo-TT-014:P_Limit_LO"> + <description>Power coupler flange temperature too low</description> + <latching>true</latching> + <annunciating>true</annunciating> + <guidance> + <title>[Cryo Operator Action]</title> + <details>contact CRYO on-call and inform SCL on-call, power coupler flange temperature is too low, check heater output, if nominal then coupler flow needs to be adjusted (reduced)</details> + </guidance> + </pv> + <pv name="MBL-020Crm:Cryo-TT-014:P_Limit_LOLO"> + <description>Power coupler flange temperature too low</description> + <latching>true</latching> + <annunciating>true</annunciating> + <guidance> + <title>[Cryo Operator Action]</title> + <details>contact CRYO on-call and inform SCL on-call, power coupler flange temperature is too low, check heater output, if nominal then coupler flow needs to be adjusted (reduced)</details> + </guidance> + </pv> + <pv name="MBL-020Crm:Cryo-TT-024:P_Limit_HIHI"> + <description>Power coupler flange temperature low</description> + <latching>true</latching> + <annunciating>true</annunciating> + <guidance> + <title>[Cryo Operator Action]</title> + <details>contact CRYO on-call and inform SCL on-call, power coupler flange temperature is too high, check heater output, if nominal then coupler flow needs to be adjusted (increased)</details> + </guidance> + </pv> + <pv name="MBL-020Crm:Cryo-TT-024:P_Limit_LO"> + <description>Power coupler flange temperature too low</description> + <latching>true</latching> + <annunciating>true</annunciating> + <guidance> + <title>[Cryo Operator Action]</title> + <details>contact CRYO on-call and inform SCL on-call, power coupler flange temperature is too low, check heater output, if nominal then coupler flow needs to be adjusted (reduced)</details> + </guidance> + </pv> + <pv name="MBL-020Crm:Cryo-TT-024:P_Limit_LOLO"> + <description>Power coupler flange temperature too high</description> + <latching>true</latching> + <annunciating>true</annunciating> + <guidance> + <title>[Cryo Operator Action]</title> + <details>contact CRYO on-call and inform SCL on-call, power coupler flange temperature is too low, check heater output, if nominal then coupler flow needs to be adjusted (reduced)</details> + </guidance> + </pv> + <pv name="MBL-020Crm:Cryo-TT-034:P_Limit_HIHI"> + <description>Power coupler flange temperature low</description> + <latching>true</latching> + <annunciating>true</annunciating> + <guidance> + <title>[Cryo Operator Action]</title> + <details>contact CRYO on-call and inform SCL on-call, power coupler flange temperature is too high, check heater output, if nominal then coupler flow needs to be adjusted (increased)</details> + </guidance> + </pv> + <pv name="MBL-020Crm:Cryo-TT-034:P_Limit_LO"> + <description>Power coupler flange temperature too low</description> + <latching>true</latching> + <annunciating>true</annunciating> + <guidance> + <title>[Cryo Operator Action]</title> + <details>contact CRYO on-call and inform SCL on-call, power coupler flange temperature is too low, check heater output, if nominal then coupler flow needs to be adjusted (reduced)</details> + </guidance> + </pv> + <pv name="MBL-020Crm:Cryo-TT-034:P_Limit_LOLO"> + <description>Power coupler flange temperature too high</description> + <latching>true</latching> + <annunciating>true</annunciating> + <guidance> + <title>[Cryo Operator Action]</title> + <details>contact CRYO on-call and inform SCL on-call, power coupler flange temperature is too low, check heater output, if nominal then coupler flow needs to be adjusted (reduced)</details> + </guidance> + </pv> + <pv name="MBL-020Crm:Cryo-TT-044:P_Limit_HIHI"> + <description>Power coupler flange temperature low</description> + <latching>true</latching> + <annunciating>true</annunciating> + <guidance> + <title>[Cryo Operator Action]</title> + <details>contact CRYO on-call and inform SCL on-call, power coupler flange temperature is too high, check heater output, if nominal then coupler flow needs to be adjusted (increased)</details> + </guidance> + </pv> + <pv name="MBL-020Crm:Cryo-TT-044:P_Limit_LO"> + <description>Power coupler flange temperature too low</description> + <latching>true</latching> + <annunciating>true</annunciating> + <guidance> + <title>[Cryo Operator Action]</title> + <details>contact CRYO on-call and inform SCL on-call, power coupler flange temperature is too low, check heater output, if nominal then coupler flow needs to be adjusted (reduced)</details> + </guidance> + </pv> + <pv name="MBL-020Crm:Cryo-TT-043:P_Limit_LOLO"> + <description>Power coupler flange temperature too high</description> + <latching>true</latching> + <annunciating>true</annunciating> + <guidance> + <title>[Cryo Operator Action]</title> + <details>contact CRYO on-call and inform SCL on-call, power coupler flange temperature is too low, check heater output, if nominal then coupler flow needs to be adjusted (reduced)</details> + </guidance> + </pv> + <pv name="MBL-020Crm:WtrC-FS-012:Flow_OK_WF"> + <description>! Alarm when signal drops from 1 to zero. No Water Flow Antenna 1</description> + <latching>true</latching> + <annunciating>true</annunciating> + <guidance> + <title>[Cryo Operator Action]</title> + <details>contact CRYO on-call and inform SCL on-call, assure Flange temperature TT-014 is correct. Risk of Water freeze if no flow and temperature too low</details> + </guidance> + </pv> + <pv name="MBL-020Crm:WtrC-FS-022:Flow_OK_WF"> + <description>! Alarm when signal drops from 1 to zero. No Water Flow Antenna 2</description> + <latching>true</latching> + <annunciating>true</annunciating> + <guidance> + <title>[Cryo Operator Action]</title> + <details>contact CRYO on-call and inform SCL on-call, assure Flange temperature TT-024 is correct. Risk of Water freeze if no flow and temperature too low</details> + </guidance> + </pv> + <pv name="MBL-020Crm:WtrC-FS-032:Flow_OK_WF"> + <description>! Alarm when signal drops from 1 to zero. No Water Flow Antenna 3</description> + <latching>true</latching> + <annunciating>true</annunciating> + <guidance> + <title>[Cryo Operator Action]</title> + <details>contact CRYO on-call and inform SCL on-call, assure Flange temperature TT-034 is correct. Risk of Water freeze if no flow and temperature too low</details> + </guidance> + </pv> + <pv name="MBL-020Crm:WtrC-FS-042:Flow_OK_WF"> + <description>! Alarm when signal drops from 1 to zero. No Water Flow Antenna 4</description> + <latching>true</latching> + <annunciating>true</annunciating> + <guidance> + <title>[Cryo Operator Action]</title> + <details>contact CRYO on-call and inform SCL on-call, assure Flange temperature TT-044 is correct. Risk of Water freeze if no flow and temperature too low</details> + </guidance> + </pv> + </component> + <component name="Cryomodules\MBL-030 Cryomodule"> + <pv name="MBL-030Crm:Cryo-LT-001:HIHI"> + <description>LT-001 helium level extremely high</description> + <latching>true</latching> + <annunciating>true</annunciating> + <guidance> + <title>[Cryo Operator Action]</title> + <details>contact CRYO on-call and inform SCL on-call, Cryomodule liquid level too high (check the other gauge LT-002). Close supply valve CV01, CV02</details> + </guidance> + </pv> + <pv name="MBL-030Crm:Cryo-LT-002:HIHI"> + <description>LT-002 helium level extremely high</description> + <latching>true</latching> + <annunciating>true</annunciating> + <guidance> + <title>[Cryo Operator Action]</title> + <details>contact CRYO on-call and inform SCL on-call, Cryomodule liquid level too high (check the other gauge LT-001). Close supply valve CV01, CV02</details> + </guidance> + </pv> + <pv name="MBL-030Crm:Cryo-LT-001:HI"> + <description>LT-001 helium level high</description> + <latching>true</latching> + <annunciating>true</annunciating> + <guidance> + <title>[Cryo Operator Action]</title> + <details>contact CRYO on-call and inform SCL on-call, Cryomodule liquid level high (check the other gauge LT-002). Check level regulation valve settings, if needed: adjust LMN_LO and if necessary: Close supply valve CV01, CV02</details> + </guidance> + </pv> + <pv name="MBL-030Crm:Cryo-LT-002:HI"> + <description>LT-002 helium level high</description> + <latching>true</latching> + <annunciating>true</annunciating> + <guidance> + <title>[Cryo Operator Action]</title> + <details>contact CRYO on-call and inform SCL on-call, Cryomodule liquid level high (check the other gauge LT-002). Check level regulation valve settings, if needed: adjust LMN_LO and if necessary: Close supply valve CV01, CV02</details> + </guidance> + </pv> + <pv name="MBL-030Crm:Cryo-LT-001:LO"> + <description>LT-001 helium level low</description> + <latching>true</latching> + <annunciating>true</annunciating> + <guidance> + <title>[Cryo Operator Action]</title> + <details>contact CRYO on-call and inform SCL on-call, Cryomodule liquid level low (check the other gauge LT-001). Check level regulation valve settings, if needed: adjust LMN_HI</details> + </guidance> + </pv> + <pv name="MBL-030Crm:Cryo-LT-002:LO"> + <description>LT-002 helium level low</description> + <latching>true</latching> + <annunciating>true</annunciating> + <guidance> + <title>[Cryo Operator Action]</title> + <details>contact CRYO on-call and inform SCL on-call, Cryomodule liquid level low (check the other gauge LT-002). Check level regulation valvesettings, if needed: adjust LMN_HI</details> + </guidance> + </pv> + <pv name="MBL-030Crm:Cryo-LT-001:LOLO"> + <description>LT-002 helium level extremely low</description> + <latching>true</latching> + <annunciating>true</annunciating> + <guidance> + <title>[Cryo Operator Action]</title> + <details>contact CRYO on-call and inform SCL on-call, Cryomodule liquid level too low (check the other gauge LT-001). Check level regulation valve settings, if needed: adjust LMN_HI</details> + </guidance> + </pv> + <pv name="MBL-030Crm:Cryo-LT-002:LOLO"> + <description>LT-002 helium level extremely low</description> + <latching>true</latching> + <annunciating>true</annunciating> + <guidance> + <title>[Cryo Operator Action]</title> + <details>contact CRYO on-call and inform SCL on-call, Cryomodule liquid level too low (check the other gauge LT-002). Check level regulation valvesettings, if needed: adjust LMN_HI</details> + </guidance> + </pv> + <pv name="MBL-030Crm:Cryo-PT-003:HIHI"> + <description>Cavity tanks pressure is too high (typical value is 31mbar in 2K mode and 1050mbar in 4K mode)</description> + <latching>true</latching> + <annunciating>true</annunciating> + <guidance> + <title>[Cryo Operator Action]</title> + <details>contact CRYO on-call and inform SCL on-call, Cryomodule bath pressure too high (check the other gauge PT002). Close supply valve CV01, CV02 if necessary</details> + </guidance> + </pv> + <pv name="MBL-030Crm:Cryo-PT-003:Cable_Error"> + <description>Cavity tanks Pressure Sensor cables are disconnected</description> + <latching>true</latching> + <annunciating>true</annunciating> + <guidance> + <title>[Cryo Operator Action]</title> + <details>contact CRYO on-call and inform SCL on-call, Cryomodule pressure cable seems disconnected (value gets stuck), assign PT002 as measuring device on CV04 and CV-090 </details> + </guidance> + </pv> + <pv name="MBL-030Crm:Cryo-PT-004:HIHI"> + <description>Cavity tanks pressure is too high (typical value is 31mbar in 2K mode and 1050mbar in 4K mode)</description> + <latching>true</latching> + <annunciating>true</annunciating> + <guidance> + <title>[Cryo Operator Action]</title> + <details>contact CRYO on-call and inform SCL on-call,, Cryomodule bath pressure too high (check the other gauge PT003). Close supply valve CV01, CV02 if necessary</details> + </guidance> + </pv> + <pv name="MBL-030Crm:Cryo-PT-004:Cable_Error"> + <description>Cavity tanks Pressure Sensor cables are disconnected</description> + <latching>true</latching> + <annunciating>true</annunciating> + <guidance> + <title>[Cryo Operator Action]</title> + <details>contact CRYO on-call and inform SCL on-call, Cryomodule pressure cable seems disconnected (value gets stuck), assign PT003 as measuring device on CV04 and CV-090 </details> + </guidance> + </pv> + <pv name="MBL-030Crm:Cryo-TT-014:P_Limit_HIHI"> + <description>Power coupler flange temperature too high</description> + <latching>true</latching> + <annunciating>true</annunciating> + <guidance> + <title>[Cryo Operator Action]</title> + <details>contact CRYO on-call and inform SCL on-call, power coupler flange temperature is too high, check heater output, if nominal then coupler flow needs to be adjusted (increased)</details> + </guidance> + </pv> + <pv name="MBL-030Crm:Cryo-TT-014:P_Limit_LO"> + <description>Power coupler flange temperature too low</description> + <latching>true</latching> + <annunciating>true</annunciating> + <guidance> + <title>[Cryo Operator Action]</title> + <details>contact CRYO on-call and inform SCL on-call, power coupler flange temperature is too low, check heater output, if nominal then coupler flow needs to be adjusted (reduced)</details> + </guidance> + </pv> + <pv name="MBL-030Crm:Cryo-TT-014:P_Limit_LOLO"> + <description>Power coupler flange temperature too low</description> + <latching>true</latching> + <annunciating>true</annunciating> + <guidance> + <title>[Cryo Operator Action]</title> + <details>contact CRYO on-call and inform SCL on-call, power coupler flange temperature is too low, check heater output, if nominal then coupler flow needs to be adjusted (reduced)</details> + </guidance> + </pv> + <pv name="MBL-030Crm:Cryo-TT-024:P_Limit_HIHI"> + <description>Power coupler flange temperature low</description> + <latching>true</latching> + <annunciating>true</annunciating> + <guidance> + <title>[Cryo Operator Action]</title> + <details>contact CRYO on-call and inform SCL on-call, power coupler flange temperature is too high, check heater output, if nominal then coupler flow needs to be adjusted (increased)</details> + </guidance> + </pv> + <pv name="MBL-030Crm:Cryo-TT-024:P_Limit_LO"> + <description>Power coupler flange temperature too low</description> + <latching>true</latching> + <annunciating>true</annunciating> + <guidance> + <title>[Cryo Operator Action]</title> + <details>contact CRYO on-call and inform SCL on-call, power coupler flange temperature is too low, check heater output, if nominal then coupler flow needs to be adjusted (reduced)</details> + </guidance> + </pv> + <pv name="MBL-030Crm:Cryo-TT-024:P_Limit_LOLO"> + <description>Power coupler flange temperature too high</description> + <latching>true</latching> + <annunciating>true</annunciating> + <guidance> + <title>[Cryo Operator Action]</title> + <details>contact CRYO on-call and inform SCL on-call, power coupler flange temperature is too low, check heater output, if nominal then coupler flow needs to be adjusted (reduced)</details> + </guidance> + </pv> + <pv name="MBL-030Crm:Cryo-TT-034:P_Limit_HIHI"> + <description>Power coupler flange temperature low</description> + <latching>true</latching> + <annunciating>true</annunciating> + <guidance> + <title>[Cryo Operator Action]</title> + <details>contact CRYO on-call and inform SCL on-call, power coupler flange temperature is too high, check heater output, if nominal then coupler flow needs to be adjusted (increased)</details> + </guidance> + </pv> + <pv name="MBL-030Crm:Cryo-TT-034:P_Limit_LO"> + <description>Power coupler flange temperature too low</description> + <latching>true</latching> + <annunciating>true</annunciating> + <guidance> + <title>[Cryo Operator Action]</title> + <details>contact CRYO on-call and inform SCL on-call, power coupler flange temperature is too low, check heater output, if nominal then coupler flow needs to be adjusted (reduced)</details> + </guidance> + </pv> + <pv name="MBL-030Crm:Cryo-TT-034:P_Limit_LOLO"> + <description>Power coupler flange temperature too high</description> + <latching>true</latching> + <annunciating>true</annunciating> + <guidance> + <title>[Cryo Operator Action]</title> + <details>contact CRYO on-call and inform SCL on-call, power coupler flange temperature is too low, check heater output, if nominal then coupler flow needs to be adjusted (reduced)</details> + </guidance> + </pv> + <pv name="MBL-030Crm:Cryo-TT-044:P_Limit_HIHI"> + <description>Power coupler flange temperature low</description> + <latching>true</latching> + <annunciating>true</annunciating> + <guidance> + <title>[Cryo Operator Action]</title> + <details>contact CRYO on-call and inform SCL on-call, power coupler flange temperature is too high, check heater output, if nominal then coupler flow needs to be adjusted (increased)</details> + </guidance> + </pv> + <pv name="MBL-030Crm:Cryo-TT-044:P_Limit_LO"> + <description>Power coupler flange temperature too low</description> + <latching>true</latching> + <annunciating>true</annunciating> + <guidance> + <title>[Cryo Operator Action]</title> + <details>contact CRYO on-call and inform SCL on-call, power coupler flange temperature is too low, check heater output, if nominal then coupler flow needs to be adjusted (reduced)</details> + </guidance> + </pv> + <pv name="MBL-030Crm:Cryo-TT-043:P_Limit_LOLO"> + <description>Power coupler flange temperature too high</description> + <latching>true</latching> + <annunciating>true</annunciating> + <guidance> + <title>[Cryo Operator Action]</title> + <details>contact CRYO on-call and inform SCL on-call, power coupler flange temperature is too low, check heater output, if nominal then coupler flow needs to be adjusted (reduced)</details> + </guidance> + </pv> + <pv name="MBL-030Crm:WtrC-FS-012:Flow_OK_WF"> + <description>! Alarm when signal drops from 1 to zero. No Water Flow Antenna 1</description> + <latching>true</latching> + <annunciating>true</annunciating> + <guidance> + <title>[Cryo Operator Action]</title> + <details>contact CRYO on-call and inform SCL on-call, assure Flange temperature TT-014 is correct. Risk of Water freeze if no flow and temperature too low</details> + </guidance> + </pv> + <pv name="MBL-030Crm:WtrC-FS-022:Flow_OK_WF"> + <description>! Alarm when signal drops from 1 to zero. No Water Flow Antenna 2</description> + <latching>true</latching> + <annunciating>true</annunciating> + <guidance> + <title>[Cryo Operator Action]</title> + <details>contact CRYO on-call and inform SCL on-call, assure Flange temperature TT-024 is correct. Risk of Water freeze if no flow and temperature too low</details> + </guidance> + </pv> + <pv name="MBL-030Crm:WtrC-FS-032:Flow_OK_WF"> + <description>! Alarm when signal drops from 1 to zero. No Water Flow Antenna 3</description> + <latching>true</latching> + <annunciating>true</annunciating> + <guidance> + <title>[Cryo Operator Action]</title> + <details>contact CRYO on-call and inform SCL on-call, assure Flange temperature TT-034 is correct. Risk of Water freeze if no flow and temperature too low</details> + </guidance> + </pv> + <pv name="MBL-030Crm:WtrC-FS-042:Flow_OK_WF"> + <description>! Alarm when signal drops from 1 to zero. No Water Flow Antenna 4</description> + <latching>true</latching> + <annunciating>true</annunciating> + <guidance> + <title>[Cryo Operator Action]</title> + <details>contact CRYO on-call and inform SCL on-call, assure Flange temperature TT-044 is correct. Risk of Water freeze if no flow and temperature too low</details> + </guidance> + </pv> + </component> + <component name="Cryomodules\MBL-040 Cryomodule"> + <pv name="MBL-040Crm:Cryo-LT-001:HIHI"> + <description>LT-001 helium level extremely high</description> + <latching>true</latching> + <annunciating>true</annunciating> + <guidance> + <title>[Cryo Operator Action]</title> + <details>contact CRYO on-call and inform SCL on-call, Cryomodule liquid level too high (check the other gauge LT-002). Close supply valve CV01, CV02</details> + </guidance> + </pv> + <pv name="MBL-040Crm:Cryo-LT-002:HIHI"> + <description>LT-002 helium level extremely high</description> + <latching>true</latching> + <annunciating>true</annunciating> + <guidance> + <title>[Cryo Operator Action]</title> + <details>contact CRYO on-call and inform SCL on-call, Cryomodule liquid level too high (check the other gauge LT-001). Close supply valve CV01, CV02</details> + </guidance> + </pv> + <pv name="MBL-040Crm:Cryo-LT-001:HI"> + <description>LT-001 helium level high</description> + <latching>true</latching> + <annunciating>true</annunciating> + <guidance> + <title>[Cryo Operator Action]</title> + <details>contact CRYO on-call and inform SCL on-call, Cryomodule liquid level high (check the other gauge LT-002). Check level regulation valve settings, if needed: adjust LMN_LO and if necessary: Close supply valve CV01, CV02</details> + </guidance> + </pv> + <pv name="MBL-040Crm:Cryo-LT-002:HI"> + <description>LT-002 helium level high</description> + <latching>true</latching> + <annunciating>true</annunciating> + <guidance> + <title>[Cryo Operator Action]</title> + <details>contact CRYO on-call and inform SCL on-call, Cryomodule liquid level high (check the other gauge LT-002). Check level regulation valve settings, if needed: adjust LMN_LO and if necessary: Close supply valve CV01, CV02</details> + </guidance> + </pv> + <pv name="MBL-040Crm:Cryo-LT-001:LO"> + <description>LT-001 helium level low</description> + <latching>true</latching> + <annunciating>true</annunciating> + <guidance> + <title>[Cryo Operator Action]</title> + <details>contact CRYO on-call and inform SCL on-call, Cryomodule liquid level low (check the other gauge LT-001). Check level regulation valve settings, if needed: adjust LMN_HI</details> + </guidance> + </pv> + <pv name="MBL-040Crm:Cryo-LT-002:LO"> + <description>LT-002 helium level low</description> + <latching>true</latching> + <annunciating>true</annunciating> + <guidance> + <title>[Cryo Operator Action]</title> + <details>contact CRYO on-call and inform SCL on-call, Cryomodule liquid level low (check the other gauge LT-002). Check level regulation valvesettings, if needed: adjust LMN_HI</details> + </guidance> + </pv> + <pv name="MBL-040Crm:Cryo-LT-001:LOLO"> + <description>LT-002 helium level extremely low</description> + <latching>true</latching> + <annunciating>true</annunciating> + <guidance> + <title>[Cryo Operator Action]</title> + <details>contact CRYO on-call and inform SCL on-call, Cryomodule liquid level too low (check the other gauge LT-001). Check level regulation valve settings, if needed: adjust LMN_HI</details> + </guidance> + </pv> + <pv name="MBL-040Crm:Cryo-LT-002:LOLO"> + <description>LT-002 helium level extremely low</description> + <latching>true</latching> + <annunciating>true</annunciating> + <guidance> + <title>[Cryo Operator Action]</title> + <details>contact CRYO on-call and inform SCL on-call, Cryomodule liquid level too low (check the other gauge LT-002). Check level regulation valvesettings, if needed: adjust LMN_HI</details> + </guidance> + </pv> + <pv name="MBL-040Crm:Cryo-PT-003:HIHI"> + <description>Cavity tanks pressure is too high (typical value is 31mbar in 2K mode and 1050mbar in 4K mode)</description> + <latching>true</latching> + <annunciating>true</annunciating> + <guidance> + <title>[Cryo Operator Action]</title> + <details>contact CRYO on-call and inform SCL on-call, Cryomodule bath pressure too high (check the other gauge PT002). Close supply valve CV01, CV02 if necessary</details> + </guidance> + </pv> + <pv name="MBL-040Crm:Cryo-PT-003:Cable_Error"> + <description>Cavity tanks Pressure Sensor cables are disconnected</description> + <latching>true</latching> + <annunciating>true</annunciating> + <guidance> + <title>[Cryo Operator Action]</title> + <details>contact CRYO on-call and inform SCL on-call, Cryomodule pressure cable seems disconnected (value gets stuck), assign PT002 as measuring device on CV04 and CV-090 </details> + </guidance> + </pv> + <pv name="MBL-040Crm:Cryo-PT-004:HIHI"> + <description>Cavity tanks pressure is too high (typical value is 31mbar in 2K mode and 1050mbar in 4K mode)</description> + <latching>true</latching> + <annunciating>true</annunciating> + <guidance> + <title>[Cryo Operator Action]</title> + <details>contact CRYO on-call and inform SCL on-call,, Cryomodule bath pressure too high (check the other gauge PT003). Close supply valve CV01, CV02 if necessary</details> + </guidance> + </pv> + <pv name="MBL-040Crm:Cryo-PT-004:Cable_Error"> + <description>Cavity tanks Pressure Sensor cables are disconnected</description> + <latching>true</latching> + <annunciating>true</annunciating> + <guidance> + <title>[Cryo Operator Action]</title> + <details>contact CRYO on-call and inform SCL on-call, Cryomodule pressure cable seems disconnected (value gets stuck), assign PT003 as measuring device on CV04 and CV-090 </details> + </guidance> + </pv> + <pv name="MBL-040Crm:Cryo-TT-014:P_Limit_HIHI"> + <description>Power coupler flange temperature too high</description> + <latching>true</latching> + <annunciating>true</annunciating> + <guidance> + <title>[Cryo Operator Action]</title> + <details>contact CRYO on-call and inform SCL on-call, power coupler flange temperature is too high, check heater output, if nominal then coupler flow needs to be adjusted (increased)</details> + </guidance> + </pv> + <pv name="MBL-040Crm:Cryo-TT-014:P_Limit_LO"> + <description>Power coupler flange temperature too low</description> + <latching>true</latching> + <annunciating>true</annunciating> + <guidance> + <title>[Cryo Operator Action]</title> + <details>contact CRYO on-call and inform SCL on-call, power coupler flange temperature is too low, check heater output, if nominal then coupler flow needs to be adjusted (reduced)</details> + </guidance> + </pv> + <pv name="MBL-040Crm:Cryo-TT-014:P_Limit_LOLO"> + <description>Power coupler flange temperature too low</description> + <latching>true</latching> + <annunciating>true</annunciating> + <guidance> + <title>[Cryo Operator Action]</title> + <details>contact CRYO on-call and inform SCL on-call, power coupler flange temperature is too low, check heater output, if nominal then coupler flow needs to be adjusted (reduced)</details> + </guidance> + </pv> + <pv name="MBL-040Crm:Cryo-TT-024:P_Limit_HIHI"> + <description>Power coupler flange temperature low</description> + <latching>true</latching> + <annunciating>true</annunciating> + <guidance> + <title>[Cryo Operator Action]</title> + <details>contact CRYO on-call and inform SCL on-call, power coupler flange temperature is too high, check heater output, if nominal then coupler flow needs to be adjusted (increased)</details> + </guidance> + </pv> + <pv name="MBL-040Crm:Cryo-TT-024:P_Limit_LO"> + <description>Power coupler flange temperature too low</description> + <latching>true</latching> + <annunciating>true</annunciating> + <guidance> + <title>[Cryo Operator Action]</title> + <details>contact CRYO on-call and inform SCL on-call, power coupler flange temperature is too low, check heater output, if nominal then coupler flow needs to be adjusted (reduced)</details> + </guidance> + </pv> + <pv name="MBL-040Crm:Cryo-TT-024:P_Limit_LOLO"> + <description>Power coupler flange temperature too high</description> + <latching>true</latching> + <annunciating>true</annunciating> + <guidance> + <title>[Cryo Operator Action]</title> + <details>contact CRYO on-call and inform SCL on-call, power coupler flange temperature is too low, check heater output, if nominal then coupler flow needs to be adjusted (reduced)</details> + </guidance> + </pv> + <pv name="MBL-040Crm:Cryo-TT-034:P_Limit_HIHI"> + <description>Power coupler flange temperature low</description> + <latching>true</latching> + <annunciating>true</annunciating> + <guidance> + <title>[Cryo Operator Action]</title> + <details>contact CRYO on-call and inform SCL on-call, power coupler flange temperature is too high, check heater output, if nominal then coupler flow needs to be adjusted (increased)</details> + </guidance> + </pv> + <pv name="MBL-040Crm:Cryo-TT-034:P_Limit_LO"> + <description>Power coupler flange temperature too low</description> + <latching>true</latching> + <annunciating>true</annunciating> + <guidance> + <title>[Cryo Operator Action]</title> + <details>contact CRYO on-call and inform SCL on-call, power coupler flange temperature is too low, check heater output, if nominal then coupler flow needs to be adjusted (reduced)</details> + </guidance> + </pv> + <pv name="MBL-040Crm:Cryo-TT-034:P_Limit_LOLO"> + <description>Power coupler flange temperature too high</description> + <latching>true</latching> + <annunciating>true</annunciating> + <guidance> + <title>[Cryo Operator Action]</title> + <details>contact CRYO on-call and inform SCL on-call, power coupler flange temperature is too low, check heater output, if nominal then coupler flow needs to be adjusted (reduced)</details> + </guidance> + </pv> + <pv name="MBL-040Crm:Cryo-TT-044:P_Limit_HIHI"> + <description>Power coupler flange temperature low</description> + <latching>true</latching> + <annunciating>true</annunciating> + <guidance> + <title>[Cryo Operator Action]</title> + <details>contact CRYO on-call and inform SCL on-call, power coupler flange temperature is too high, check heater output, if nominal then coupler flow needs to be adjusted (increased)</details> + </guidance> + </pv> + <pv name="MBL-040Crm:Cryo-TT-044:P_Limit_LO"> + <description>Power coupler flange temperature too low</description> + <latching>true</latching> + <annunciating>true</annunciating> + <guidance> + <title>[Cryo Operator Action]</title> + <details>contact CRYO on-call and inform SCL on-call, power coupler flange temperature is too low, check heater output, if nominal then coupler flow needs to be adjusted (reduced)</details> + </guidance> + </pv> + <pv name="MBL-040Crm:Cryo-TT-043:P_Limit_LOLO"> + <description>Power coupler flange temperature too high</description> + <latching>true</latching> + <annunciating>true</annunciating> + <guidance> + <title>[Cryo Operator Action]</title> + <details>contact CRYO on-call and inform SCL on-call, power coupler flange temperature is too low, check heater output, if nominal then coupler flow needs to be adjusted (reduced)</details> + </guidance> + </pv> + <pv name="MBL-040Crm:WtrC-FS-012:Flow_OK_WF"> + <description>! Alarm when signal drops from 1 to zero. No Water Flow Antenna 1</description> + <latching>true</latching> + <annunciating>true</annunciating> + <guidance> + <title>[Cryo Operator Action]</title> + <details>contact CRYO on-call and inform SCL on-call, assure Flange temperature TT-014 is correct. Risk of Water freeze if no flow and temperature too low</details> + </guidance> + </pv> + <pv name="MBL-040Crm:WtrC-FS-022:Flow_OK_WF"> + <description>! Alarm when signal drops from 1 to zero. No Water Flow Antenna 2</description> + <latching>true</latching> + <annunciating>true</annunciating> + <guidance> + <title>[Cryo Operator Action]</title> + <details>contact CRYO on-call and inform SCL on-call, assure Flange temperature TT-024 is correct. Risk of Water freeze if no flow and temperature too low</details> + </guidance> + </pv> + <pv name="MBL-040Crm:WtrC-FS-032:Flow_OK_WF"> + <description>! Alarm when signal drops from 1 to zero. No Water Flow Antenna 3</description> + <latching>true</latching> + <annunciating>true</annunciating> + <guidance> + <title>[Cryo Operator Action]</title> + <details>contact CRYO on-call and inform SCL on-call, assure Flange temperature TT-034 is correct. Risk of Water freeze if no flow and temperature too low</details> + </guidance> + </pv> + <pv name="MBL-040Crm:WtrC-FS-042:Flow_OK_WF"> + <description>! Alarm when signal drops from 1 to zero. No Water Flow Antenna 4</description> + <latching>true</latching> + <annunciating>true</annunciating> + <guidance> + <title>[Cryo Operator Action]</title> + <details>contact CRYO on-call and inform SCL on-call, assure Flange temperature TT-044 is correct. Risk of Water freeze if no flow and temperature too low</details> + </guidance> + </pv> + </component> + <component name="Cryomodules\MBL-050 Cryomodule"> + <pv name="MBL-050Crm:Cryo-LT-001:HIHI"> + <description>LT-001 helium level extremely high</description> + <latching>true</latching> + <annunciating>true</annunciating> + <guidance> + <title>[Cryo Operator Action]</title> + <details>contact CRYO on-call and inform SCL on-call, Cryomodule liquid level too high (check the other gauge LT-002). Close supply valve CV01, CV02</details> + </guidance> + </pv> + <pv name="MBL-050Crm:Cryo-LT-002:HIHI"> + <description>LT-002 helium level extremely high</description> + <latching>true</latching> + <annunciating>true</annunciating> + <guidance> + <title>[Cryo Operator Action]</title> + <details>contact CRYO on-call and inform SCL on-call, Cryomodule liquid level too high (check the other gauge LT-001). Close supply valve CV01, CV02</details> + </guidance> + </pv> + <pv name="MBL-050Crm:Cryo-LT-001:HI"> + <description>LT-001 helium level high</description> + <latching>true</latching> + <annunciating>true</annunciating> + <guidance> + <title>[Cryo Operator Action]</title> + <details>contact CRYO on-call and inform SCL on-call, Cryomodule liquid level high (check the other gauge LT-002). Check level regulation valve settings, if needed: adjust LMN_LO and if necessary: Close supply valve CV01, CV02</details> + </guidance> + </pv> + <pv name="MBL-050Crm:Cryo-LT-002:HI"> + <description>LT-002 helium level high</description> + <latching>true</latching> + <annunciating>true</annunciating> + <guidance> + <title>[Cryo Operator Action]</title> + <details>contact CRYO on-call and inform SCL on-call, Cryomodule liquid level high (check the other gauge LT-002). Check level regulation valve settings, if needed: adjust LMN_LO and if necessary: Close supply valve CV01, CV02</details> + </guidance> + </pv> + <pv name="MBL-050Crm:Cryo-LT-001:LO"> + <description>LT-001 helium level low</description> + <latching>true</latching> + <annunciating>true</annunciating> + <guidance> + <title>[Cryo Operator Action]</title> + <details>contact CRYO on-call and inform SCL on-call, Cryomodule liquid level low (check the other gauge LT-001). Check level regulation valve settings, if needed: adjust LMN_HI</details> + </guidance> + </pv> + <pv name="MBL-050Crm:Cryo-LT-002:LO"> + <description>LT-002 helium level low</description> + <latching>true</latching> + <annunciating>true</annunciating> + <guidance> + <title>[Cryo Operator Action]</title> + <details>contact CRYO on-call and inform SCL on-call, Cryomodule liquid level low (check the other gauge LT-002). Check level regulation valvesettings, if needed: adjust LMN_HI</details> + </guidance> + </pv> + <pv name="MBL-050Crm:Cryo-LT-001:LOLO"> + <description>LT-002 helium level extremely low</description> + <latching>true</latching> + <annunciating>true</annunciating> + <guidance> + <title>[Cryo Operator Action]</title> + <details>contact CRYO on-call and inform SCL on-call, Cryomodule liquid level too low (check the other gauge LT-001). Check level regulation valve settings, if needed: adjust LMN_HI</details> + </guidance> + </pv> + <pv name="MBL-050Crm:Cryo-LT-002:LOLO"> + <description>LT-002 helium level extremely low</description> + <latching>true</latching> + <annunciating>true</annunciating> + <guidance> + <title>[Cryo Operator Action]</title> + <details>contact CRYO on-call and inform SCL on-call, Cryomodule liquid level too low (check the other gauge LT-002). Check level regulation valvesettings, if needed: adjust LMN_HI</details> + </guidance> + </pv> + <pv name="MBL-050Crm:Cryo-PT-003:HIHI"> + <description>Cavity tanks pressure is too high (typical value is 31mbar in 2K mode and 1050mbar in 4K mode)</description> + <latching>true</latching> + <annunciating>true</annunciating> + <guidance> + <title>[Cryo Operator Action]</title> + <details>contact CRYO on-call and inform SCL on-call, Cryomodule bath pressure too high (check the other gauge PT002). Close supply valve CV01, CV02 if necessary</details> + </guidance> + </pv> + <pv name="MBL-050Crm:Cryo-PT-003:Cable_Error"> + <description>Cavity tanks Pressure Sensor cables are disconnected</description> + <latching>true</latching> + <annunciating>true</annunciating> + <guidance> + <title>[Cryo Operator Action]</title> + <details>contact CRYO on-call and inform SCL on-call, Cryomodule pressure cable seems disconnected (value gets stuck), assign PT002 as measuring device on CV04 and CV-090 </details> + </guidance> + </pv> + <pv name="MBL-050Crm:Cryo-PT-004:HIHI"> + <description>Cavity tanks pressure is too high (typical value is 31mbar in 2K mode and 1050mbar in 4K mode)</description> + <latching>true</latching> + <annunciating>true</annunciating> + <guidance> + <title>[Cryo Operator Action]</title> + <details>contact CRYO on-call and inform SCL on-call,, Cryomodule bath pressure too high (check the other gauge PT003). Close supply valve CV01, CV02 if necessary</details> + </guidance> + </pv> + <pv name="MBL-050Crm:Cryo-PT-004:Cable_Error"> + <description>Cavity tanks Pressure Sensor cables are disconnected</description> + <latching>true</latching> + <annunciating>true</annunciating> + <guidance> + <title>[Cryo Operator Action]</title> + <details>contact CRYO on-call and inform SCL on-call, Cryomodule pressure cable seems disconnected (value gets stuck), assign PT003 as measuring device on CV04 and CV-090 </details> + </guidance> + </pv> + <pv name="MBL-050Crm:Cryo-TT-014:P_Limit_HIHI"> + <description>Power coupler flange temperature too high</description> + <latching>true</latching> + <annunciating>true</annunciating> + <guidance> + <title>[Cryo Operator Action]</title> + <details>contact CRYO on-call and inform SCL on-call, power coupler flange temperature is too high, check heater output, if nominal then coupler flow needs to be adjusted (increased)</details> + </guidance> + </pv> + <pv name="MBL-050Crm:Cryo-TT-014:P_Limit_LO"> + <description>Power coupler flange temperature too low</description> + <latching>true</latching> + <annunciating>true</annunciating> + <guidance> + <title>[Cryo Operator Action]</title> + <details>contact CRYO on-call and inform SCL on-call, power coupler flange temperature is too low, check heater output, if nominal then coupler flow needs to be adjusted (reduced)</details> + </guidance> + </pv> + <pv name="MBL-050Crm:Cryo-TT-014:P_Limit_LOLO"> + <description>Power coupler flange temperature too low</description> + <latching>true</latching> + <annunciating>true</annunciating> + <guidance> + <title>[Cryo Operator Action]</title> + <details>contact CRYO on-call and inform SCL on-call, power coupler flange temperature is too low, check heater output, if nominal then coupler flow needs to be adjusted (reduced)</details> + </guidance> + </pv> + <pv name="MBL-050Crm:Cryo-TT-024:P_Limit_HIHI"> + <description>Power coupler flange temperature low</description> + <latching>true</latching> + <annunciating>true</annunciating> + <guidance> + <title>[Cryo Operator Action]</title> + <details>contact CRYO on-call and inform SCL on-call, power coupler flange temperature is too high, check heater output, if nominal then coupler flow needs to be adjusted (increased)</details> + </guidance> + </pv> + <pv name="MBL-050Crm:Cryo-TT-024:P_Limit_LO"> + <description>Power coupler flange temperature too low</description> + <latching>true</latching> + <annunciating>true</annunciating> + <guidance> + <title>[Cryo Operator Action]</title> + <details>contact CRYO on-call and inform SCL on-call, power coupler flange temperature is too low, check heater output, if nominal then coupler flow needs to be adjusted (reduced)</details> + </guidance> + </pv> + <pv name="MBL-050Crm:Cryo-TT-024:P_Limit_LOLO"> + <description>Power coupler flange temperature too high</description> + <latching>true</latching> + <annunciating>true</annunciating> + <guidance> + <title>[Cryo Operator Action]</title> + <details>contact CRYO on-call and inform SCL on-call, power coupler flange temperature is too low, check heater output, if nominal then coupler flow needs to be adjusted (reduced)</details> + </guidance> + </pv> + <pv name="MBL-050Crm:Cryo-TT-034:P_Limit_HIHI"> + <description>Power coupler flange temperature low</description> + <latching>true</latching> + <annunciating>true</annunciating> + <guidance> + <title>[Cryo Operator Action]</title> + <details>contact CRYO on-call and inform SCL on-call, power coupler flange temperature is too high, check heater output, if nominal then coupler flow needs to be adjusted (increased)</details> + </guidance> + </pv> + <pv name="MBL-050Crm:Cryo-TT-034:P_Limit_LO"> + <description>Power coupler flange temperature too low</description> + <latching>true</latching> + <annunciating>true</annunciating> + <guidance> + <title>[Cryo Operator Action]</title> + <details>contact CRYO on-call and inform SCL on-call, power coupler flange temperature is too low, check heater output, if nominal then coupler flow needs to be adjusted (reduced)</details> + </guidance> + </pv> + <pv name="MBL-050Crm:Cryo-TT-034:P_Limit_LOLO"> + <description>Power coupler flange temperature too high</description> + <latching>true</latching> + <annunciating>true</annunciating> + <guidance> + <title>[Cryo Operator Action]</title> + <details>contact CRYO on-call and inform SCL on-call, power coupler flange temperature is too low, check heater output, if nominal then coupler flow needs to be adjusted (reduced)</details> + </guidance> + </pv> + <pv name="MBL-050Crm:Cryo-TT-044:P_Limit_HIHI"> + <description>Power coupler flange temperature low</description> + <latching>true</latching> + <annunciating>true</annunciating> + <guidance> + <title>[Cryo Operator Action]</title> + <details>contact CRYO on-call and inform SCL on-call, power coupler flange temperature is too high, check heater output, if nominal then coupler flow needs to be adjusted (increased)</details> + </guidance> + </pv> + <pv name="MBL-050Crm:Cryo-TT-044:P_Limit_LO"> + <description>Power coupler flange temperature too low</description> + <latching>true</latching> + <annunciating>true</annunciating> + <guidance> + <title>[Cryo Operator Action]</title> + <details>contact CRYO on-call and inform SCL on-call, power coupler flange temperature is too low, check heater output, if nominal then coupler flow needs to be adjusted (reduced)</details> + </guidance> + </pv> + <pv name="MBL-050Crm:Cryo-TT-043:P_Limit_LOLO"> + <description>Power coupler flange temperature too high</description> + <latching>true</latching> + <annunciating>true</annunciating> + <guidance> + <title>[Cryo Operator Action]</title> + <details>contact CRYO on-call and inform SCL on-call, power coupler flange temperature is too low, check heater output, if nominal then coupler flow needs to be adjusted (reduced)</details> + </guidance> + </pv> + <pv name="MBL-050Crm:WtrC-FS-012:Flow_OK_WF"> + <description>! Alarm when signal drops from 1 to zero. No Water Flow Antenna 1</description> + <latching>true</latching> + <annunciating>true</annunciating> + <guidance> + <title>[Cryo Operator Action]</title> + <details>contact CRYO on-call and inform SCL on-call, assure Flange temperature TT-014 is correct. Risk of Water freeze if no flow and temperature too low</details> + </guidance> + </pv> + <pv name="MBL-050Crm:WtrC-FS-022:Flow_OK_WF"> + <description>! Alarm when signal drops from 1 to zero. No Water Flow Antenna 2</description> + <latching>true</latching> + <annunciating>true</annunciating> + <guidance> + <title>[Cryo Operator Action]</title> + <details>contact CRYO on-call and inform SCL on-call, assure Flange temperature TT-024 is correct. Risk of Water freeze if no flow and temperature too low</details> + </guidance> + </pv> + <pv name="MBL-050Crm:WtrC-FS-032:Flow_OK_WF"> + <description>! Alarm when signal drops from 1 to zero. No Water Flow Antenna 3</description> + <latching>true</latching> + <annunciating>true</annunciating> + <guidance> + <title>[Cryo Operator Action]</title> + <details>contact CRYO on-call and inform SCL on-call, assure Flange temperature TT-034 is correct. Risk of Water freeze if no flow and temperature too low</details> + </guidance> + </pv> + <pv name="MBL-050Crm:WtrC-FS-042:Flow_OK_WF"> + <description>! Alarm when signal drops from 1 to zero. No Water Flow Antenna 4</description> + <latching>true</latching> + <annunciating>true</annunciating> + <guidance> + <title>[Cryo Operator Action]</title> + <details>contact CRYO on-call and inform SCL on-call, assure Flange temperature TT-044 is correct. Risk of Water freeze if no flow and temperature too low</details> + </guidance> + </pv> + </component> + <component name="Cryomodules\MBL-060 Cryomodule"> + <pv name="MBL-060Crm:Cryo-LT-001:HIHI"> + <description>LT-001 helium level extremely high</description> + <latching>true</latching> + <annunciating>true</annunciating> + <guidance> + <title>[Cryo Operator Action]</title> + <details>contact CRYO on-call and inform SCL on-call, Cryomodule liquid level too high (check the other gauge LT-002). Close supply valve CV01, CV02</details> + </guidance> + </pv> + <pv name="MBL-060Crm:Cryo-LT-002:HIHI"> + <description>LT-002 helium level extremely high</description> + <latching>true</latching> + <annunciating>true</annunciating> + <guidance> + <title>[Cryo Operator Action]</title> + <details>contact CRYO on-call and inform SCL on-call, Cryomodule liquid level too high (check the other gauge LT-001). Close supply valve CV01, CV02</details> + </guidance> + </pv> + <pv name="MBL-060Crm:Cryo-LT-001:HI"> + <description>LT-001 helium level high</description> + <latching>true</latching> + <annunciating>true</annunciating> + <guidance> + <title>[Cryo Operator Action]</title> + <details>contact CRYO on-call and inform SCL on-call, Cryomodule liquid level high (check the other gauge LT-002). Check level regulation valve settings, if needed: adjust LMN_LO and if necessary: Close supply valve CV01, CV02</details> + </guidance> + </pv> + <pv name="MBL-060Crm:Cryo-LT-002:HI"> + <description>LT-002 helium level high</description> + <latching>true</latching> + <annunciating>true</annunciating> + <guidance> + <title>[Cryo Operator Action]</title> + <details>contact CRYO on-call and inform SCL on-call, Cryomodule liquid level high (check the other gauge LT-002). Check level regulation valve settings, if needed: adjust LMN_LO and if necessary: Close supply valve CV01, CV02</details> + </guidance> + </pv> + <pv name="MBL-060Crm:Cryo-LT-001:LO"> + <description>LT-001 helium level low</description> + <latching>true</latching> + <annunciating>true</annunciating> + <guidance> + <title>[Cryo Operator Action]</title> + <details>contact CRYO on-call and inform SCL on-call, Cryomodule liquid level low (check the other gauge LT-001). Check level regulation valve settings, if needed: adjust LMN_HI</details> + </guidance> + </pv> + <pv name="MBL-060Crm:Cryo-LT-002:LO"> + <description>LT-002 helium level low</description> + <latching>true</latching> + <annunciating>true</annunciating> + <guidance> + <title>[Cryo Operator Action]</title> + <details>contact CRYO on-call and inform SCL on-call, Cryomodule liquid level low (check the other gauge LT-002). Check level regulation valvesettings, if needed: adjust LMN_HI</details> + </guidance> + </pv> + <pv name="MBL-060Crm:Cryo-LT-001:LOLO"> + <description>LT-002 helium level extremely low</description> + <latching>true</latching> + <annunciating>true</annunciating> + <guidance> + <title>[Cryo Operator Action]</title> + <details>contact CRYO on-call and inform SCL on-call, Cryomodule liquid level too low (check the other gauge LT-001). Check level regulation valve settings, if needed: adjust LMN_HI</details> + </guidance> + </pv> + <pv name="MBL-060Crm:Cryo-LT-002:LOLO"> + <description>LT-002 helium level extremely low</description> + <latching>true</latching> + <annunciating>true</annunciating> + <guidance> + <title>[Cryo Operator Action]</title> + <details>contact CRYO on-call and inform SCL on-call, Cryomodule liquid level too low (check the other gauge LT-002). Check level regulation valvesettings, if needed: adjust LMN_HI</details> + </guidance> + </pv> + <pv name="MBL-060Crm:Cryo-PT-003:HIHI"> + <description>Cavity tanks pressure is too high (typical value is 31mbar in 2K mode and 1050mbar in 4K mode)</description> + <latching>true</latching> + <annunciating>true</annunciating> + <guidance> + <title>[Cryo Operator Action]</title> + <details>contact CRYO on-call and inform SCL on-call, Cryomodule bath pressure too high (check the other gauge PT002). Close supply valve CV01, CV02 if necessary</details> + </guidance> + </pv> + <pv name="MBL-060Crm:Cryo-PT-003:Cable_Error"> + <description>Cavity tanks Pressure Sensor cables are disconnected</description> + <latching>true</latching> + <annunciating>true</annunciating> + <guidance> + <title>[Cryo Operator Action]</title> + <details>contact CRYO on-call and inform SCL on-call, Cryomodule pressure cable seems disconnected (value gets stuck), assign PT002 as measuring device on CV04 and CV-090 </details> + </guidance> + </pv> + <pv name="MBL-060Crm:Cryo-PT-004:HIHI"> + <description>Cavity tanks pressure is too high (typical value is 31mbar in 2K mode and 1050mbar in 4K mode)</description> + <latching>true</latching> + <annunciating>true</annunciating> + <guidance> + <title>[Cryo Operator Action]</title> + <details>contact CRYO on-call and inform SCL on-call,, Cryomodule bath pressure too high (check the other gauge PT003). Close supply valve CV01, CV02 if necessary</details> + </guidance> + </pv> + <pv name="MBL-060Crm:Cryo-PT-004:Cable_Error"> + <description>Cavity tanks Pressure Sensor cables are disconnected</description> + <latching>true</latching> + <annunciating>true</annunciating> + <guidance> + <title>[Cryo Operator Action]</title> + <details>contact CRYO on-call and inform SCL on-call, Cryomodule pressure cable seems disconnected (value gets stuck), assign PT003 as measuring device on CV04 and CV-090 </details> + </guidance> + </pv> + <pv name="MBL-060Crm:Cryo-TT-014:P_Limit_HIHI"> + <description>Power coupler flange temperature too high</description> + <latching>true</latching> + <annunciating>true</annunciating> + <guidance> + <title>[Cryo Operator Action]</title> + <details>contact CRYO on-call and inform SCL on-call, power coupler flange temperature is too high, check heater output, if nominal then coupler flow needs to be adjusted (increased)</details> + </guidance> + </pv> + <pv name="MBL-060Crm:Cryo-TT-014:P_Limit_LO"> + <description>Power coupler flange temperature too low</description> + <latching>true</latching> + <annunciating>true</annunciating> + <guidance> + <title>[Cryo Operator Action]</title> + <details>contact CRYO on-call and inform SCL on-call, power coupler flange temperature is too low, check heater output, if nominal then coupler flow needs to be adjusted (reduced)</details> + </guidance> + </pv> + <pv name="MBL-060Crm:Cryo-TT-014:P_Limit_LOLO"> + <description>Power coupler flange temperature too low</description> + <latching>true</latching> + <annunciating>true</annunciating> + <guidance> + <title>[Cryo Operator Action]</title> + <details>contact CRYO on-call and inform SCL on-call, power coupler flange temperature is too low, check heater output, if nominal then coupler flow needs to be adjusted (reduced)</details> + </guidance> + </pv> + <pv name="MBL-060Crm:Cryo-TT-024:P_Limit_HIHI"> + <description>Power coupler flange temperature low</description> + <latching>true</latching> + <annunciating>true</annunciating> + <guidance> + <title>[Cryo Operator Action]</title> + <details>contact CRYO on-call and inform SCL on-call, power coupler flange temperature is too high, check heater output, if nominal then coupler flow needs to be adjusted (increased)</details> + </guidance> + </pv> + <pv name="MBL-060Crm:Cryo-TT-024:P_Limit_LO"> + <description>Power coupler flange temperature too low</description> + <latching>true</latching> + <annunciating>true</annunciating> + <guidance> + <title>[Cryo Operator Action]</title> + <details>contact CRYO on-call and inform SCL on-call, power coupler flange temperature is too low, check heater output, if nominal then coupler flow needs to be adjusted (reduced)</details> + </guidance> + </pv> + <pv name="MBL-060Crm:Cryo-TT-024:P_Limit_LOLO"> + <description>Power coupler flange temperature too high</description> + <latching>true</latching> + <annunciating>true</annunciating> + <guidance> + <title>[Cryo Operator Action]</title> + <details>contact CRYO on-call and inform SCL on-call, power coupler flange temperature is too low, check heater output, if nominal then coupler flow needs to be adjusted (reduced)</details> + </guidance> + </pv> + <pv name="MBL-060Crm:Cryo-TT-034:P_Limit_HIHI"> + <description>Power coupler flange temperature low</description> + <latching>true</latching> + <annunciating>true</annunciating> + <guidance> + <title>[Cryo Operator Action]</title> + <details>contact CRYO on-call and inform SCL on-call, power coupler flange temperature is too high, check heater output, if nominal then coupler flow needs to be adjusted (increased)</details> + </guidance> + </pv> + <pv name="MBL-060Crm:Cryo-TT-034:P_Limit_LO"> + <description>Power coupler flange temperature too low</description> + <latching>true</latching> + <annunciating>true</annunciating> + <guidance> + <title>[Cryo Operator Action]</title> + <details>contact CRYO on-call and inform SCL on-call, power coupler flange temperature is too low, check heater output, if nominal then coupler flow needs to be adjusted (reduced)</details> + </guidance> + </pv> + <pv name="MBL-060Crm:Cryo-TT-034:P_Limit_LOLO"> + <description>Power coupler flange temperature too high</description> + <latching>true</latching> + <annunciating>true</annunciating> + <guidance> + <title>[Cryo Operator Action]</title> + <details>contact CRYO on-call and inform SCL on-call, power coupler flange temperature is too low, check heater output, if nominal then coupler flow needs to be adjusted (reduced)</details> + </guidance> + </pv> + <pv name="MBL-060Crm:Cryo-TT-044:P_Limit_HIHI"> + <description>Power coupler flange temperature low</description> + <latching>true</latching> + <annunciating>true</annunciating> + <guidance> + <title>[Cryo Operator Action]</title> + <details>contact CRYO on-call and inform SCL on-call, power coupler flange temperature is too high, check heater output, if nominal then coupler flow needs to be adjusted (increased)</details> + </guidance> + </pv> + <pv name="MBL-060Crm:Cryo-TT-044:P_Limit_LO"> + <description>Power coupler flange temperature too low</description> + <latching>true</latching> + <annunciating>true</annunciating> + <guidance> + <title>[Cryo Operator Action]</title> + <details>contact CRYO on-call and inform SCL on-call, power coupler flange temperature is too low, check heater output, if nominal then coupler flow needs to be adjusted (reduced)</details> + </guidance> + </pv> + <pv name="MBL-060Crm:Cryo-TT-043:P_Limit_LOLO"> + <description>Power coupler flange temperature too high</description> + <latching>true</latching> + <annunciating>true</annunciating> + <guidance> + <title>[Cryo Operator Action]</title> + <details>contact CRYO on-call and inform SCL on-call, power coupler flange temperature is too low, check heater output, if nominal then coupler flow needs to be adjusted (reduced)</details> + </guidance> + </pv> + <pv name="MBL-060Crm:WtrC-FS-012:Flow_OK_WF"> + <description>! Alarm when signal drops from 1 to zero. No Water Flow Antenna 1</description> + <latching>true</latching> + <annunciating>true</annunciating> + <guidance> + <title>[Cryo Operator Action]</title> + <details>contact CRYO on-call and inform SCL on-call, assure Flange temperature TT-014 is correct. Risk of Water freeze if no flow and temperature too low</details> + </guidance> + </pv> + <pv name="MBL-060Crm:WtrC-FS-022:Flow_OK_WF"> + <description>! Alarm when signal drops from 1 to zero. No Water Flow Antenna 2</description> + <latching>true</latching> + <annunciating>true</annunciating> + <guidance> + <title>[Cryo Operator Action]</title> + <details>contact CRYO on-call and inform SCL on-call, assure Flange temperature TT-024 is correct. Risk of Water freeze if no flow and temperature too low</details> + </guidance> + </pv> + <pv name="MBL-060Crm:WtrC-FS-032:Flow_OK_WF"> + <description>! Alarm when signal drops from 1 to zero. No Water Flow Antenna 3</description> + <latching>true</latching> + <annunciating>true</annunciating> + <guidance> + <title>[Cryo Operator Action]</title> + <details>contact CRYO on-call and inform SCL on-call, assure Flange temperature TT-034 is correct. Risk of Water freeze if no flow and temperature too low</details> + </guidance> + </pv> + <pv name="MBL-060Crm:WtrC-FS-042:Flow_OK_WF"> + <description>! Alarm when signal drops from 1 to zero. No Water Flow Antenna 4</description> + <latching>true</latching> + <annunciating>true</annunciating> + <guidance> + <title>[Cryo Operator Action]</title> + <details>contact CRYO on-call and inform SCL on-call, assure Flange temperature TT-044 is correct. Risk of Water freeze if no flow and temperature too low</details> + </guidance> + </pv> + </component> + <component name="Cryomodules\MBL-070 Cryomodule"> + <pv name="MBL-070Crm:Cryo-LT-001:HIHI"> + <description>LT-001 helium level extremely high</description> + <latching>true</latching> + <annunciating>true</annunciating> + <guidance> + <title>[Cryo Operator Action]</title> + <details>contact CRYO on-call and inform SCL on-call, Cryomodule liquid level too high (check the other gauge LT-002). Close supply valve CV01, CV02</details> + </guidance> + </pv> + <pv name="MBL-070Crm:Cryo-LT-002:HIHI"> + <description>LT-002 helium level extremely high</description> + <latching>true</latching> + <annunciating>true</annunciating> + <guidance> + <title>[Cryo Operator Action]</title> + <details>contact CRYO on-call and inform SCL on-call, Cryomodule liquid level too high (check the other gauge LT-001). Close supply valve CV01, CV02</details> + </guidance> + </pv> + <pv name="MBL-070Crm:Cryo-LT-001:HI"> + <description>LT-001 helium level high</description> + <latching>true</latching> + <annunciating>true</annunciating> + <guidance> + <title>[Cryo Operator Action]</title> + <details>contact CRYO on-call and inform SCL on-call, Cryomodule liquid level high (check the other gauge LT-002). Check level regulation valve settings, if needed: adjust LMN_LO and if necessary: Close supply valve CV01, CV02</details> + </guidance> + </pv> + <pv name="MBL-070Crm:Cryo-LT-002:HI"> + <description>LT-002 helium level high</description> + <latching>true</latching> + <annunciating>true</annunciating> + <guidance> + <title>[Cryo Operator Action]</title> + <details>contact CRYO on-call and inform SCL on-call, Cryomodule liquid level high (check the other gauge LT-002). Check level regulation valve settings, if needed: adjust LMN_LO and if necessary: Close supply valve CV01, CV02</details> + </guidance> + </pv> + <pv name="MBL-070Crm:Cryo-LT-001:LO"> + <description>LT-001 helium level low</description> + <latching>true</latching> + <annunciating>true</annunciating> + <guidance> + <title>[Cryo Operator Action]</title> + <details>contact CRYO on-call and inform SCL on-call, Cryomodule liquid level low (check the other gauge LT-001). Check level regulation valve settings, if needed: adjust LMN_HI</details> + </guidance> + </pv> + <pv name="MBL-070Crm:Cryo-LT-002:LO"> + <description>LT-002 helium level low</description> + <latching>true</latching> + <annunciating>true</annunciating> + <guidance> + <title>[Cryo Operator Action]</title> + <details>contact CRYO on-call and inform SCL on-call, Cryomodule liquid level low (check the other gauge LT-002). Check level regulation valvesettings, if needed: adjust LMN_HI</details> + </guidance> + </pv> + <pv name="MBL-070Crm:Cryo-LT-001:LOLO"> + <description>LT-002 helium level extremely low</description> + <latching>true</latching> + <annunciating>true</annunciating> + <guidance> + <title>[Cryo Operator Action]</title> + <details>contact CRYO on-call and inform SCL on-call, Cryomodule liquid level too low (check the other gauge LT-001). Check level regulation valve settings, if needed: adjust LMN_HI</details> + </guidance> + </pv> + <pv name="MBL-070Crm:Cryo-LT-002:LOLO"> + <description>LT-002 helium level extremely low</description> + <latching>true</latching> + <annunciating>true</annunciating> + <guidance> + <title>[Cryo Operator Action]</title> + <details>contact CRYO on-call and inform SCL on-call, Cryomodule liquid level too low (check the other gauge LT-002). Check level regulation valvesettings, if needed: adjust LMN_HI</details> + </guidance> + </pv> + <pv name="MBL-070Crm:Cryo-PT-003:HIHI"> + <description>Cavity tanks pressure is too high (typical value is 31mbar in 2K mode and 1050mbar in 4K mode)</description> + <latching>true</latching> + <annunciating>true</annunciating> + <guidance> + <title>[Cryo Operator Action]</title> + <details>contact CRYO on-call and inform SCL on-call, Cryomodule bath pressure too high (check the other gauge PT002). Close supply valve CV01, CV02 if necessary</details> + </guidance> + </pv> + <pv name="MBL-070Crm:Cryo-PT-003:Cable_Error"> + <description>Cavity tanks Pressure Sensor cables are disconnected</description> + <latching>true</latching> + <annunciating>true</annunciating> + <guidance> + <title>[Cryo Operator Action]</title> + <details>contact CRYO on-call and inform SCL on-call, Cryomodule pressure cable seems disconnected (value gets stuck), assign PT002 as measuring device on CV04 and CV-090 </details> + </guidance> + </pv> + <pv name="MBL-070Crm:Cryo-PT-004:HIHI"> + <description>Cavity tanks pressure is too high (typical value is 31mbar in 2K mode and 1050mbar in 4K mode)</description> + <latching>true</latching> + <annunciating>true</annunciating> + <guidance> + <title>[Cryo Operator Action]</title> + <details>contact CRYO on-call and inform SCL on-call,, Cryomodule bath pressure too high (check the other gauge PT003). Close supply valve CV01, CV02 if necessary</details> + </guidance> + </pv> + <pv name="MBL-070Crm:Cryo-PT-004:Cable_Error"> + <description>Cavity tanks Pressure Sensor cables are disconnected</description> + <latching>true</latching> + <annunciating>true</annunciating> + <guidance> + <title>[Cryo Operator Action]</title> + <details>contact CRYO on-call and inform SCL on-call, Cryomodule pressure cable seems disconnected (value gets stuck), assign PT003 as measuring device on CV04 and CV-090 </details> + </guidance> + </pv> + <pv name="MBL-070Crm:Cryo-TT-014:P_Limit_HIHI"> + <description>Power coupler flange temperature too high</description> + <latching>true</latching> + <annunciating>true</annunciating> + <guidance> + <title>[Cryo Operator Action]</title> + <details>contact CRYO on-call and inform SCL on-call, power coupler flange temperature is too high, check heater output, if nominal then coupler flow needs to be adjusted (increased)</details> + </guidance> + </pv> + <pv name="MBL-070Crm:Cryo-TT-014:P_Limit_LO"> + <description>Power coupler flange temperature too low</description> + <latching>true</latching> + <annunciating>true</annunciating> + <guidance> + <title>[Cryo Operator Action]</title> + <details>contact CRYO on-call and inform SCL on-call, power coupler flange temperature is too low, check heater output, if nominal then coupler flow needs to be adjusted (reduced)</details> + </guidance> + </pv> + <pv name="MBL-070Crm:Cryo-TT-014:P_Limit_LOLO"> + <description>Power coupler flange temperature too low</description> + <latching>true</latching> + <annunciating>true</annunciating> + <guidance> + <title>[Cryo Operator Action]</title> + <details>contact CRYO on-call and inform SCL on-call, power coupler flange temperature is too low, check heater output, if nominal then coupler flow needs to be adjusted (reduced)</details> + </guidance> + </pv> + <pv name="MBL-070Crm:Cryo-TT-024:P_Limit_HIHI"> + <description>Power coupler flange temperature low</description> + <latching>true</latching> + <annunciating>true</annunciating> + <guidance> + <title>[Cryo Operator Action]</title> + <details>contact CRYO on-call and inform SCL on-call, power coupler flange temperature is too high, check heater output, if nominal then coupler flow needs to be adjusted (increased)</details> + </guidance> + </pv> + <pv name="MBL-070Crm:Cryo-TT-024:P_Limit_LO"> + <description>Power coupler flange temperature too low</description> + <latching>true</latching> + <annunciating>true</annunciating> + <guidance> + <title>[Cryo Operator Action]</title> + <details>contact CRYO on-call and inform SCL on-call, power coupler flange temperature is too low, check heater output, if nominal then coupler flow needs to be adjusted (reduced)</details> + </guidance> + </pv> + <pv name="MBL-070Crm:Cryo-TT-024:P_Limit_LOLO"> + <description>Power coupler flange temperature too high</description> + <latching>true</latching> + <annunciating>true</annunciating> + <guidance> + <title>[Cryo Operator Action]</title> + <details>contact CRYO on-call and inform SCL on-call, power coupler flange temperature is too low, check heater output, if nominal then coupler flow needs to be adjusted (reduced)</details> + </guidance> + </pv> + <pv name="MBL-070Crm:Cryo-TT-034:P_Limit_HIHI"> + <description>Power coupler flange temperature low</description> + <latching>true</latching> + <annunciating>true</annunciating> + <guidance> + <title>[Cryo Operator Action]</title> + <details>contact CRYO on-call and inform SCL on-call, power coupler flange temperature is too high, check heater output, if nominal then coupler flow needs to be adjusted (increased)</details> + </guidance> + </pv> + <pv name="MBL-070Crm:Cryo-TT-034:P_Limit_LO"> + <description>Power coupler flange temperature too low</description> + <latching>true</latching> + <annunciating>true</annunciating> + <guidance> + <title>[Cryo Operator Action]</title> + <details>contact CRYO on-call and inform SCL on-call, power coupler flange temperature is too low, check heater output, if nominal then coupler flow needs to be adjusted (reduced)</details> + </guidance> + </pv> + <pv name="MBL-070Crm:Cryo-TT-034:P_Limit_LOLO"> + <description>Power coupler flange temperature too high</description> + <latching>true</latching> + <annunciating>true</annunciating> + <guidance> + <title>[Cryo Operator Action]</title> + <details>contact CRYO on-call and inform SCL on-call, power coupler flange temperature is too low, check heater output, if nominal then coupler flow needs to be adjusted (reduced)</details> + </guidance> + </pv> + <pv name="MBL-070Crm:Cryo-TT-044:P_Limit_HIHI"> + <description>Power coupler flange temperature low</description> + <latching>true</latching> + <annunciating>true</annunciating> + <guidance> + <title>[Cryo Operator Action]</title> + <details>contact CRYO on-call and inform SCL on-call, power coupler flange temperature is too high, check heater output, if nominal then coupler flow needs to be adjusted (increased)</details> + </guidance> + </pv> + <pv name="MBL-070Crm:Cryo-TT-044:P_Limit_LO"> + <description>Power coupler flange temperature too low</description> + <latching>true</latching> + <annunciating>true</annunciating> + <guidance> + <title>[Cryo Operator Action]</title> + <details>contact CRYO on-call and inform SCL on-call, power coupler flange temperature is too low, check heater output, if nominal then coupler flow needs to be adjusted (reduced)</details> + </guidance> + </pv> + <pv name="MBL-070Crm:Cryo-TT-043:P_Limit_LOLO"> + <description>Power coupler flange temperature too high</description> + <latching>true</latching> + <annunciating>true</annunciating> + <guidance> + <title>[Cryo Operator Action]</title> + <details>contact CRYO on-call and inform SCL on-call, power coupler flange temperature is too low, check heater output, if nominal then coupler flow needs to be adjusted (reduced)</details> + </guidance> + </pv> + <pv name="MBL-070Crm:WtrC-FS-012:Flow_OK_WF"> + <description>! Alarm when signal drops from 1 to zero. No Water Flow Antenna 1</description> + <latching>true</latching> + <annunciating>true</annunciating> + <guidance> + <title>[Cryo Operator Action]</title> + <details>contact CRYO on-call and inform SCL on-call, assure Flange temperature TT-014 is correct. Risk of Water freeze if no flow and temperature too low</details> + </guidance> + </pv> + <pv name="MBL-070Crm:WtrC-FS-022:Flow_OK_WF"> + <description>! Alarm when signal drops from 1 to zero. No Water Flow Antenna 2</description> + <latching>true</latching> + <annunciating>true</annunciating> + <guidance> + <title>[Cryo Operator Action]</title> + <details>contact CRYO on-call and inform SCL on-call, assure Flange temperature TT-024 is correct. Risk of Water freeze if no flow and temperature too low</details> + </guidance> + </pv> + <pv name="MBL-070Crm:WtrC-FS-032:Flow_OK_WF"> + <description>! Alarm when signal drops from 1 to zero. No Water Flow Antenna 3</description> + <latching>true</latching> + <annunciating>true</annunciating> + <guidance> + <title>[Cryo Operator Action]</title> + <details>contact CRYO on-call and inform SCL on-call, assure Flange temperature TT-034 is correct. Risk of Water freeze if no flow and temperature too low</details> + </guidance> + </pv> + <pv name="MBL-070Crm:WtrC-FS-042:Flow_OK_WF"> + <description>! Alarm when signal drops from 1 to zero. No Water Flow Antenna 4</description> + <latching>true</latching> + <annunciating>true</annunciating> + <guidance> + <title>[Cryo Operator Action]</title> + <details>contact CRYO on-call and inform SCL on-call, assure Flange temperature TT-044 is correct. Risk of Water freeze if no flow and temperature too low</details> + </guidance> + </pv> + </component> + <component name="Cryomodules\MBL-080 Cryomodule"> + <pv name="MBL-080Crm:Cryo-LT-001:HIHI"> + <description>LT-001 helium level extremely high</description> + <latching>true</latching> + <annunciating>true</annunciating> + <guidance> + <title>[Cryo Operator Action]</title> + <details>contact CRYO on-call and inform SCL on-call, Cryomodule liquid level too high (check the other gauge LT-002). Close supply valve CV01, CV02</details> + </guidance> + </pv> + <pv name="MBL-080Crm:Cryo-LT-002:HIHI"> + <description>LT-002 helium level extremely high</description> + <latching>true</latching> + <annunciating>true</annunciating> + <guidance> + <title>[Cryo Operator Action]</title> + <details>contact CRYO on-call and inform SCL on-call, Cryomodule liquid level too high (check the other gauge LT-001). Close supply valve CV01, CV02</details> + </guidance> + </pv> + <pv name="MBL-080Crm:Cryo-LT-001:HI"> + <description>LT-001 helium level high</description> + <latching>true</latching> + <annunciating>true</annunciating> + <guidance> + <title>[Cryo Operator Action]</title> + <details>contact CRYO on-call and inform SCL on-call, Cryomodule liquid level high (check the other gauge LT-002). Check level regulation valve settings, if needed: adjust LMN_LO and if necessary: Close supply valve CV01, CV02</details> + </guidance> + </pv> + <pv name="MBL-080Crm:Cryo-LT-002:HI"> + <description>LT-002 helium level high</description> + <latching>true</latching> + <annunciating>true</annunciating> + <guidance> + <title>[Cryo Operator Action]</title> + <details>contact CRYO on-call and inform SCL on-call, Cryomodule liquid level high (check the other gauge LT-002). Check level regulation valve settings, if needed: adjust LMN_LO and if necessary: Close supply valve CV01, CV02</details> + </guidance> + </pv> + <pv name="MBL-080Crm:Cryo-LT-001:LO"> + <description>LT-001 helium level low</description> + <latching>true</latching> + <annunciating>true</annunciating> + <guidance> + <title>[Cryo Operator Action]</title> + <details>contact CRYO on-call and inform SCL on-call, Cryomodule liquid level low (check the other gauge LT-001). Check level regulation valve settings, if needed: adjust LMN_HI</details> + </guidance> + </pv> + <pv name="MBL-080Crm:Cryo-LT-002:LO"> + <description>LT-002 helium level low</description> + <latching>true</latching> + <annunciating>true</annunciating> + <guidance> + <title>[Cryo Operator Action]</title> + <details>contact CRYO on-call and inform SCL on-call, Cryomodule liquid level low (check the other gauge LT-002). Check level regulation valvesettings, if needed: adjust LMN_HI</details> + </guidance> + </pv> + <pv name="MBL-080Crm:Cryo-LT-001:LOLO"> + <description>LT-002 helium level extremely low</description> + <latching>true</latching> + <annunciating>true</annunciating> + <guidance> + <title>[Cryo Operator Action]</title> + <details>contact CRYO on-call and inform SCL on-call, Cryomodule liquid level too low (check the other gauge LT-001). Check level regulation valve settings, if needed: adjust LMN_HI</details> + </guidance> + </pv> + <pv name="MBL-080Crm:Cryo-LT-002:LOLO"> + <description>LT-002 helium level extremely low</description> + <latching>true</latching> + <annunciating>true</annunciating> + <guidance> + <title>[Cryo Operator Action]</title> + <details>contact CRYO on-call and inform SCL on-call, Cryomodule liquid level too low (check the other gauge LT-002). Check level regulation valvesettings, if needed: adjust LMN_HI</details> + </guidance> + </pv> + <pv name="MBL-080Crm:Cryo-PT-003:HIHI"> + <description>Cavity tanks pressure is too high (typical value is 31mbar in 2K mode and 1050mbar in 4K mode)</description> + <latching>true</latching> + <annunciating>true</annunciating> + <guidance> + <title>[Cryo Operator Action]</title> + <details>contact CRYO on-call and inform SCL on-call, Cryomodule bath pressure too high (check the other gauge PT002). Close supply valve CV01, CV02 if necessary</details> + </guidance> + </pv> + <pv name="MBL-080Crm:Cryo-PT-003:Cable_Error"> + <description>Cavity tanks Pressure Sensor cables are disconnected</description> + <latching>true</latching> + <annunciating>true</annunciating> + <guidance> + <title>[Cryo Operator Action]</title> + <details>contact CRYO on-call and inform SCL on-call, Cryomodule pressure cable seems disconnected (value gets stuck), assign PT002 as measuring device on CV04 and CV-090 </details> + </guidance> + </pv> + <pv name="MBL-080Crm:Cryo-PT-004:HIHI"> + <description>Cavity tanks pressure is too high (typical value is 31mbar in 2K mode and 1050mbar in 4K mode)</description> + <latching>true</latching> + <annunciating>true</annunciating> + <guidance> + <title>[Cryo Operator Action]</title> + <details>contact CRYO on-call and inform SCL on-call,, Cryomodule bath pressure too high (check the other gauge PT003). Close supply valve CV01, CV02 if necessary</details> + </guidance> + </pv> + <pv name="MBL-080Crm:Cryo-PT-004:Cable_Error"> + <description>Cavity tanks Pressure Sensor cables are disconnected</description> + <latching>true</latching> + <annunciating>true</annunciating> + <guidance> + <title>[Cryo Operator Action]</title> + <details>contact CRYO on-call and inform SCL on-call, Cryomodule pressure cable seems disconnected (value gets stuck), assign PT003 as measuring device on CV04 and CV-090 </details> + </guidance> + </pv> + <pv name="MBL-080Crm:Cryo-TT-014:P_Limit_HIHI"> + <description>Power coupler flange temperature too high</description> + <latching>true</latching> + <annunciating>true</annunciating> + <guidance> + <title>[Cryo Operator Action]</title> + <details>contact CRYO on-call and inform SCL on-call, power coupler flange temperature is too high, check heater output, if nominal then coupler flow needs to be adjusted (increased)</details> + </guidance> + </pv> + <pv name="MBL-080Crm:Cryo-TT-014:P_Limit_LO"> + <description>Power coupler flange temperature too low</description> + <latching>true</latching> + <annunciating>true</annunciating> + <guidance> + <title>[Cryo Operator Action]</title> + <details>contact CRYO on-call and inform SCL on-call, power coupler flange temperature is too low, check heater output, if nominal then coupler flow needs to be adjusted (reduced)</details> + </guidance> + </pv> + <pv name="MBL-080Crm:Cryo-TT-014:P_Limit_LOLO"> + <description>Power coupler flange temperature too low</description> + <latching>true</latching> + <annunciating>true</annunciating> + <guidance> + <title>[Cryo Operator Action]</title> + <details>contact CRYO on-call and inform SCL on-call, power coupler flange temperature is too low, check heater output, if nominal then coupler flow needs to be adjusted (reduced)</details> + </guidance> + </pv> + <pv name="MBL-080Crm:Cryo-TT-024:P_Limit_HIHI"> + <description>Power coupler flange temperature low</description> + <latching>true</latching> + <annunciating>true</annunciating> + <guidance> + <title>[Cryo Operator Action]</title> + <details>contact CRYO on-call and inform SCL on-call, power coupler flange temperature is too high, check heater output, if nominal then coupler flow needs to be adjusted (increased)</details> + </guidance> + </pv> + <pv name="MBL-080Crm:Cryo-TT-024:P_Limit_LO"> + <description>Power coupler flange temperature too low</description> + <latching>true</latching> + <annunciating>true</annunciating> + <guidance> + <title>[Cryo Operator Action]</title> + <details>contact CRYO on-call and inform SCL on-call, power coupler flange temperature is too low, check heater output, if nominal then coupler flow needs to be adjusted (reduced)</details> + </guidance> + </pv> + <pv name="MBL-080Crm:Cryo-TT-024:P_Limit_LOLO"> + <description>Power coupler flange temperature too high</description> + <latching>true</latching> + <annunciating>true</annunciating> + <guidance> + <title>[Cryo Operator Action]</title> + <details>contact CRYO on-call and inform SCL on-call, power coupler flange temperature is too low, check heater output, if nominal then coupler flow needs to be adjusted (reduced)</details> + </guidance> + </pv> + <pv name="MBL-080Crm:Cryo-TT-034:P_Limit_HIHI"> + <description>Power coupler flange temperature low</description> + <latching>true</latching> + <annunciating>true</annunciating> + <guidance> + <title>[Cryo Operator Action]</title> + <details>contact CRYO on-call and inform SCL on-call, power coupler flange temperature is too high, check heater output, if nominal then coupler flow needs to be adjusted (increased)</details> + </guidance> + </pv> + <pv name="MBL-080Crm:Cryo-TT-034:P_Limit_LO"> + <description>Power coupler flange temperature too low</description> + <latching>true</latching> + <annunciating>true</annunciating> + <guidance> + <title>[Cryo Operator Action]</title> + <details>contact CRYO on-call and inform SCL on-call, power coupler flange temperature is too low, check heater output, if nominal then coupler flow needs to be adjusted (reduced)</details> + </guidance> + </pv> + <pv name="MBL-080Crm:Cryo-TT-034:P_Limit_LOLO"> + <description>Power coupler flange temperature too high</description> + <latching>true</latching> + <annunciating>true</annunciating> + <guidance> + <title>[Cryo Operator Action]</title> + <details>contact CRYO on-call and inform SCL on-call, power coupler flange temperature is too low, check heater output, if nominal then coupler flow needs to be adjusted (reduced)</details> + </guidance> + </pv> + <pv name="MBL-080Crm:Cryo-TT-044:P_Limit_HIHI"> + <description>Power coupler flange temperature low</description> + <latching>true</latching> + <annunciating>true</annunciating> + <guidance> + <title>[Cryo Operator Action]</title> + <details>contact CRYO on-call and inform SCL on-call, power coupler flange temperature is too high, check heater output, if nominal then coupler flow needs to be adjusted (increased)</details> + </guidance> + </pv> + <pv name="MBL-080Crm:Cryo-TT-044:P_Limit_LO"> + <description>Power coupler flange temperature too low</description> + <latching>true</latching> + <annunciating>true</annunciating> + <guidance> + <title>[Cryo Operator Action]</title> + <details>contact CRYO on-call and inform SCL on-call, power coupler flange temperature is too low, check heater output, if nominal then coupler flow needs to be adjusted (reduced)</details> + </guidance> + </pv> + <pv name="MBL-080Crm:Cryo-TT-043:P_Limit_LOLO"> + <description>Power coupler flange temperature too high</description> + <latching>true</latching> + <annunciating>true</annunciating> + <guidance> + <title>[Cryo Operator Action]</title> + <details>contact CRYO on-call and inform SCL on-call, power coupler flange temperature is too low, check heater output, if nominal then coupler flow needs to be adjusted (reduced)</details> + </guidance> + </pv> + <pv name="MBL-080Crm:WtrC-FS-012:Flow_OK_WF"> + <description>! Alarm when signal drops from 1 to zero. No Water Flow Antenna 1</description> + <latching>true</latching> + <annunciating>true</annunciating> + <guidance> + <title>[Cryo Operator Action]</title> + <details>contact CRYO on-call and inform SCL on-call, assure Flange temperature TT-014 is correct. Risk of Water freeze if no flow and temperature too low</details> + </guidance> + </pv> + <pv name="MBL-080Crm:WtrC-FS-022:Flow_OK_WF"> + <description>! Alarm when signal drops from 1 to zero. No Water Flow Antenna 2</description> + <latching>true</latching> + <annunciating>true</annunciating> + <guidance> + <title>[Cryo Operator Action]</title> + <details>contact CRYO on-call and inform SCL on-call, assure Flange temperature TT-024 is correct. Risk of Water freeze if no flow and temperature too low</details> + </guidance> + </pv> + <pv name="MBL-080Crm:WtrC-FS-032:Flow_OK_WF"> + <description>! Alarm when signal drops from 1 to zero. No Water Flow Antenna 3</description> + <latching>true</latching> + <annunciating>true</annunciating> + <guidance> + <title>[Cryo Operator Action]</title> + <details>contact CRYO on-call and inform SCL on-call, assure Flange temperature TT-034 is correct. Risk of Water freeze if no flow and temperature too low</details> + </guidance> + </pv> + <pv name="MBL-080Crm:WtrC-FS-042:Flow_OK_WF"> + <description>! Alarm when signal drops from 1 to zero. No Water Flow Antenna 4</description> + <latching>true</latching> + <annunciating>true</annunciating> + <guidance> + <title>[Cryo Operator Action]</title> + <details>contact CRYO on-call and inform SCL on-call, assure Flange temperature TT-044 is correct. Risk of Water freeze if no flow and temperature too low</details> + </guidance> + </pv> + </component> + <component name="Cryomodules\MBL-090 Cryomodule"> + <pv name="MBL-090Crm:Cryo-LT-001:HIHI"> + <description>LT-001 helium level extremely high</description> + <latching>true</latching> + <annunciating>true</annunciating> + <guidance> + <title>[Cryo Operator Action]</title> + <details>contact CRYO on-call and inform SCL on-call, Cryomodule liquid level too high (check the other gauge LT-002). Close supply valve CV01, CV02</details> + </guidance> + </pv> + <pv name="MBL-090Crm:Cryo-LT-002:HIHI"> + <description>LT-002 helium level extremely high</description> + <latching>true</latching> + <annunciating>true</annunciating> + <guidance> + <title>[Cryo Operator Action]</title> + <details>contact CRYO on-call and inform SCL on-call, Cryomodule liquid level too high (check the other gauge LT-001). Close supply valve CV01, CV02</details> + </guidance> + </pv> + <pv name="MBL-090Crm:Cryo-LT-001:HI"> + <description>LT-001 helium level high</description> + <latching>true</latching> + <annunciating>true</annunciating> + <guidance> + <title>[Cryo Operator Action]</title> + <details>contact CRYO on-call and inform SCL on-call, Cryomodule liquid level high (check the other gauge LT-002). Check level regulation valve settings, if needed: adjust LMN_LO and if necessary: Close supply valve CV01, CV02</details> + </guidance> + </pv> + <pv name="MBL-090Crm:Cryo-LT-002:HI"> + <description>LT-002 helium level high</description> + <latching>true</latching> + <annunciating>true</annunciating> + <guidance> + <title>[Cryo Operator Action]</title> + <details>contact CRYO on-call and inform SCL on-call, Cryomodule liquid level high (check the other gauge LT-002). Check level regulation valve settings, if needed: adjust LMN_LO and if necessary: Close supply valve CV01, CV02</details> + </guidance> + </pv> + <pv name="MBL-090Crm:Cryo-LT-001:LO"> + <description>LT-001 helium level low</description> + <latching>true</latching> + <annunciating>true</annunciating> + <guidance> + <title>[Cryo Operator Action]</title> + <details>contact CRYO on-call and inform SCL on-call, Cryomodule liquid level low (check the other gauge LT-001). Check level regulation valve settings, if needed: adjust LMN_HI</details> + </guidance> + </pv> + <pv name="MBL-090Crm:Cryo-LT-002:LO"> + <description>LT-002 helium level low</description> + <latching>true</latching> + <annunciating>true</annunciating> + <guidance> + <title>[Cryo Operator Action]</title> + <details>contact CRYO on-call and inform SCL on-call, Cryomodule liquid level low (check the other gauge LT-002). Check level regulation valvesettings, if needed: adjust LMN_HI</details> + </guidance> + </pv> + <pv name="MBL-090Crm:Cryo-LT-001:LOLO"> + <description>LT-002 helium level extremely low</description> + <latching>true</latching> + <annunciating>true</annunciating> + <guidance> + <title>[Cryo Operator Action]</title> + <details>contact CRYO on-call and inform SCL on-call, Cryomodule liquid level too low (check the other gauge LT-001). Check level regulation valve settings, if needed: adjust LMN_HI</details> + </guidance> + </pv> + <pv name="MBL-090Crm:Cryo-LT-002:LOLO"> + <description>LT-002 helium level extremely low</description> + <latching>true</latching> + <annunciating>true</annunciating> + <guidance> + <title>[Cryo Operator Action]</title> + <details>contact CRYO on-call and inform SCL on-call, Cryomodule liquid level too low (check the other gauge LT-002). Check level regulation valvesettings, if needed: adjust LMN_HI</details> + </guidance> + </pv> + <pv name="MBL-090Crm:Cryo-PT-003:HIHI"> + <description>Cavity tanks pressure is too high (typical value is 31mbar in 2K mode and 1050mbar in 4K mode)</description> + <latching>true</latching> + <annunciating>true</annunciating> + <guidance> + <title>[Cryo Operator Action]</title> + <details>contact CRYO on-call and inform SCL on-call, Cryomodule bath pressure too high (check the other gauge PT002). Close supply valve CV01, CV02 if necessary</details> + </guidance> + </pv> + <pv name="MBL-090Crm:Cryo-PT-003:Cable_Error"> + <description>Cavity tanks Pressure Sensor cables are disconnected</description> + <latching>true</latching> + <annunciating>true</annunciating> + <guidance> + <title>[Cryo Operator Action]</title> + <details>contact CRYO on-call and inform SCL on-call, Cryomodule pressure cable seems disconnected (value gets stuck), assign PT002 as measuring device on CV04 and CV-090 </details> + </guidance> + </pv> + <pv name="MBL-090Crm:Cryo-PT-004:HIHI"> + <description>Cavity tanks pressure is too high (typical value is 31mbar in 2K mode and 1050mbar in 4K mode)</description> + <latching>true</latching> + <annunciating>true</annunciating> + <guidance> + <title>[Cryo Operator Action]</title> + <details>contact CRYO on-call and inform SCL on-call,, Cryomodule bath pressure too high (check the other gauge PT003). Close supply valve CV01, CV02 if necessary</details> + </guidance> + </pv> + <pv name="MBL-090Crm:Cryo-PT-004:Cable_Error"> + <description>Cavity tanks Pressure Sensor cables are disconnected</description> + <latching>true</latching> + <annunciating>true</annunciating> + <guidance> + <title>[Cryo Operator Action]</title> + <details>contact CRYO on-call and inform SCL on-call, Cryomodule pressure cable seems disconnected (value gets stuck), assign PT003 as measuring device on CV04 and CV-090 </details> + </guidance> + </pv> + <pv name="MBL-090Crm:Cryo-TT-014:P_Limit_HIHI"> + <description>Power coupler flange temperature too high</description> + <latching>true</latching> + <annunciating>true</annunciating> + <guidance> + <title>[Cryo Operator Action]</title> + <details>contact CRYO on-call and inform SCL on-call, power coupler flange temperature is too high, check heater output, if nominal then coupler flow needs to be adjusted (increased)</details> + </guidance> + </pv> + <pv name="MBL-090Crm:Cryo-TT-014:P_Limit_LO"> + <description>Power coupler flange temperature too low</description> + <latching>true</latching> + <annunciating>true</annunciating> + <guidance> + <title>[Cryo Operator Action]</title> + <details>contact CRYO on-call and inform SCL on-call, power coupler flange temperature is too low, check heater output, if nominal then coupler flow needs to be adjusted (reduced)</details> + </guidance> + </pv> + <pv name="MBL-090Crm:Cryo-TT-014:P_Limit_LOLO"> + <description>Power coupler flange temperature too low</description> + <latching>true</latching> + <annunciating>true</annunciating> + <guidance> + <title>[Cryo Operator Action]</title> + <details>contact CRYO on-call and inform SCL on-call, power coupler flange temperature is too low, check heater output, if nominal then coupler flow needs to be adjusted (reduced)</details> + </guidance> + </pv> + <pv name="MBL-090Crm:Cryo-TT-024:P_Limit_HIHI"> + <description>Power coupler flange temperature low</description> + <latching>true</latching> + <annunciating>true</annunciating> + <guidance> + <title>[Cryo Operator Action]</title> + <details>contact CRYO on-call and inform SCL on-call, power coupler flange temperature is too high, check heater output, if nominal then coupler flow needs to be adjusted (increased)</details> + </guidance> + </pv> + <pv name="MBL-090Crm:Cryo-TT-024:P_Limit_LO"> + <description>Power coupler flange temperature too low</description> + <latching>true</latching> + <annunciating>true</annunciating> + <guidance> + <title>[Cryo Operator Action]</title> + <details>contact CRYO on-call and inform SCL on-call, power coupler flange temperature is too low, check heater output, if nominal then coupler flow needs to be adjusted (reduced)</details> + </guidance> + </pv> + <pv name="MBL-090Crm:Cryo-TT-024:P_Limit_LOLO"> + <description>Power coupler flange temperature too high</description> + <latching>true</latching> + <annunciating>true</annunciating> + <guidance> + <title>[Cryo Operator Action]</title> + <details>contact CRYO on-call and inform SCL on-call, power coupler flange temperature is too low, check heater output, if nominal then coupler flow needs to be adjusted (reduced)</details> + </guidance> + </pv> + <pv name="MBL-090Crm:Cryo-TT-034:P_Limit_HIHI"> + <description>Power coupler flange temperature low</description> + <latching>true</latching> + <annunciating>true</annunciating> + <guidance> + <title>[Cryo Operator Action]</title> + <details>contact CRYO on-call and inform SCL on-call, power coupler flange temperature is too high, check heater output, if nominal then coupler flow needs to be adjusted (increased)</details> + </guidance> + </pv> + <pv name="MBL-090Crm:Cryo-TT-034:P_Limit_LO"> + <description>Power coupler flange temperature too low</description> + <latching>true</latching> + <annunciating>true</annunciating> + <guidance> + <title>[Cryo Operator Action]</title> + <details>contact CRYO on-call and inform SCL on-call, power coupler flange temperature is too low, check heater output, if nominal then coupler flow needs to be adjusted (reduced)</details> + </guidance> + </pv> + <pv name="MBL-090Crm:Cryo-TT-034:P_Limit_LOLO"> + <description>Power coupler flange temperature too high</description> + <latching>true</latching> + <annunciating>true</annunciating> + <guidance> + <title>[Cryo Operator Action]</title> + <details>contact CRYO on-call and inform SCL on-call, power coupler flange temperature is too low, check heater output, if nominal then coupler flow needs to be adjusted (reduced)</details> + </guidance> + </pv> + <pv name="MBL-090Crm:Cryo-TT-044:P_Limit_HIHI"> + <description>Power coupler flange temperature low</description> + <latching>true</latching> + <annunciating>true</annunciating> + <guidance> + <title>[Cryo Operator Action]</title> + <details>contact CRYO on-call and inform SCL on-call, power coupler flange temperature is too high, check heater output, if nominal then coupler flow needs to be adjusted (increased)</details> + </guidance> + </pv> + <pv name="MBL-090Crm:Cryo-TT-044:P_Limit_LO"> + <description>Power coupler flange temperature too low</description> + <latching>true</latching> + <annunciating>true</annunciating> + <guidance> + <title>[Cryo Operator Action]</title> + <details>contact CRYO on-call and inform SCL on-call, power coupler flange temperature is too low, check heater output, if nominal then coupler flow needs to be adjusted (reduced)</details> + </guidance> + </pv> + <pv name="MBL-090Crm:Cryo-TT-043:P_Limit_LOLO"> + <description>Power coupler flange temperature too high</description> + <latching>true</latching> + <annunciating>true</annunciating> + <guidance> + <title>[Cryo Operator Action]</title> + <details>contact CRYO on-call and inform SCL on-call, power coupler flange temperature is too low, check heater output, if nominal then coupler flow needs to be adjusted (reduced)</details> + </guidance> + </pv> + <pv name="MBL-090Crm:WtrC-FS-012:Flow_OK_WF"> + <description>! Alarm when signal drops from 1 to zero. No Water Flow Antenna 1</description> + <latching>true</latching> + <annunciating>true</annunciating> + <guidance> + <title>[Cryo Operator Action]</title> + <details>contact CRYO on-call and inform SCL on-call, assure Flange temperature TT-014 is correct. Risk of Water freeze if no flow and temperature too low</details> + </guidance> + </pv> + <pv name="MBL-090Crm:WtrC-FS-022:Flow_OK_WF"> + <description>! Alarm when signal drops from 1 to zero. No Water Flow Antenna 2</description> + <latching>true</latching> + <annunciating>true</annunciating> + <guidance> + <title>[Cryo Operator Action]</title> + <details>contact CRYO on-call and inform SCL on-call, assure Flange temperature TT-024 is correct. Risk of Water freeze if no flow and temperature too low</details> + </guidance> + </pv> + <pv name="MBL-090Crm:WtrC-FS-032:Flow_OK_WF"> + <description>! Alarm when signal drops from 1 to zero. No Water Flow Antenna 3</description> + <latching>true</latching> + <annunciating>true</annunciating> + <guidance> + <title>[Cryo Operator Action]</title> + <details>contact CRYO on-call and inform SCL on-call, assure Flange temperature TT-034 is correct. Risk of Water freeze if no flow and temperature too low</details> + </guidance> + </pv> + <pv name="MBL-090Crm:WtrC-FS-042:Flow_OK_WF"> + <description>! Alarm when signal drops from 1 to zero. No Water Flow Antenna 4</description> + <latching>true</latching> + <annunciating>true</annunciating> + <guidance> + <title>[Cryo Operator Action]</title> + <details>contact CRYO on-call and inform SCL on-call, assure Flange temperature TT-044 is correct. Risk of Water freeze if no flow and temperature too low</details> + </guidance> + </pv> + </component> + <component name="Cryomodules\HBL-010 Cryomodule"> + <pv name="HBL-010Crm:Cryo-LT-001:HIHI"> + <description>LT-001 helium level extremely high</description> + <latching>true</latching> + <annunciating>true</annunciating> + <guidance> + <title>[Cryo Operator Action]</title> + <details>contact CRYO on-call and inform SCL on-call, Cryomodule liquid level too high (check the other gauge LT-002). Close supply valve CV01, CV02</details> + </guidance> + </pv> + <pv name="HBL-010Crm:Cryo-LT-002:HIHI"> + <description>LT-002 helium level extremely high</description> + <latching>true</latching> + <annunciating>true</annunciating> + <guidance> + <title>[Cryo Operator Action]</title> + <details>contact CRYO on-call and inform SCL on-call, Cryomodule liquid level too high (check the other gauge LT-001). Close supply valve CV01, CV02</details> + </guidance> + </pv> + <pv name="HBL-010Crm:Cryo-LT-001:HI"> + <description>LT-001 helium level high</description> + <latching>true</latching> + <annunciating>true</annunciating> + <guidance> + <title>[Cryo Operator Action]</title> + <details>contact CRYO on-call and inform SCL on-call, Cryomodule liquid level high (check the other gauge LT-002). Check level regulation valve settings, if needed: adjust LMN_LO and if necessary: Close supply valve CV01, CV02</details> + </guidance> + </pv> + <pv name="HBL-010Crm:Cryo-LT-002:HI"> + <description>LT-002 helium level high</description> + <latching>true</latching> + <annunciating>true</annunciating> + <guidance> + <title>[Cryo Operator Action]</title> + <details>contact CRYO on-call and inform SCL on-call, Cryomodule liquid level high (check the other gauge LT-002). Check level regulation valve settings, if needed: adjust LMN_LO and if necessary: Close supply valve CV01, CV02</details> + </guidance> + </pv> + <pv name="HBL-010Crm:Cryo-LT-001:LO"> + <description>LT-001 helium level low</description> + <latching>true</latching> + <annunciating>true</annunciating> + <guidance> + <title>[Cryo Operator Action]</title> + <details>contact CRYO on-call and inform SCL on-call, Cryomodule liquid level low (check the other gauge LT-001). Check level regulation valve settings, if needed: adjust LMN_HI</details> + </guidance> + </pv> + <pv name="HBL-010Crm:Cryo-LT-002:LO"> + <description>LT-002 helium level low</description> + <latching>true</latching> + <annunciating>true</annunciating> + <guidance> + <title>[Cryo Operator Action]</title> + <details>contact CRYO on-call and inform SCL on-call, Cryomodule liquid level low (check the other gauge LT-002). Check level regulation valvesettings, if needed: adjust LMN_HI</details> + </guidance> + </pv> + <pv name="HBL-010Crm:Cryo-LT-001:LOLO"> + <description>LT-002 helium level extremely low</description> + <latching>true</latching> + <annunciating>true</annunciating> + <guidance> + <title>[Cryo Operator Action]</title> + <details>contact CRYO on-call and inform SCL on-call, Cryomodule liquid level too low (check the other gauge LT-001). Check level regulation valve settings, if needed: adjust LMN_HI</details> + </guidance> + </pv> + <pv name="HBL-010Crm:Cryo-LT-002:LOLO"> + <description>LT-002 helium level extremely low</description> + <latching>true</latching> + <annunciating>true</annunciating> + <guidance> + <title>[Cryo Operator Action]</title> + <details>contact CRYO on-call and inform SCL on-call, Cryomodule liquid level too low (check the other gauge LT-002). Check level regulation valvesettings, if needed: adjust LMN_HI</details> + </guidance> + </pv> + <pv name="HBL-010Crm:Cryo-PT-003:HIHI"> + <description>Cavity tanks pressure is too high (typical value is 31mbar in 2K mode and 1050mbar in 4K mode)</description> + <latching>true</latching> + <annunciating>true</annunciating> + <guidance> + <title>[Cryo Operator Action]</title> + <details>contact CRYO on-call and inform SCL on-call, Cryomodule bath pressure too high (check the other gauge PT002). Close supply valve CV01, CV02 if necessary</details> + </guidance> + </pv> + <pv name="HBL-010Crm:Cryo-PT-003:Cable_Error"> + <description>Cavity tanks Pressure Sensor cables are disconnected</description> + <latching>true</latching> + <annunciating>true</annunciating> + <guidance> + <title>[Cryo Operator Action]</title> + <details>contact CRYO on-call and inform SCL on-call, Cryomodule pressure cable seems disconnected (value gets stuck), assign PT002 as measuring device on CV04 and CV-090 </details> + </guidance> + </pv> + <pv name="HBL-010Crm:Cryo-PT-004:HIHI"> + <description>Cavity tanks pressure is too high (typical value is 31mbar in 2K mode and 1050mbar in 4K mode)</description> + <latching>true</latching> + <annunciating>true</annunciating> + <guidance> + <title>[Cryo Operator Action]</title> + <details>contact CRYO on-call and inform SCL on-call,, Cryomodule bath pressure too high (check the other gauge PT003). Close supply valve CV01, CV02 if necessary</details> + </guidance> + </pv> + <pv name="HBL-010Crm:Cryo-PT-004:Cable_Error"> + <description>Cavity tanks Pressure Sensor cables are disconnected</description> + <latching>true</latching> + <annunciating>true</annunciating> + <guidance> + <title>[Cryo Operator Action]</title> + <details>contact CRYO on-call and inform SCL on-call, Cryomodule pressure cable seems disconnected (value gets stuck), assign PT003 as measuring device on CV04 and CV-090 </details> + </guidance> + </pv> + <pv name="HBL-010Crm:Cryo-TT-014:P_Limit_HIHI"> + <description>Power coupler flange temperature too high</description> + <latching>true</latching> + <annunciating>true</annunciating> + <guidance> + <title>[Cryo Operator Action]</title> + <details>contact CRYO on-call and inform SCL on-call, power coupler flange temperature is too high, check heater output, if nominal then coupler flow needs to be adjusted (increased)</details> + </guidance> + </pv> + <pv name="HBL-010Crm:Cryo-TT-014:P_Limit_LO"> + <description>Power coupler flange temperature too low</description> + <latching>true</latching> + <annunciating>true</annunciating> + <guidance> + <title>[Cryo Operator Action]</title> + <details>contact CRYO on-call and inform SCL on-call, power coupler flange temperature is too low, check heater output, if nominal then coupler flow needs to be adjusted (reduced)</details> + </guidance> + </pv> + <pv name="HBL-010Crm:Cryo-TT-014:P_Limit_LOLO"> + <description>Power coupler flange temperature too low</description> + <latching>true</latching> + <annunciating>true</annunciating> + <guidance> + <title>[Cryo Operator Action]</title> + <details>contact CRYO on-call and inform SCL on-call, power coupler flange temperature is too low, check heater output, if nominal then coupler flow needs to be adjusted (reduced)</details> + </guidance> + </pv> + <pv name="HBL-010Crm:Cryo-TT-024:P_Limit_HIHI"> + <description>Power coupler flange temperature low</description> + <latching>true</latching> + <annunciating>true</annunciating> + <guidance> + <title>[Cryo Operator Action]</title> + <details>contact CRYO on-call and inform SCL on-call, power coupler flange temperature is too high, check heater output, if nominal then coupler flow needs to be adjusted (increased)</details> + </guidance> + </pv> + <pv name="HBL-010Crm:Cryo-TT-024:P_Limit_LO"> + <description>Power coupler flange temperature too low</description> + <latching>true</latching> + <annunciating>true</annunciating> + <guidance> + <title>[Cryo Operator Action]</title> + <details>contact CRYO on-call and inform SCL on-call, power coupler flange temperature is too low, check heater output, if nominal then coupler flow needs to be adjusted (reduced)</details> + </guidance> + </pv> + <pv name="HBL-010Crm:Cryo-TT-024:P_Limit_LOLO"> + <description>Power coupler flange temperature too high</description> + <latching>true</latching> + <annunciating>true</annunciating> + <guidance> + <title>[Cryo Operator Action]</title> + <details>contact CRYO on-call and inform SCL on-call, power coupler flange temperature is too low, check heater output, if nominal then coupler flow needs to be adjusted (reduced)</details> + </guidance> + </pv> + <pv name="HBL-010Crm:Cryo-TT-034:P_Limit_HIHI"> + <description>Power coupler flange temperature low</description> + <latching>true</latching> + <annunciating>true</annunciating> + <guidance> + <title>[Cryo Operator Action]</title> + <details>contact CRYO on-call and inform SCL on-call, power coupler flange temperature is too high, check heater output, if nominal then coupler flow needs to be adjusted (increased)</details> + </guidance> + </pv> + <pv name="HBL-010Crm:Cryo-TT-034:P_Limit_LO"> + <description>Power coupler flange temperature too low</description> + <latching>true</latching> + <annunciating>true</annunciating> + <guidance> + <title>[Cryo Operator Action]</title> + <details>contact CRYO on-call and inform SCL on-call, power coupler flange temperature is too low, check heater output, if nominal then coupler flow needs to be adjusted (reduced)</details> + </guidance> + </pv> + <pv name="HBL-010Crm:Cryo-TT-034:P_Limit_LOLO"> + <description>Power coupler flange temperature too high</description> + <latching>true</latching> + <annunciating>true</annunciating> + <guidance> + <title>[Cryo Operator Action]</title> + <details>contact CRYO on-call and inform SCL on-call, power coupler flange temperature is too low, check heater output, if nominal then coupler flow needs to be adjusted (reduced)</details> + </guidance> + </pv> + <pv name="HBL-010Crm:Cryo-TT-044:P_Limit_HIHI"> + <description>Power coupler flange temperature low</description> + <latching>true</latching> + <annunciating>true</annunciating> + <guidance> + <title>[Cryo Operator Action]</title> + <details>contact CRYO on-call and inform SCL on-call, power coupler flange temperature is too high, check heater output, if nominal then coupler flow needs to be adjusted (increased)</details> + </guidance> + </pv> + <pv name="HBL-010Crm:Cryo-TT-044:P_Limit_LO"> + <description>Power coupler flange temperature too low</description> + <latching>true</latching> + <annunciating>true</annunciating> + <guidance> + <title>[Cryo Operator Action]</title> + <details>contact CRYO on-call and inform SCL on-call, power coupler flange temperature is too low, check heater output, if nominal then coupler flow needs to be adjusted (reduced)</details> + </guidance> + </pv> + <pv name="HBL-010Crm:Cryo-TT-043:P_Limit_LOLO"> + <description>Power coupler flange temperature too high</description> + <latching>true</latching> + <annunciating>true</annunciating> + <guidance> + <title>[Cryo Operator Action]</title> + <details>contact CRYO on-call and inform SCL on-call, power coupler flange temperature is too low, check heater output, if nominal then coupler flow needs to be adjusted (reduced)</details> + </guidance> + </pv> + <pv name="HBL-010Crm:WtrC-FS-012:Flow_OK_WF"> + <description>! Alarm when signal drops from 1 to zero. No Water Flow Antenna 1</description> + <latching>true</latching> + <annunciating>true</annunciating> + <guidance> + <title>[Cryo Operator Action]</title> + <details>contact CRYO on-call and inform SCL on-call, assure Flange temperature TT-014 is correct. Risk of Water freeze if no flow and temperature too low</details> + </guidance> + </pv> + <pv name="HBL-010Crm:WtrC-FS-022:Flow_OK_WF"> + <description>! Alarm when signal drops from 1 to zero. No Water Flow Antenna 2</description> + <latching>true</latching> + <annunciating>true</annunciating> + <guidance> + <title>[Cryo Operator Action]</title> + <details>contact CRYO on-call and inform SCL on-call, assure Flange temperature TT-024 is correct. Risk of Water freeze if no flow and temperature too low</details> + </guidance> + </pv> + <pv name="HBL-010Crm:WtrC-FS-032:Flow_OK_WF"> + <description>! Alarm when signal drops from 1 to zero. No Water Flow Antenna 3</description> + <latching>true</latching> + <annunciating>true</annunciating> + <guidance> + <title>[Cryo Operator Action]</title> + <details>contact CRYO on-call and inform SCL on-call, assure Flange temperature TT-034 is correct. Risk of Water freeze if no flow and temperature too low</details> + </guidance> + </pv> + <pv name="HBL-010Crm:WtrC-FS-042:Flow_OK_WF"> + <description>! Alarm when signal drops from 1 to zero. No Water Flow Antenna 4</description> + <latching>true</latching> + <annunciating>true</annunciating> + <guidance> + <title>[Cryo Operator Action]</title> + <details>contact CRYO on-call and inform SCL on-call, assure Flange temperature TT-044 is correct. Risk of Water freeze if no flow and temperature too low</details> + </guidance> + </pv> + </component> + <component name="Cryomodules\HBL-020 Cryomodule"> + <pv name="HBL-020Crm:Cryo-LT-001:HIHI"> + <description>LT-001 helium level extremely high</description> + <latching>true</latching> + <annunciating>true</annunciating> + <guidance> + <title>[Cryo Operator Action]</title> + <details>contact CRYO on-call and inform SCL on-call, Cryomodule liquid level too high (check the other gauge LT-002). Close supply valve CV01, CV02</details> + </guidance> + </pv> + <pv name="HBL-020Crm:Cryo-LT-002:HIHI"> + <description>LT-002 helium level extremely high</description> + <latching>true</latching> + <annunciating>true</annunciating> + <guidance> + <title>[Cryo Operator Action]</title> + <details>contact CRYO on-call and inform SCL on-call, Cryomodule liquid level too high (check the other gauge LT-001). Close supply valve CV01, CV02</details> + </guidance> + </pv> + <pv name="HBL-020Crm:Cryo-LT-001:HI"> + <description>LT-001 helium level high</description> + <latching>true</latching> + <annunciating>true</annunciating> + <guidance> + <title>[Cryo Operator Action]</title> + <details>contact CRYO on-call and inform SCL on-call, Cryomodule liquid level high (check the other gauge LT-002). Check level regulation valve settings, if needed: adjust LMN_LO and if necessary: Close supply valve CV01, CV02</details> + </guidance> + </pv> + <pv name="HBL-020Crm:Cryo-LT-002:HI"> + <description>LT-002 helium level high</description> + <latching>true</latching> + <annunciating>true</annunciating> + <guidance> + <title>[Cryo Operator Action]</title> + <details>contact CRYO on-call and inform SCL on-call, Cryomodule liquid level high (check the other gauge LT-002). Check level regulation valve settings, if needed: adjust LMN_LO and if necessary: Close supply valve CV01, CV02</details> + </guidance> + </pv> + <pv name="HBL-020Crm:Cryo-LT-001:LO"> + <description>LT-001 helium level low</description> + <latching>true</latching> + <annunciating>true</annunciating> + <guidance> + <title>[Cryo Operator Action]</title> + <details>contact CRYO on-call and inform SCL on-call, Cryomodule liquid level low (check the other gauge LT-001). Check level regulation valve settings, if needed: adjust LMN_HI</details> + </guidance> + </pv> + <pv name="HBL-020Crm:Cryo-LT-002:LO"> + <description>LT-002 helium level low</description> + <latching>true</latching> + <annunciating>true</annunciating> + <guidance> + <title>[Cryo Operator Action]</title> + <details>contact CRYO on-call and inform SCL on-call, Cryomodule liquid level low (check the other gauge LT-002). Check level regulation valvesettings, if needed: adjust LMN_HI</details> + </guidance> + </pv> + <pv name="HBL-020Crm:Cryo-LT-001:LOLO"> + <description>LT-002 helium level extremely low</description> + <latching>true</latching> + <annunciating>true</annunciating> + <guidance> + <title>[Cryo Operator Action]</title> + <details>contact CRYO on-call and inform SCL on-call, Cryomodule liquid level too low (check the other gauge LT-001). Check level regulation valve settings, if needed: adjust LMN_HI</details> + </guidance> + </pv> + <pv name="HBL-020Crm:Cryo-LT-002:LOLO"> + <description>LT-002 helium level extremely low</description> + <latching>true</latching> + <annunciating>true</annunciating> + <guidance> + <title>[Cryo Operator Action]</title> + <details>contact CRYO on-call and inform SCL on-call, Cryomodule liquid level too low (check the other gauge LT-002). Check level regulation valvesettings, if needed: adjust LMN_HI</details> + </guidance> + </pv> + <pv name="HBL-020Crm:Cryo-PT-003:HIHI"> + <description>Cavity tanks pressure is too high (typical value is 31mbar in 2K mode and 1050mbar in 4K mode)</description> + <latching>true</latching> + <annunciating>true</annunciating> + <guidance> + <title>[Cryo Operator Action]</title> + <details>contact CRYO on-call and inform SCL on-call, Cryomodule bath pressure too high (check the other gauge PT002). Close supply valve CV01, CV02 if necessary</details> + </guidance> + </pv> + <pv name="HBL-020Crm:Cryo-PT-003:Cable_Error"> + <description>Cavity tanks Pressure Sensor cables are disconnected</description> + <latching>true</latching> + <annunciating>true</annunciating> + <guidance> + <title>[Cryo Operator Action]</title> + <details>contact CRYO on-call and inform SCL on-call, Cryomodule pressure cable seems disconnected (value gets stuck), assign PT002 as measuring device on CV04 and CV-090 </details> + </guidance> + </pv> + <pv name="HBL-020Crm:Cryo-PT-004:HIHI"> + <description>Cavity tanks pressure is too high (typical value is 31mbar in 2K mode and 1050mbar in 4K mode)</description> + <latching>true</latching> + <annunciating>true</annunciating> + <guidance> + <title>[Cryo Operator Action]</title> + <details>contact CRYO on-call and inform SCL on-call,, Cryomodule bath pressure too high (check the other gauge PT003). Close supply valve CV01, CV02 if necessary</details> + </guidance> + </pv> + <pv name="HBL-020Crm:Cryo-PT-004:Cable_Error"> + <description>Cavity tanks Pressure Sensor cables are disconnected</description> + <latching>true</latching> + <annunciating>true</annunciating> + <guidance> + <title>[Cryo Operator Action]</title> + <details>contact CRYO on-call and inform SCL on-call, Cryomodule pressure cable seems disconnected (value gets stuck), assign PT003 as measuring device on CV04 and CV-090 </details> + </guidance> + </pv> + <pv name="HBL-020Crm:Cryo-TT-014:P_Limit_HIHI"> + <description>Power coupler flange temperature too high</description> + <latching>true</latching> + <annunciating>true</annunciating> + <guidance> + <title>[Cryo Operator Action]</title> + <details>contact CRYO on-call and inform SCL on-call, power coupler flange temperature is too high, check heater output, if nominal then coupler flow needs to be adjusted (increased)</details> + </guidance> + </pv> + <pv name="HBL-020Crm:Cryo-TT-014:P_Limit_LO"> + <description>Power coupler flange temperature too low</description> + <latching>true</latching> + <annunciating>true</annunciating> + <guidance> + <title>[Cryo Operator Action]</title> + <details>contact CRYO on-call and inform SCL on-call, power coupler flange temperature is too low, check heater output, if nominal then coupler flow needs to be adjusted (reduced)</details> + </guidance> + </pv> + <pv name="HBL-020Crm:Cryo-TT-014:P_Limit_LOLO"> + <description>Power coupler flange temperature too low</description> + <latching>true</latching> + <annunciating>true</annunciating> + <guidance> + <title>[Cryo Operator Action]</title> + <details>contact CRYO on-call and inform SCL on-call, power coupler flange temperature is too low, check heater output, if nominal then coupler flow needs to be adjusted (reduced)</details> + </guidance> + </pv> + <pv name="HBL-020Crm:Cryo-TT-024:P_Limit_HIHI"> + <description>Power coupler flange temperature low</description> + <latching>true</latching> + <annunciating>true</annunciating> + <guidance> + <title>[Cryo Operator Action]</title> + <details>contact CRYO on-call and inform SCL on-call, power coupler flange temperature is too high, check heater output, if nominal then coupler flow needs to be adjusted (increased)</details> + </guidance> + </pv> + <pv name="HBL-020Crm:Cryo-TT-024:P_Limit_LO"> + <description>Power coupler flange temperature too low</description> + <latching>true</latching> + <annunciating>true</annunciating> + <guidance> + <title>[Cryo Operator Action]</title> + <details>contact CRYO on-call and inform SCL on-call, power coupler flange temperature is too low, check heater output, if nominal then coupler flow needs to be adjusted (reduced)</details> + </guidance> + </pv> + <pv name="HBL-020Crm:Cryo-TT-024:P_Limit_LOLO"> + <description>Power coupler flange temperature too high</description> + <latching>true</latching> + <annunciating>true</annunciating> + <guidance> + <title>[Cryo Operator Action]</title> + <details>contact CRYO on-call and inform SCL on-call, power coupler flange temperature is too low, check heater output, if nominal then coupler flow needs to be adjusted (reduced)</details> + </guidance> + </pv> + <pv name="HBL-020Crm:Cryo-TT-034:P_Limit_HIHI"> + <description>Power coupler flange temperature low</description> + <latching>true</latching> + <annunciating>true</annunciating> + <guidance> + <title>[Cryo Operator Action]</title> + <details>contact CRYO on-call and inform SCL on-call, power coupler flange temperature is too high, check heater output, if nominal then coupler flow needs to be adjusted (increased)</details> + </guidance> + </pv> + <pv name="HBL-020Crm:Cryo-TT-034:P_Limit_LO"> + <description>Power coupler flange temperature too low</description> + <latching>true</latching> + <annunciating>true</annunciating> + <guidance> + <title>[Cryo Operator Action]</title> + <details>contact CRYO on-call and inform SCL on-call, power coupler flange temperature is too low, check heater output, if nominal then coupler flow needs to be adjusted (reduced)</details> + </guidance> + </pv> + <pv name="HBL-020Crm:Cryo-TT-034:P_Limit_LOLO"> + <description>Power coupler flange temperature too high</description> + <latching>true</latching> + <annunciating>true</annunciating> + <guidance> + <title>[Cryo Operator Action]</title> + <details>contact CRYO on-call and inform SCL on-call, power coupler flange temperature is too low, check heater output, if nominal then coupler flow needs to be adjusted (reduced)</details> + </guidance> + </pv> + <pv name="HBL-020Crm:Cryo-TT-044:P_Limit_HIHI"> + <description>Power coupler flange temperature low</description> + <latching>true</latching> + <annunciating>true</annunciating> + <guidance> + <title>[Cryo Operator Action]</title> + <details>contact CRYO on-call and inform SCL on-call, power coupler flange temperature is too high, check heater output, if nominal then coupler flow needs to be adjusted (increased)</details> + </guidance> + </pv> + <pv name="HBL-020Crm:Cryo-TT-044:P_Limit_LO"> + <description>Power coupler flange temperature too low</description> + <latching>true</latching> + <annunciating>true</annunciating> + <guidance> + <title>[Cryo Operator Action]</title> + <details>contact CRYO on-call and inform SCL on-call, power coupler flange temperature is too low, check heater output, if nominal then coupler flow needs to be adjusted (reduced)</details> + </guidance> + </pv> + <pv name="HBL-020Crm:Cryo-TT-043:P_Limit_LOLO"> + <description>Power coupler flange temperature too high</description> + <latching>true</latching> + <annunciating>true</annunciating> + <guidance> + <title>[Cryo Operator Action]</title> + <details>contact CRYO on-call and inform SCL on-call, power coupler flange temperature is too low, check heater output, if nominal then coupler flow needs to be adjusted (reduced)</details> + </guidance> + </pv> + <pv name="HBL-020Crm:WtrC-FS-012:Flow_OK_WF"> + <description>! Alarm when signal drops from 1 to zero. No Water Flow Antenna 1</description> + <latching>true</latching> + <annunciating>true</annunciating> + <guidance> + <title>[Cryo Operator Action]</title> + <details>contact CRYO on-call and inform SCL on-call, assure Flange temperature TT-014 is correct. Risk of Water freeze if no flow and temperature too low</details> + </guidance> + </pv> + <pv name="HBL-020Crm:WtrC-FS-022:Flow_OK_WF"> + <description>! Alarm when signal drops from 1 to zero. No Water Flow Antenna 2</description> + <latching>true</latching> + <annunciating>true</annunciating> + <guidance> + <title>[Cryo Operator Action]</title> + <details>contact CRYO on-call and inform SCL on-call, assure Flange temperature TT-024 is correct. Risk of Water freeze if no flow and temperature too low</details> + </guidance> + </pv> + <pv name="HBL-020Crm:WtrC-FS-032:Flow_OK_WF"> + <description>! Alarm when signal drops from 1 to zero. No Water Flow Antenna 3</description> + <latching>true</latching> + <annunciating>true</annunciating> + <guidance> + <title>[Cryo Operator Action]</title> + <details>contact CRYO on-call and inform SCL on-call, assure Flange temperature TT-034 is correct. Risk of Water freeze if no flow and temperature too low</details> + </guidance> + </pv> + <pv name="HBL-020Crm:WtrC-FS-042:Flow_OK_WF"> + <description>! Alarm when signal drops from 1 to zero. No Water Flow Antenna 4</description> + <latching>true</latching> + <annunciating>true</annunciating> + <guidance> + <title>[Cryo Operator Action]</title> + <details>contact CRYO on-call and inform SCL on-call, assure Flange temperature TT-044 is correct. Risk of Water freeze if no flow and temperature too low</details> + </guidance> + </pv> + </component> + <component name="Cryomodules\HBL-030 Cryomodule"> + <pv name="HBL-030Crm:Cryo-LT-001:HIHI"> + <description>LT-001 helium level extremely high</description> + <latching>true</latching> + <annunciating>true</annunciating> + <guidance> + <title>[Cryo Operator Action]</title> + <details>contact CRYO on-call and inform SCL on-call, Cryomodule liquid level too high (check the other gauge LT-002). Close supply valve CV01, CV02</details> + </guidance> + </pv> + <pv name="HBL-030Crm:Cryo-LT-002:HIHI"> + <description>LT-002 helium level extremely high</description> + <latching>true</latching> + <annunciating>true</annunciating> + <guidance> + <title>[Cryo Operator Action]</title> + <details>contact CRYO on-call and inform SCL on-call, Cryomodule liquid level too high (check the other gauge LT-001). Close supply valve CV01, CV02</details> + </guidance> + </pv> + <pv name="HBL-030Crm:Cryo-LT-001:HI"> + <description>LT-001 helium level high</description> + <latching>true</latching> + <annunciating>true</annunciating> + <guidance> + <title>[Cryo Operator Action]</title> + <details>contact CRYO on-call and inform SCL on-call, Cryomodule liquid level high (check the other gauge LT-002). Check level regulation valve settings, if needed: adjust LMN_LO and if necessary: Close supply valve CV01, CV02</details> + </guidance> + </pv> + <pv name="HBL-030Crm:Cryo-LT-002:HI"> + <description>LT-002 helium level high</description> + <latching>true</latching> + <annunciating>true</annunciating> + <guidance> + <title>[Cryo Operator Action]</title> + <details>contact CRYO on-call and inform SCL on-call, Cryomodule liquid level high (check the other gauge LT-002). Check level regulation valve settings, if needed: adjust LMN_LO and if necessary: Close supply valve CV01, CV02</details> + </guidance> + </pv> + <pv name="HBL-030Crm:Cryo-LT-001:LO"> + <description>LT-001 helium level low</description> + <latching>true</latching> + <annunciating>true</annunciating> + <guidance> + <title>[Cryo Operator Action]</title> + <details>contact CRYO on-call and inform SCL on-call, Cryomodule liquid level low (check the other gauge LT-001). Check level regulation valve settings, if needed: adjust LMN_HI</details> + </guidance> + </pv> + <pv name="HBL-030Crm:Cryo-LT-002:LO"> + <description>LT-002 helium level low</description> + <latching>true</latching> + <annunciating>true</annunciating> + <guidance> + <title>[Cryo Operator Action]</title> + <details>contact CRYO on-call and inform SCL on-call, Cryomodule liquid level low (check the other gauge LT-002). Check level regulation valvesettings, if needed: adjust LMN_HI</details> + </guidance> + </pv> + <pv name="HBL-030Crm:Cryo-LT-001:LOLO"> + <description>LT-002 helium level extremely low</description> + <latching>true</latching> + <annunciating>true</annunciating> + <guidance> + <title>[Cryo Operator Action]</title> + <details>contact CRYO on-call and inform SCL on-call, Cryomodule liquid level too low (check the other gauge LT-001). Check level regulation valve settings, if needed: adjust LMN_HI</details> + </guidance> + </pv> + <pv name="HBL-030Crm:Cryo-LT-002:LOLO"> + <description>LT-002 helium level extremely low</description> + <latching>true</latching> + <annunciating>true</annunciating> + <guidance> + <title>[Cryo Operator Action]</title> + <details>contact CRYO on-call and inform SCL on-call, Cryomodule liquid level too low (check the other gauge LT-002). Check level regulation valvesettings, if needed: adjust LMN_HI</details> + </guidance> + </pv> + <pv name="HBL-030Crm:Cryo-PT-003:HIHI"> + <description>Cavity tanks pressure is too high (typical value is 31mbar in 2K mode and 1050mbar in 4K mode)</description> + <latching>true</latching> + <annunciating>true</annunciating> + <guidance> + <title>[Cryo Operator Action]</title> + <details>contact CRYO on-call and inform SCL on-call, Cryomodule bath pressure too high (check the other gauge PT002). Close supply valve CV01, CV02 if necessary</details> + </guidance> + </pv> + <pv name="HBL-030Crm:Cryo-PT-003:Cable_Error"> + <description>Cavity tanks Pressure Sensor cables are disconnected</description> + <latching>true</latching> + <annunciating>true</annunciating> + <guidance> + <title>[Cryo Operator Action]</title> + <details>contact CRYO on-call and inform SCL on-call, Cryomodule pressure cable seems disconnected (value gets stuck), assign PT002 as measuring device on CV04 and CV-090 </details> + </guidance> + </pv> + <pv name="HBL-030Crm:Cryo-PT-004:HIHI"> + <description>Cavity tanks pressure is too high (typical value is 31mbar in 2K mode and 1050mbar in 4K mode)</description> + <latching>true</latching> + <annunciating>true</annunciating> + <guidance> + <title>[Cryo Operator Action]</title> + <details>contact CRYO on-call and inform SCL on-call,, Cryomodule bath pressure too high (check the other gauge PT003). Close supply valve CV01, CV02 if necessary</details> + </guidance> + </pv> + <pv name="HBL-030Crm:Cryo-PT-004:Cable_Error"> + <description>Cavity tanks Pressure Sensor cables are disconnected</description> + <latching>true</latching> + <annunciating>true</annunciating> + <guidance> + <title>[Cryo Operator Action]</title> + <details>contact CRYO on-call and inform SCL on-call, Cryomodule pressure cable seems disconnected (value gets stuck), assign PT003 as measuring device on CV04 and CV-090 </details> + </guidance> + </pv> + <pv name="HBL-030Crm:Cryo-TT-014:P_Limit_HIHI"> + <description>Power coupler flange temperature too high</description> + <latching>true</latching> + <annunciating>true</annunciating> + <guidance> + <title>[Cryo Operator Action]</title> + <details>contact CRYO on-call and inform SCL on-call, power coupler flange temperature is too high, check heater output, if nominal then coupler flow needs to be adjusted (increased)</details> + </guidance> + </pv> + <pv name="HBL-030Crm:Cryo-TT-014:P_Limit_LO"> + <description>Power coupler flange temperature too low</description> + <latching>true</latching> + <annunciating>true</annunciating> + <guidance> + <title>[Cryo Operator Action]</title> + <details>contact CRYO on-call and inform SCL on-call, power coupler flange temperature is too low, check heater output, if nominal then coupler flow needs to be adjusted (reduced)</details> + </guidance> + </pv> + <pv name="HBL-030Crm:Cryo-TT-014:P_Limit_LOLO"> + <description>Power coupler flange temperature too low</description> + <latching>true</latching> + <annunciating>true</annunciating> + <guidance> + <title>[Cryo Operator Action]</title> + <details>contact CRYO on-call and inform SCL on-call, power coupler flange temperature is too low, check heater output, if nominal then coupler flow needs to be adjusted (reduced)</details> + </guidance> + </pv> + <pv name="HBL-030Crm:Cryo-TT-024:P_Limit_HIHI"> + <description>Power coupler flange temperature low</description> + <latching>true</latching> + <annunciating>true</annunciating> + <guidance> + <title>[Cryo Operator Action]</title> + <details>contact CRYO on-call and inform SCL on-call, power coupler flange temperature is too high, check heater output, if nominal then coupler flow needs to be adjusted (increased)</details> + </guidance> + </pv> + <pv name="HBL-030Crm:Cryo-TT-024:P_Limit_LO"> + <description>Power coupler flange temperature too low</description> + <latching>true</latching> + <annunciating>true</annunciating> + <guidance> + <title>[Cryo Operator Action]</title> + <details>contact CRYO on-call and inform SCL on-call, power coupler flange temperature is too low, check heater output, if nominal then coupler flow needs to be adjusted (reduced)</details> + </guidance> + </pv> + <pv name="HBL-030Crm:Cryo-TT-024:P_Limit_LOLO"> + <description>Power coupler flange temperature too high</description> + <latching>true</latching> + <annunciating>true</annunciating> + <guidance> + <title>[Cryo Operator Action]</title> + <details>contact CRYO on-call and inform SCL on-call, power coupler flange temperature is too low, check heater output, if nominal then coupler flow needs to be adjusted (reduced)</details> + </guidance> + </pv> + <pv name="HBL-030Crm:Cryo-TT-034:P_Limit_HIHI"> + <description>Power coupler flange temperature low</description> + <latching>true</latching> + <annunciating>true</annunciating> + <guidance> + <title>[Cryo Operator Action]</title> + <details>contact CRYO on-call and inform SCL on-call, power coupler flange temperature is too high, check heater output, if nominal then coupler flow needs to be adjusted (increased)</details> + </guidance> + </pv> + <pv name="HBL-030Crm:Cryo-TT-034:P_Limit_LO"> + <description>Power coupler flange temperature too low</description> + <latching>true</latching> + <annunciating>true</annunciating> + <guidance> + <title>[Cryo Operator Action]</title> + <details>contact CRYO on-call and inform SCL on-call, power coupler flange temperature is too low, check heater output, if nominal then coupler flow needs to be adjusted (reduced)</details> + </guidance> + </pv> + <pv name="HBL-030Crm:Cryo-TT-034:P_Limit_LOLO"> + <description>Power coupler flange temperature too high</description> + <latching>true</latching> + <annunciating>true</annunciating> + <guidance> + <title>[Cryo Operator Action]</title> + <details>contact CRYO on-call and inform SCL on-call, power coupler flange temperature is too low, check heater output, if nominal then coupler flow needs to be adjusted (reduced)</details> + </guidance> + </pv> + <pv name="HBL-030Crm:Cryo-TT-044:P_Limit_HIHI"> + <description>Power coupler flange temperature low</description> + <latching>true</latching> + <annunciating>true</annunciating> + <guidance> + <title>[Cryo Operator Action]</title> + <details>contact CRYO on-call and inform SCL on-call, power coupler flange temperature is too high, check heater output, if nominal then coupler flow needs to be adjusted (increased)</details> + </guidance> + </pv> + <pv name="HBL-030Crm:Cryo-TT-044:P_Limit_LO"> + <description>Power coupler flange temperature too low</description> + <latching>true</latching> + <annunciating>true</annunciating> + <guidance> + <title>[Cryo Operator Action]</title> + <details>contact CRYO on-call and inform SCL on-call, power coupler flange temperature is too low, check heater output, if nominal then coupler flow needs to be adjusted (reduced)</details> + </guidance> + </pv> + <pv name="HBL-030Crm:Cryo-TT-043:P_Limit_LOLO"> + <description>Power coupler flange temperature too high</description> + <latching>true</latching> + <annunciating>true</annunciating> + <guidance> + <title>[Cryo Operator Action]</title> + <details>contact CRYO on-call and inform SCL on-call, power coupler flange temperature is too low, check heater output, if nominal then coupler flow needs to be adjusted (reduced)</details> + </guidance> + </pv> + <pv name="HBL-030Crm:WtrC-FS-012:Flow_OK_WF"> + <description>! Alarm when signal drops from 1 to zero. No Water Flow Antenna 1</description> + <latching>true</latching> + <annunciating>true</annunciating> + <guidance> + <title>[Cryo Operator Action]</title> + <details>contact CRYO on-call and inform SCL on-call, assure Flange temperature TT-014 is correct. Risk of Water freeze if no flow and temperature too low</details> + </guidance> + </pv> + <pv name="HBL-030Crm:WtrC-FS-022:Flow_OK_WF"> + <description>! Alarm when signal drops from 1 to zero. No Water Flow Antenna 2</description> + <latching>true</latching> + <annunciating>true</annunciating> + <guidance> + <title>[Cryo Operator Action]</title> + <details>contact CRYO on-call and inform SCL on-call, assure Flange temperature TT-024 is correct. Risk of Water freeze if no flow and temperature too low</details> + </guidance> + </pv> + <pv name="HBL-030Crm:WtrC-FS-032:Flow_OK_WF"> + <description>! Alarm when signal drops from 1 to zero. No Water Flow Antenna 3</description> + <latching>true</latching> + <annunciating>true</annunciating> + <guidance> + <title>[Cryo Operator Action]</title> + <details>contact CRYO on-call and inform SCL on-call, assure Flange temperature TT-034 is correct. Risk of Water freeze if no flow and temperature too low</details> + </guidance> + </pv> + <pv name="HBL-030Crm:WtrC-FS-042:Flow_OK_WF"> + <description>! Alarm when signal drops from 1 to zero. No Water Flow Antenna 4</description> + <latching>true</latching> + <annunciating>true</annunciating> + <guidance> + <title>[Cryo Operator Action]</title> + <details>contact CRYO on-call and inform SCL on-call, assure Flange temperature TT-044 is correct. Risk of Water freeze if no flow and temperature too low</details> + </guidance> + </pv> + </component> + <component name="Cryomodules\HBL-040 Cryomodule"> + <pv name="HBL-040Crm:Cryo-LT-001:HIHI"> + <description>LT-001 helium level extremely high</description> + <latching>true</latching> + <annunciating>true</annunciating> + <guidance> + <title>[Cryo Operator Action]</title> + <details>contact CRYO on-call and inform SCL on-call, Cryomodule liquid level too high (check the other gauge LT-002). Close supply valve CV01, CV02</details> + </guidance> + </pv> + <pv name="HBL-040Crm:Cryo-LT-002:HIHI"> + <description>LT-002 helium level extremely high</description> + <latching>true</latching> + <annunciating>true</annunciating> + <guidance> + <title>[Cryo Operator Action]</title> + <details>contact CRYO on-call and inform SCL on-call, Cryomodule liquid level too high (check the other gauge LT-001). Close supply valve CV01, CV02</details> + </guidance> + </pv> + <pv name="HBL-040Crm:Cryo-LT-001:HI"> + <description>LT-001 helium level high</description> + <latching>true</latching> + <annunciating>true</annunciating> + <guidance> + <title>[Cryo Operator Action]</title> + <details>contact CRYO on-call and inform SCL on-call, Cryomodule liquid level high (check the other gauge LT-002). Check level regulation valve settings, if needed: adjust LMN_LO and if necessary: Close supply valve CV01, CV02</details> + </guidance> + </pv> + <pv name="HBL-040Crm:Cryo-LT-002:HI"> + <description>LT-002 helium level high</description> + <latching>true</latching> + <annunciating>true</annunciating> + <guidance> + <title>[Cryo Operator Action]</title> + <details>contact CRYO on-call and inform SCL on-call, Cryomodule liquid level high (check the other gauge LT-002). Check level regulation valve settings, if needed: adjust LMN_LO and if necessary: Close supply valve CV01, CV02</details> + </guidance> + </pv> + <pv name="HBL-040Crm:Cryo-LT-001:LO"> + <description>LT-001 helium level low</description> + <latching>true</latching> + <annunciating>true</annunciating> + <guidance> + <title>[Cryo Operator Action]</title> + <details>contact CRYO on-call and inform SCL on-call, Cryomodule liquid level low (check the other gauge LT-001). Check level regulation valve settings, if needed: adjust LMN_HI</details> + </guidance> + </pv> + <pv name="HBL-040Crm:Cryo-LT-002:LO"> + <description>LT-002 helium level low</description> + <latching>true</latching> + <annunciating>true</annunciating> + <guidance> + <title>[Cryo Operator Action]</title> + <details>contact CRYO on-call and inform SCL on-call, Cryomodule liquid level low (check the other gauge LT-002). Check level regulation valvesettings, if needed: adjust LMN_HI</details> + </guidance> + </pv> + <pv name="HBL-040Crm:Cryo-LT-001:LOLO"> + <description>LT-002 helium level extremely low</description> + <latching>true</latching> + <annunciating>true</annunciating> + <guidance> + <title>[Cryo Operator Action]</title> + <details>contact CRYO on-call and inform SCL on-call, Cryomodule liquid level too low (check the other gauge LT-001). Check level regulation valve settings, if needed: adjust LMN_HI</details> + </guidance> + </pv> + <pv name="HBL-040Crm:Cryo-LT-002:LOLO"> + <description>LT-002 helium level extremely low</description> + <latching>true</latching> + <annunciating>true</annunciating> + <guidance> + <title>[Cryo Operator Action]</title> + <details>contact CRYO on-call and inform SCL on-call, Cryomodule liquid level too low (check the other gauge LT-002). Check level regulation valvesettings, if needed: adjust LMN_HI</details> + </guidance> + </pv> + <pv name="HBL-040Crm:Cryo-PT-003:HIHI"> + <description>Cavity tanks pressure is too high (typical value is 31mbar in 2K mode and 1050mbar in 4K mode)</description> + <latching>true</latching> + <annunciating>true</annunciating> + <guidance> + <title>[Cryo Operator Action]</title> + <details>contact CRYO on-call and inform SCL on-call, Cryomodule bath pressure too high (check the other gauge PT002). Close supply valve CV01, CV02 if necessary</details> + </guidance> + </pv> + <pv name="HBL-040Crm:Cryo-PT-003:Cable_Error"> + <description>Cavity tanks Pressure Sensor cables are disconnected</description> + <latching>true</latching> + <annunciating>true</annunciating> + <guidance> + <title>[Cryo Operator Action]</title> + <details>contact CRYO on-call and inform SCL on-call, Cryomodule pressure cable seems disconnected (value gets stuck), assign PT002 as measuring device on CV04 and CV-090 </details> + </guidance> + </pv> + <pv name="HBL-040Crm:Cryo-PT-004:HIHI"> + <description>Cavity tanks pressure is too high (typical value is 31mbar in 2K mode and 1050mbar in 4K mode)</description> + <latching>true</latching> + <annunciating>true</annunciating> + <guidance> + <title>[Cryo Operator Action]</title> + <details>contact CRYO on-call and inform SCL on-call,, Cryomodule bath pressure too high (check the other gauge PT003). Close supply valve CV01, CV02 if necessary</details> + </guidance> + </pv> + <pv name="HBL-040Crm:Cryo-PT-004:Cable_Error"> + <description>Cavity tanks Pressure Sensor cables are disconnected</description> + <latching>true</latching> + <annunciating>true</annunciating> + <guidance> + <title>[Cryo Operator Action]</title> + <details>contact CRYO on-call and inform SCL on-call, Cryomodule pressure cable seems disconnected (value gets stuck), assign PT003 as measuring device on CV04 and CV-090 </details> + </guidance> + </pv> + <pv name="HBL-040Crm:Cryo-TT-014:P_Limit_HIHI"> + <description>Power coupler flange temperature too high</description> + <latching>true</latching> + <annunciating>true</annunciating> + <guidance> + <title>[Cryo Operator Action]</title> + <details>contact CRYO on-call and inform SCL on-call, power coupler flange temperature is too high, check heater output, if nominal then coupler flow needs to be adjusted (increased)</details> + </guidance> + </pv> + <pv name="HBL-040Crm:Cryo-TT-014:P_Limit_LO"> + <description>Power coupler flange temperature too low</description> + <latching>true</latching> + <annunciating>true</annunciating> + <guidance> + <title>[Cryo Operator Action]</title> + <details>contact CRYO on-call and inform SCL on-call, power coupler flange temperature is too low, check heater output, if nominal then coupler flow needs to be adjusted (reduced)</details> + </guidance> + </pv> + <pv name="HBL-040Crm:Cryo-TT-014:P_Limit_LOLO"> + <description>Power coupler flange temperature too low</description> + <latching>true</latching> + <annunciating>true</annunciating> + <guidance> + <title>[Cryo Operator Action]</title> + <details>contact CRYO on-call and inform SCL on-call, power coupler flange temperature is too low, check heater output, if nominal then coupler flow needs to be adjusted (reduced)</details> + </guidance> + </pv> + <pv name="HBL-040Crm:Cryo-TT-024:P_Limit_HIHI"> + <description>Power coupler flange temperature low</description> + <latching>true</latching> + <annunciating>true</annunciating> + <guidance> + <title>[Cryo Operator Action]</title> + <details>contact CRYO on-call and inform SCL on-call, power coupler flange temperature is too high, check heater output, if nominal then coupler flow needs to be adjusted (increased)</details> + </guidance> + </pv> + <pv name="HBL-040Crm:Cryo-TT-024:P_Limit_LO"> + <description>Power coupler flange temperature too low</description> + <latching>true</latching> + <annunciating>true</annunciating> + <guidance> + <title>[Cryo Operator Action]</title> + <details>contact CRYO on-call and inform SCL on-call, power coupler flange temperature is too low, check heater output, if nominal then coupler flow needs to be adjusted (reduced)</details> + </guidance> + </pv> + <pv name="HBL-040Crm:Cryo-TT-024:P_Limit_LOLO"> + <description>Power coupler flange temperature too high</description> + <latching>true</latching> + <annunciating>true</annunciating> + <guidance> + <title>[Cryo Operator Action]</title> + <details>contact CRYO on-call and inform SCL on-call, power coupler flange temperature is too low, check heater output, if nominal then coupler flow needs to be adjusted (reduced)</details> + </guidance> + </pv> + <pv name="HBL-040Crm:Cryo-TT-034:P_Limit_HIHI"> + <description>Power coupler flange temperature low</description> + <latching>true</latching> + <annunciating>true</annunciating> + <guidance> + <title>[Cryo Operator Action]</title> + <details>contact CRYO on-call and inform SCL on-call, power coupler flange temperature is too high, check heater output, if nominal then coupler flow needs to be adjusted (increased)</details> + </guidance> + </pv> + <pv name="HBL-040Crm:Cryo-TT-034:P_Limit_LO"> + <description>Power coupler flange temperature too low</description> + <latching>true</latching> + <annunciating>true</annunciating> + <guidance> + <title>[Cryo Operator Action]</title> + <details>contact CRYO on-call and inform SCL on-call, power coupler flange temperature is too low, check heater output, if nominal then coupler flow needs to be adjusted (reduced)</details> + </guidance> + </pv> + <pv name="HBL-040Crm:Cryo-TT-034:P_Limit_LOLO"> + <description>Power coupler flange temperature too high</description> + <latching>true</latching> + <annunciating>true</annunciating> + <guidance> + <title>[Cryo Operator Action]</title> + <details>contact CRYO on-call and inform SCL on-call, power coupler flange temperature is too low, check heater output, if nominal then coupler flow needs to be adjusted (reduced)</details> + </guidance> + </pv> + <pv name="HBL-040Crm:Cryo-TT-044:P_Limit_HIHI"> + <description>Power coupler flange temperature low</description> + <latching>true</latching> + <annunciating>true</annunciating> + <guidance> + <title>[Cryo Operator Action]</title> + <details>contact CRYO on-call and inform SCL on-call, power coupler flange temperature is too high, check heater output, if nominal then coupler flow needs to be adjusted (increased)</details> + </guidance> + </pv> + <pv name="HBL-040Crm:Cryo-TT-044:P_Limit_LO"> + <description>Power coupler flange temperature too low</description> + <latching>true</latching> + <annunciating>true</annunciating> + <guidance> + <title>[Cryo Operator Action]</title> + <details>contact CRYO on-call and inform SCL on-call, power coupler flange temperature is too low, check heater output, if nominal then coupler flow needs to be adjusted (reduced)</details> + </guidance> + </pv> + <pv name="HBL-040Crm:Cryo-TT-043:P_Limit_LOLO"> + <description>Power coupler flange temperature too high</description> + <latching>true</latching> + <annunciating>true</annunciating> + <guidance> + <title>[Cryo Operator Action]</title> + <details>contact CRYO on-call and inform SCL on-call, power coupler flange temperature is too low, check heater output, if nominal then coupler flow needs to be adjusted (reduced)</details> + </guidance> + </pv> + <pv name="HBL-040Crm:WtrC-FS-012:Flow_OK_WF"> + <description>! Alarm when signal drops from 1 to zero. No Water Flow Antenna 1</description> + <latching>true</latching> + <annunciating>true</annunciating> + <guidance> + <title>[Cryo Operator Action]</title> + <details>contact CRYO on-call and inform SCL on-call, assure Flange temperature TT-014 is correct. Risk of Water freeze if no flow and temperature too low</details> + </guidance> + </pv> + <pv name="HBL-040Crm:WtrC-FS-022:Flow_OK_WF"> + <description>! Alarm when signal drops from 1 to zero. No Water Flow Antenna 2</description> + <latching>true</latching> + <annunciating>true</annunciating> + <guidance> + <title>[Cryo Operator Action]</title> + <details>contact CRYO on-call and inform SCL on-call, assure Flange temperature TT-024 is correct. Risk of Water freeze if no flow and temperature too low</details> + </guidance> + </pv> + <pv name="HBL-040Crm:WtrC-FS-032:Flow_OK_WF"> + <description>! Alarm when signal drops from 1 to zero. No Water Flow Antenna 3</description> + <latching>true</latching> + <annunciating>true</annunciating> + <guidance> + <title>[Cryo Operator Action]</title> + <details>contact CRYO on-call and inform SCL on-call, assure Flange temperature TT-034 is correct. Risk of Water freeze if no flow and temperature too low</details> + </guidance> + </pv> + <pv name="HBL-040Crm:WtrC-FS-042:Flow_OK_WF"> + <description>! Alarm when signal drops from 1 to zero. No Water Flow Antenna 4</description> + <latching>true</latching> + <annunciating>true</annunciating> + <guidance> + <title>[Cryo Operator Action]</title> + <details>contact CRYO on-call and inform SCL on-call, assure Flange temperature TT-044 is correct. Risk of Water freeze if no flow and temperature too low</details> + </guidance> + </pv> + </component> + <component name="Cryomodules\HBL-050 Cryomodule"> + <pv name="HBL-050Crm:Cryo-LT-001:HIHI"> + <description>LT-001 helium level extremely high</description> + <latching>true</latching> + <annunciating>true</annunciating> + <guidance> + <title>[Cryo Operator Action]</title> + <details>contact CRYO on-call and inform SCL on-call, Cryomodule liquid level too high (check the other gauge LT-002). Close supply valve CV01, CV02</details> + </guidance> + </pv> + <pv name="HBL-050Crm:Cryo-LT-002:HIHI"> + <description>LT-002 helium level extremely high</description> + <latching>true</latching> + <annunciating>true</annunciating> + <guidance> + <title>[Cryo Operator Action]</title> + <details>contact CRYO on-call and inform SCL on-call, Cryomodule liquid level too high (check the other gauge LT-001). Close supply valve CV01, CV02</details> + </guidance> + </pv> + <pv name="HBL-050Crm:Cryo-LT-001:HI"> + <description>LT-001 helium level high</description> + <latching>true</latching> + <annunciating>true</annunciating> + <guidance> + <title>[Cryo Operator Action]</title> + <details>contact CRYO on-call and inform SCL on-call, Cryomodule liquid level high (check the other gauge LT-002). Check level regulation valve settings, if needed: adjust LMN_LO and if necessary: Close supply valve CV01, CV02</details> + </guidance> + </pv> + <pv name="HBL-050Crm:Cryo-LT-002:HI"> + <description>LT-002 helium level high</description> + <latching>true</latching> + <annunciating>true</annunciating> + <guidance> + <title>[Cryo Operator Action]</title> + <details>contact CRYO on-call and inform SCL on-call, Cryomodule liquid level high (check the other gauge LT-002). Check level regulation valve settings, if needed: adjust LMN_LO and if necessary: Close supply valve CV01, CV02</details> + </guidance> + </pv> + <pv name="HBL-050Crm:Cryo-LT-001:LO"> + <description>LT-001 helium level low</description> + <latching>true</latching> + <annunciating>true</annunciating> + <guidance> + <title>[Cryo Operator Action]</title> + <details>contact CRYO on-call and inform SCL on-call, Cryomodule liquid level low (check the other gauge LT-001). Check level regulation valve settings, if needed: adjust LMN_HI</details> + </guidance> + </pv> + <pv name="HBL-050Crm:Cryo-LT-002:LO"> + <description>LT-002 helium level low</description> + <latching>true</latching> + <annunciating>true</annunciating> + <guidance> + <title>[Cryo Operator Action]</title> + <details>contact CRYO on-call and inform SCL on-call, Cryomodule liquid level low (check the other gauge LT-002). Check level regulation valvesettings, if needed: adjust LMN_HI</details> + </guidance> + </pv> + <pv name="HBL-050Crm:Cryo-LT-001:LOLO"> + <description>LT-002 helium level extremely low</description> + <latching>true</latching> + <annunciating>true</annunciating> + <guidance> + <title>[Cryo Operator Action]</title> + <details>contact CRYO on-call and inform SCL on-call, Cryomodule liquid level too low (check the other gauge LT-001). Check level regulation valve settings, if needed: adjust LMN_HI</details> + </guidance> + </pv> + <pv name="HBL-050Crm:Cryo-LT-002:LOLO"> + <description>LT-002 helium level extremely low</description> + <latching>true</latching> + <annunciating>true</annunciating> + <guidance> + <title>[Cryo Operator Action]</title> + <details>contact CRYO on-call and inform SCL on-call, Cryomodule liquid level too low (check the other gauge LT-002). Check level regulation valvesettings, if needed: adjust LMN_HI</details> + </guidance> + </pv> + <pv name="HBL-050Crm:Cryo-PT-003:HIHI"> + <description>Cavity tanks pressure is too high (typical value is 31mbar in 2K mode and 1050mbar in 4K mode)</description> + <latching>true</latching> + <annunciating>true</annunciating> + <guidance> + <title>[Cryo Operator Action]</title> + <details>contact CRYO on-call and inform SCL on-call, Cryomodule bath pressure too high (check the other gauge PT002). Close supply valve CV01, CV02 if necessary</details> + </guidance> + </pv> + <pv name="HBL-050Crm:Cryo-PT-003:Cable_Error"> + <description>Cavity tanks Pressure Sensor cables are disconnected</description> + <latching>true</latching> + <annunciating>true</annunciating> + <guidance> + <title>[Cryo Operator Action]</title> + <details>contact CRYO on-call and inform SCL on-call, Cryomodule pressure cable seems disconnected (value gets stuck), assign PT002 as measuring device on CV04 and CV-090 </details> + </guidance> + </pv> + <pv name="HBL-050Crm:Cryo-PT-004:HIHI"> + <description>Cavity tanks pressure is too high (typical value is 31mbar in 2K mode and 1050mbar in 4K mode)</description> + <latching>true</latching> + <annunciating>true</annunciating> + <guidance> + <title>[Cryo Operator Action]</title> + <details>contact CRYO on-call and inform SCL on-call,, Cryomodule bath pressure too high (check the other gauge PT003). Close supply valve CV01, CV02 if necessary</details> + </guidance> + </pv> + <pv name="HBL-050Crm:Cryo-PT-004:Cable_Error"> + <description>Cavity tanks Pressure Sensor cables are disconnected</description> + <latching>true</latching> + <annunciating>true</annunciating> + <guidance> + <title>[Cryo Operator Action]</title> + <details>contact CRYO on-call and inform SCL on-call, Cryomodule pressure cable seems disconnected (value gets stuck), assign PT003 as measuring device on CV04 and CV-090 </details> + </guidance> + </pv> + <pv name="HBL-050Crm:Cryo-TT-014:P_Limit_HIHI"> + <description>Power coupler flange temperature too high</description> + <latching>true</latching> + <annunciating>true</annunciating> + <guidance> + <title>[Cryo Operator Action]</title> + <details>contact CRYO on-call and inform SCL on-call, power coupler flange temperature is too high, check heater output, if nominal then coupler flow needs to be adjusted (increased)</details> + </guidance> + </pv> + <pv name="HBL-050Crm:Cryo-TT-014:P_Limit_LO"> + <description>Power coupler flange temperature too low</description> + <latching>true</latching> + <annunciating>true</annunciating> + <guidance> + <title>[Cryo Operator Action]</title> + <details>contact CRYO on-call and inform SCL on-call, power coupler flange temperature is too low, check heater output, if nominal then coupler flow needs to be adjusted (reduced)</details> + </guidance> + </pv> + <pv name="HBL-050Crm:Cryo-TT-014:P_Limit_LOLO"> + <description>Power coupler flange temperature too low</description> + <latching>true</latching> + <annunciating>true</annunciating> + <guidance> + <title>[Cryo Operator Action]</title> + <details>contact CRYO on-call and inform SCL on-call, power coupler flange temperature is too low, check heater output, if nominal then coupler flow needs to be adjusted (reduced)</details> + </guidance> + </pv> + <pv name="HBL-050Crm:Cryo-TT-024:P_Limit_HIHI"> + <description>Power coupler flange temperature low</description> + <latching>true</latching> + <annunciating>true</annunciating> + <guidance> + <title>[Cryo Operator Action]</title> + <details>contact CRYO on-call and inform SCL on-call, power coupler flange temperature is too high, check heater output, if nominal then coupler flow needs to be adjusted (increased)</details> + </guidance> + </pv> + <pv name="HBL-050Crm:Cryo-TT-024:P_Limit_LO"> + <description>Power coupler flange temperature too low</description> + <latching>true</latching> + <annunciating>true</annunciating> + <guidance> + <title>[Cryo Operator Action]</title> + <details>contact CRYO on-call and inform SCL on-call, power coupler flange temperature is too low, check heater output, if nominal then coupler flow needs to be adjusted (reduced)</details> + </guidance> + </pv> + <pv name="HBL-050Crm:Cryo-TT-024:P_Limit_LOLO"> + <description>Power coupler flange temperature too high</description> + <latching>true</latching> + <annunciating>true</annunciating> + <guidance> + <title>[Cryo Operator Action]</title> + <details>contact CRYO on-call and inform SCL on-call, power coupler flange temperature is too low, check heater output, if nominal then coupler flow needs to be adjusted (reduced)</details> + </guidance> + </pv> + <pv name="HBL-050Crm:Cryo-TT-034:P_Limit_HIHI"> + <description>Power coupler flange temperature low</description> + <latching>true</latching> + <annunciating>true</annunciating> + <guidance> + <title>[Cryo Operator Action]</title> + <details>contact CRYO on-call and inform SCL on-call, power coupler flange temperature is too high, check heater output, if nominal then coupler flow needs to be adjusted (increased)</details> + </guidance> + </pv> + <pv name="HBL-050Crm:Cryo-TT-034:P_Limit_LO"> + <description>Power coupler flange temperature too low</description> + <latching>true</latching> + <annunciating>true</annunciating> + <guidance> + <title>[Cryo Operator Action]</title> + <details>contact CRYO on-call and inform SCL on-call, power coupler flange temperature is too low, check heater output, if nominal then coupler flow needs to be adjusted (reduced)</details> + </guidance> + </pv> + <pv name="HBL-050Crm:Cryo-TT-034:P_Limit_LOLO"> + <description>Power coupler flange temperature too high</description> + <latching>true</latching> + <annunciating>true</annunciating> + <guidance> + <title>[Cryo Operator Action]</title> + <details>contact CRYO on-call and inform SCL on-call, power coupler flange temperature is too low, check heater output, if nominal then coupler flow needs to be adjusted (reduced)</details> + </guidance> + </pv> + <pv name="HBL-050Crm:Cryo-TT-044:P_Limit_HIHI"> + <description>Power coupler flange temperature low</description> + <latching>true</latching> + <annunciating>true</annunciating> + <guidance> + <title>[Cryo Operator Action]</title> + <details>contact CRYO on-call and inform SCL on-call, power coupler flange temperature is too high, check heater output, if nominal then coupler flow needs to be adjusted (increased)</details> + </guidance> + </pv> + <pv name="HBL-050Crm:Cryo-TT-044:P_Limit_LO"> + <description>Power coupler flange temperature too low</description> + <latching>true</latching> + <annunciating>true</annunciating> + <guidance> + <title>[Cryo Operator Action]</title> + <details>contact CRYO on-call and inform SCL on-call, power coupler flange temperature is too low, check heater output, if nominal then coupler flow needs to be adjusted (reduced)</details> + </guidance> + </pv> + <pv name="HBL-050Crm:Cryo-TT-043:P_Limit_LOLO"> + <description>Power coupler flange temperature too high</description> + <latching>true</latching> + <annunciating>true</annunciating> + <guidance> + <title>[Cryo Operator Action]</title> + <details>contact CRYO on-call and inform SCL on-call, power coupler flange temperature is too low, check heater output, if nominal then coupler flow needs to be adjusted (reduced)</details> + </guidance> + </pv> + <pv name="HBL-050Crm:WtrC-FS-012:Flow_OK_WF"> + <description>! Alarm when signal drops from 1 to zero. No Water Flow Antenna 1</description> + <latching>true</latching> + <annunciating>true</annunciating> + <guidance> + <title>[Cryo Operator Action]</title> + <details>contact CRYO on-call and inform SCL on-call, assure Flange temperature TT-014 is correct. Risk of Water freeze if no flow and temperature too low</details> + </guidance> + </pv> + <pv name="HBL-050Crm:WtrC-FS-022:Flow_OK_WF"> + <description>! Alarm when signal drops from 1 to zero. No Water Flow Antenna 2</description> + <latching>true</latching> + <annunciating>true</annunciating> + <guidance> + <title>[Cryo Operator Action]</title> + <details>contact CRYO on-call and inform SCL on-call, assure Flange temperature TT-024 is correct. Risk of Water freeze if no flow and temperature too low</details> + </guidance> + </pv> + <pv name="HBL-050Crm:WtrC-FS-032:Flow_OK_WF"> + <description>! Alarm when signal drops from 1 to zero. No Water Flow Antenna 3</description> + <latching>true</latching> + <annunciating>true</annunciating> + <guidance> + <title>[Cryo Operator Action]</title> + <details>contact CRYO on-call and inform SCL on-call, assure Flange temperature TT-034 is correct. Risk of Water freeze if no flow and temperature too low</details> + </guidance> + </pv> + <pv name="HBL-050Crm:WtrC-FS-042:Flow_OK_WF"> + <description>! Alarm when signal drops from 1 to zero. No Water Flow Antenna 4</description> + <latching>true</latching> + <annunciating>true</annunciating> + <guidance> + <title>[Cryo Operator Action]</title> + <details>contact CRYO on-call and inform SCL on-call, assure Flange temperature TT-044 is correct. Risk of Water freeze if no flow and temperature too low</details> + </guidance> + </pv> + </component> + </component> </config> \ No newline at end of file