diff --git a/alarm-01.tn.esss.lu.se/ODH.xml b/alarm-01.tn.esss.lu.se/ODH.xml index 203d783d0da1a7b79b976012fe1eb02fc2dd63f8..eb99e9dbe2c08c7b97a7d60cb774097eda8845ab 100644 --- a/alarm-01.tn.esss.lu.se/ODH.xml +++ b/alarm-01.tn.esss.lu.se/ODH.xml @@ -1,20 +1,20 @@ <?xml version='1.0' encoding='UTF-8'?> <!-- Alarm configuration generated by AlarmFactory using the following arguments (please remove the spaces between the hyphens): - - -merge-xmls - -config ODH ACC.xml CRYOB.xml + - -merge-xmls - -config ODH ACC.xml CRYOB.xml TSGDS.xml Repository: https://gitlab.esss.lu.se/icshwi/plcfactory.git Branch: master Commit: a33cfba4ed6dab6f40f8199c103138c40e4b2777 - Date: 2024.09.10. 09:03:29 + Date: 2024.10.22. 21:26:05 --> <config name="ODH"> <component name="DIAG"> <component name="ACC"> <pv name="Spk-070Row:CnPw-U-015:CabHealthy"> <description>Device error in the RIO1 cabinet</description> - <latching>true</latching> - <annunciating>true</annunciating> + <latching>false</latching> + <annunciating>false</annunciating> <guidance> <title>[Operator Action]</title> <details>Hardware error detected in the RIO1 cabinet. Inform PSS team.</details> @@ -22,8 +22,8 @@ </pv> <pv name="HBL-070Row:CnPw-U-018:CabHealthy"> <description>Device error in the RIO2 cabinet</description> - <latching>true</latching> - <annunciating>true</annunciating> + <latching>false</latching> + <annunciating>false</annunciating> <guidance> <title>[Operator Action]</title> <details>Hardware error detected in the RIO2 cabinet. Inform PSS team.</details> @@ -31,8 +31,8 @@ </pv> <pv name="HBL-150Row:CnPw-U-017:CabHealthy"> <description>Device error in the RIO3 cabinet</description> - <latching>true</latching> - <annunciating>true</annunciating> + <latching>false</latching> + <annunciating>false</annunciating> <guidance> <title>[Operator Action]</title> <details>Hardware error detected in the RIO3 cabinet. Inform PSS team.</details> @@ -41,7 +41,7 @@ <pv name="AccODH-AT:Ctrl-CPU-001:FGCPU_CommStatus_Ok"> <description>Connection between Safety PLC and gateway PLC has been lost</description> <latching>true</latching> - <annunciating>false</annunciating> + <annunciating>true</annunciating> <guidance> <title>[Operator Action]</title> <details>Connection between Safety PLC and gateway PLC has been lost. Inform PSS team.</details> @@ -50,7 +50,7 @@ <pv name="AccODH-AT:Ctrl-GCPU-001:AliveR"> <description>Connection between gateway PLC and IOC has been lost</description> <latching>true</latching> - <annunciating>false</annunciating> + <annunciating>true</annunciating> <guidance> <title>[Operator Action]</title> <details>Connection between gateway PLC and IOC has been lost. Inform PSS team.</details> @@ -78,7 +78,7 @@ <component name="CRYOB"> <pv name="HCB-ACH:ODH-RIO-1:CabHealthy"> <description>Device error in the RIO1 cabinet</description> - <latching>true</latching> + <latching>false</latching> <annunciating>false</annunciating> <guidance> <title>[Operator Action]</title> @@ -87,7 +87,7 @@ </pv> <pv name="CXB-CXH:ODH-RIO-2:CabHealthy"> <description>Device error in the RIO2 cabinet</description> - <latching>true</latching> + <latching>false</latching> <annunciating>false</annunciating> <guidance> <title>[Operator Action]</title> @@ -131,11 +131,85 @@ </guidance> </pv> </component> + <component name="TS"> + <pv name="TgtGDS:CnPw-U-001:CabHealthy"> + <description>Device error in the PLC cabinet</description> + <latching>true</latching> + <annunciating>false</annunciating> + <guidance> + <title>[Operator Action]</title> + <details>Hardware error detected in the PLC cabinet. Inform PSS team.</details> + </guidance> + </pv> + <pv name="TgtGDS:CnPw-U-002:CabHealthy"> + <description>Device error in the RIO1 cabinet</description> + <latching>false</latching> + <annunciating>false</annunciating> + <guidance> + <title>[Operator Action]</title> + <details>Hardware error detected in the RIO1 cabinet. Inform PSS team.</details> + </guidance> + </pv> + <pv name="TgtGDS:CnPw-U-003:CabHealthy"> + <description>Device error in the RIO2 cabinet</description> + <latching>false</latching> + <annunciating>false</annunciating> + <guidance> + <title>[Operator Action]</title> + <details>Hardware error detected in the RIO2 cabinet. Inform PSS team.</details> + </guidance> + </pv> + <pv name="TgtGDS:Ctrl-CPU-001:FGCPU_CommStatus_Ok"> + <description>Connection between Safety PLC and gateway PLC has been lost</description> + <latching>false</latching> + <annunciating>false</annunciating> + <guidance> + <title>[Operator Action]</title> + <details>Connection between Safety PLC and gateway PLC has been lost. Inform PSS team.</details> + </guidance> + </pv> + <pv name="TgtGDS:Ctrl-GCPU-001:AliveR"> + <description>Connection between gateway PLC and IOC has been lost</description> + <latching>false</latching> + <annunciating>false</annunciating> + <guidance> + <title>[Operator Action]</title> + <details>Connection between gateway PLC and IOC has been lost. Inform PSS team.</details> + </guidance> + </pv> + <pv name="TgtGDS:Ctrl-CPU-001:ChecksumStd_check"> + <description>Safety PLC standard software checksum mismatch</description> + <latching>false</latching> + <annunciating>false</annunciating> + <guidance> + <title>[Operator Action]</title> + <details>Safety PLC standard software checksum mismatch. Inform PSS team.</details> + </guidance> + </pv> + <pv name="TgtGDS:Ctrl-CPU-001:ChecksumFS_check"> + <description>Safety PLC F-software checksum mismatch</description> + <latching>false</latching> + <annunciating>false</annunciating> + <guidance> + <title>[Operator Action]</title> + <details>Safety PLC F-software checksum mismatch. Inform PSS team.</details> + </guidance> + </pv> + <pv name="TgtGDS:Ctrl-GCPU-001:ChecksumGW_check"> + <description>Gateway PLC standard software checksum mismatch</description> + <latching>false</latching> + <annunciating>false</annunciating> + <guidance> + <title>[Operator Action]</title> + <details>Gateway PLC standard software checksum mismatch. Inform PSS team.</details> + </guidance> + </pv> + </component> </component> <component name="ACC"> <pv name="AccODH-AT:ODH-Area-001:Alrm"> <description>Zone ODH Alarm (Oxygen below 18%)</description> - <latching>true</latching> + <latching>false</latching> <annunciating>true</annunciating> <guidance> <title>[Operator Action]</title> @@ -148,7 +222,7 @@ Call cryo on call </pv> <pv name="AccODH-AT:ODH-Area-001:Warning"> <description>Zone ODH Warning (Oxygen below 19.5%)</description> - <latching>true</latching> + <latching>false</latching> <annunciating>true</annunciating> <guidance> <title>[Operator Action]</title> @@ -161,7 +235,7 @@ Call cryo on call </pv> <pv name="AccODH-AT:ODH-Area-001:Error"> <description>Zone oxygen monitor error</description> - <latching>true</latching> + <latching>false</latching> <annunciating>true</annunciating> <guidance> <title>[Operator Action]</title> @@ -200,8 +274,8 @@ Call cryo on call </pv> <pv name="AccODH-AT:ODH-Area-001:BatteryLow"> <description>Zone UPS battery low alarm while buffering</description> - <latching>true</latching> - <annunciating>true</annunciating> + <latching>false</latching> + <annunciating>false</annunciating> <guidance> <title>[Operator Action]</title> <details>Accelerator tunnel ODH evacuation alarm due to low battery alarm @@ -252,8 +326,8 @@ Call cryo on call <component name="ACS"> <pv name="AccODH-AT:ODH-ACS-001:Failure"> <description>Device failure</description> - <latching>true</latching> - <annunciating>true</annunciating> + <latching>false</latching> + <annunciating>false</annunciating> <guidance> <title>[Operator Action]</title> <details>AccODH-AT:ODH-ACS-001 in NCL section of the accelerator tunnel failure @@ -262,8 +336,8 @@ Call cryo on call </pv> <pv name="AccODH-AT:ODH-ACS-002:Failure"> <description>Device failure</description> - <latching>true</latching> - <annunciating>true</annunciating> + <latching>false</latching> + <annunciating>false</annunciating> <guidance> <title>[Operator Action]</title> <details>AccODH-AT:ODH-ACS-002 in NCL section of the accelerator tunnel failure @@ -272,8 +346,8 @@ Call cryo on call </pv> <pv name="AccODH-AT:ODH-ACS-003:Failure"> <description>Device failure</description> - <latching>true</latching> - <annunciating>true</annunciating> + <latching>false</latching> + <annunciating>false</annunciating> <guidance> <title>[Operator Action]</title> <details>AccODH-AT:ODH-ACS-003 in NCL section of the accelerator tunnel failure @@ -282,8 +356,8 @@ Call cryo on call </pv> <pv name="AccODH-AT:ODH-ACS-004:Failure"> <description>Device failure</description> - <latching>true</latching> - <annunciating>true</annunciating> + <latching>false</latching> + <annunciating>false</annunciating> <guidance> <title>[Operator Action]</title> <details>AccODH-AT:ODH-ACS-004 in NCL section of the accelerator tunnel failure @@ -292,8 +366,8 @@ Call cryo on call </pv> <pv name="AccODH-AT:ODH-ACS-005:Failure"> <description>Device failure</description> - <latching>true</latching> - <annunciating>true</annunciating> + <latching>false</latching> + <annunciating>false</annunciating> <guidance> <title>[Operator Action]</title> <details>AccODH-AT:ODH-ACS-005 in NCL section of the accelerator tunnel failure @@ -302,8 +376,8 @@ Call cryo on call </pv> <pv name="AccODH-AT:ODH-ACS-006:Failure"> <description>Device failure</description> - <latching>true</latching> - <annunciating>true</annunciating> + <latching>false</latching> + <annunciating>false</annunciating> <guidance> <title>[Operator Action]</title> <details>AccODH-AT:ODH-ACS-006 in SPK section of the accelerator tunnel failure @@ -312,8 +386,8 @@ Call cryo on call </pv> <pv name="AccODH-AT:ODH-ACS-007:Failure"> <description>Device failure</description> - <latching>true</latching> - <annunciating>true</annunciating> + <latching>false</latching> + <annunciating>false</annunciating> <guidance> <title>[Operator Action]</title> <details>AccODH-AT:ODH-ACS-007 in SPK section of the accelerator tunnel failure @@ -322,8 +396,8 @@ Call cryo on call </pv> <pv name="AccODH-AT:ODH-ACS-008:Failure"> <description>Device failure</description> - <latching>true</latching> - <annunciating>true</annunciating> + <latching>false</latching> + <annunciating>false</annunciating> <guidance> <title>[Operator Action]</title> <details>AccODH-AT:ODH-ACS-008 in MBL section of the accelerator tunnel failure @@ -332,8 +406,8 @@ Call cryo on call </pv> <pv name="AccODH-AT:ODH-ACS-009:Failure"> <description>Device failure</description> - <latching>true</latching> - <annunciating>true</annunciating> + <latching>false</latching> + <annunciating>false</annunciating> <guidance> <title>[Operator Action]</title> <details>AccODH-AT:ODH-ACS-009 in EEx1 section of the accelerator tunnel failure @@ -342,8 +416,8 @@ Call cryo on call </pv> <pv name="AccODH-AT:ODH-ACS-010:Failure"> <description>Device failure</description> - <latching>true</latching> - <annunciating>true</annunciating> + <latching>false</latching> + <annunciating>false</annunciating> <guidance> <title>[Operator Action]</title> <details>AccODH-AT:ODH-ACS-010 in EEx1 section of the accelerator tunnel failure @@ -352,8 +426,8 @@ Call cryo on call </pv> <pv name="AccODH-AT:ODH-ACS-011:Failure"> <description>Device failure</description> - <latching>true</latching> - <annunciating>true</annunciating> + <latching>false</latching> + <annunciating>false</annunciating> <guidance> <title>[Operator Action]</title> <details>AccODH-AT:ODH-ACS-011 in MBL section of the accelerator tunnel failure @@ -362,8 +436,8 @@ Call cryo on call </pv> <pv name="AccODH-AT:ODH-ACS-012:Failure"> <description>Device failure</description> - <latching>true</latching> - <annunciating>true</annunciating> + <latching>false</latching> + <annunciating>false</annunciating> <guidance> <title>[Operator Action]</title> <details>AccODH-AT:ODH-ACS-012 in MBL section of the accelerator tunnel failure @@ -372,8 +446,8 @@ Call cryo on call </pv> <pv name="AccODH-AT:ODH-ACS-013:Failure"> <description>Device failure</description> - <latching>true</latching> - <annunciating>true</annunciating> + <latching>false</latching> + <annunciating>false</annunciating> <guidance> <title>[Operator Action]</title> <details>AccODH-AT:ODH-ACS-013 in HBL section of the accelerator tunnel failure @@ -382,8 +456,8 @@ Call cryo on call </pv> <pv name="AccODH-AT:ODH-ACS-014:Failure"> <description>Device failure</description> - <latching>true</latching> - <annunciating>true</annunciating> + <latching>false</latching> + <annunciating>false</annunciating> <guidance> <title>[Operator Action]</title> <details>AccODH-AT:ODH-ACS-014 in HBL section of the accelerator tunnel failure @@ -392,8 +466,8 @@ Call cryo on call </pv> <pv name="AccODH-AT:ODH-ACS-015:Failure"> <description>Device failure</description> - <latching>true</latching> - <annunciating>true</annunciating> + <latching>false</latching> + <annunciating>false</annunciating> <guidance> <title>[Operator Action]</title> <details>AccODH-AT:ODH-ACS-015 in HBL section of the accelerator tunnel failure @@ -402,8 +476,8 @@ Call cryo on call </pv> <pv name="AccODH-AT:ODH-ACS-016:Failure"> <description>Device failure</description> - <latching>true</latching> - <annunciating>true</annunciating> + <latching>false</latching> + <annunciating>false</annunciating> <guidance> <title>[Operator Action]</title> <details>AccODH-AT:ODH-ACS-016 in EEx2 section of the accelerator tunnel failure @@ -412,8 +486,8 @@ Call cryo on call </pv> <pv name="AccODH-AT:ODH-ACS-017:Failure"> <description>Device failure</description> - <latching>true</latching> - <annunciating>true</annunciating> + <latching>false</latching> + <annunciating>false</annunciating> <guidance> <title>[Operator Action]</title> <details>AccODH-AT:ODH-ACS-017 in EEx2 section of the accelerator tunnel failure @@ -422,8 +496,8 @@ Call cryo on call </pv> <pv name="AccODH-AT:ODH-ACS-018:Failure"> <description>Device failure</description> - <latching>true</latching> - <annunciating>true</annunciating> + <latching>false</latching> + <annunciating>false</annunciating> <guidance> <title>[Operator Action]</title> <details>AccODH-AT:ODH-ACS-018 in HBL section of the accelerator tunnel failure @@ -432,8 +506,8 @@ Call cryo on call </pv> <pv name="AccODH-AT:ODH-ACS-019:Failure"> <description>Device failure</description> - <latching>true</latching> - <annunciating>true</annunciating> + <latching>false</latching> + <annunciating>false</annunciating> <guidance> <title>[Operator Action]</title> <details>AccODH-AT:ODH-ACS-019 in HBL section of the accelerator tunnel failure @@ -442,8 +516,8 @@ Call cryo on call </pv> <pv name="AccODH-AT:ODH-ACS-020:Failure"> <description>Device failure</description> - <latching>true</latching> - <annunciating>true</annunciating> + <latching>false</latching> + <annunciating>false</annunciating> <guidance> <title>[Operator Action]</title> <details>AccODH-AT:ODH-ACS-020 in HBL section of the accelerator tunnel failure @@ -452,8 +526,8 @@ Call cryo on call </pv> <pv name="AccODH-AT:ODH-ACS-021:Failure"> <description>Device failure</description> - <latching>true</latching> - <annunciating>true</annunciating> + <latching>false</latching> + <annunciating>false</annunciating> <guidance> <title>[Operator Action]</title> <details>AccODH-AT:ODH-ACS-021 in HBL section of the accelerator tunnel failure @@ -462,8 +536,8 @@ Call cryo on call </pv> <pv name="AccODH-AT:ODH-ACS-022:Failure"> <description>Device failure</description> - <latching>true</latching> - <annunciating>true</annunciating> + <latching>false</latching> + <annunciating>false</annunciating> <guidance> <title>[Operator Action]</title> <details>AccODH-AT:ODH-ACS-022 in HEBT loading bay section of the accelerator tunnel failure @@ -472,8 +546,8 @@ Call cryo on call </pv> <pv name="AccODH-AT:ODH-ACS-023:Failure"> <description>Device failure</description> - <latching>true</latching> - <annunciating>true</annunciating> + <latching>false</latching> + <annunciating>false</annunciating> <guidance> <title>[Operator Action]</title> <details>AccODH-AT:ODH-ACS-023 in HEBT loading bay section of the accelerator tunnel failure @@ -482,8 +556,8 @@ Call cryo on call </pv> <pv name="AccODH-AT:ODH-ACS-024:Failure"> <description>Device failure</description> - <latching>true</latching> - <annunciating>true</annunciating> + <latching>false</latching> + <annunciating>false</annunciating> <guidance> <title>[Operator Action]</title> <details>AccODH-AT:ODH-ACS-024 in HEBT loading bay section of the accelerator tunnel failure @@ -492,8 +566,8 @@ Call cryo on call </pv> <pv name="AccODH-AT:ODH-ACS-025:Failure"> <description>Device failure</description> - <latching>true</latching> - <annunciating>true</annunciating> + <latching>false</latching> + <annunciating>false</annunciating> <guidance> <title>[Operator Action]</title> <details>AccODH-AT:ODH-ACS-025 in HEBT section of the accelerator tunnel failure @@ -502,8 +576,8 @@ Call cryo on call </pv> <pv name="AccODH-AT:ODH-ACS-026:Failure"> <description>Device failure</description> - <latching>true</latching> - <annunciating>true</annunciating> + <latching>false</latching> + <annunciating>false</annunciating> <guidance> <title>[Operator Action]</title> <details>AccODH-AT:ODH-ACS-026 in EEx3 section of the accelerator tunnel failure @@ -512,8 +586,8 @@ Call cryo on call </pv> <pv name="AccODH-AT:ODH-ACS-027:Failure"> <description>Device failure</description> - <latching>true</latching> - <annunciating>true</annunciating> + <latching>false</latching> + <annunciating>false</annunciating> <guidance> <title>[Operator Action]</title> <details>AccODH-AT:ODH-ACS-027 in EEx3 section of the accelerator tunnel failure @@ -522,8 +596,8 @@ Call cryo on call </pv> <pv name="AccODH-AT:ODH-ACS-028:Failure"> <description>Device failure</description> - <latching>true</latching> - <annunciating>true</annunciating> + <latching>false</latching> + <annunciating>false</annunciating> <guidance> <title>[Operator Action]</title> <details>AccODH-AT:ODH-ACS-028 in HEBT loading bay section of the accelerator tunnel failure @@ -532,8 +606,8 @@ Call cryo on call </pv> <pv name="AccODH-AT:ODH-ACS-029:Failure"> <description>Device failure</description> - <latching>true</latching> - <annunciating>true</annunciating> + <latching>false</latching> + <annunciating>false</annunciating> <guidance> <title>[Operator Action]</title> <details>AccODH-AT:ODH-ACS-029 in HEBT section of the accelerator tunnel failure @@ -542,8 +616,8 @@ Call cryo on call </pv> <pv name="AccODH-AT:ODH-ACS-030:Failure"> <description>Device failure</description> - <latching>true</latching> - <annunciating>true</annunciating> + <latching>false</latching> + <annunciating>false</annunciating> <guidance> <title>[Operator Action]</title> <details>AccODH-AT:ODH-ACS-030 in HEBT section of the accelerator tunnel failure @@ -552,8 +626,8 @@ Call cryo on call </pv> <pv name="AccODH-AT:ODH-ACS-031:Failure"> <description>Device failure</description> - <latching>true</latching> - <annunciating>true</annunciating> + <latching>false</latching> + <annunciating>false</annunciating> <guidance> <title>[Operator Action]</title> <details>AccODH-AT:ODH-ACS-031 in HEBT section of the accelerator tunnel failure @@ -562,8 +636,8 @@ Call cryo on call </pv> <pv name="AccODH-AT:ODH-ACS-032:Failure"> <description>Device failure</description> - <latching>true</latching> - <annunciating>true</annunciating> + <latching>false</latching> + <annunciating>false</annunciating> <guidance> <title>[Operator Action]</title> <details>AccODH-AT:ODH-ACS-032 in DL section of the accelerator tunnel failure @@ -572,18 +646,18 @@ Call cryo on call </pv> <pv name="AccODH-AT:ODH-ACS-033:Failure"> <description>Device failure</description> - <latching>true</latching> - <annunciating>true</annunciating> + <latching>false</latching> + <annunciating>false</annunciating> <guidance> <title>[Operator Action]</title> - <details>AccODH-AT:ODH-ACS-033 in DL section of the accelerator tunnel failure + <details>AccODH-AT:ODH-ACS-033 in EEx4 section of the accelerator tunnel failure - MCR/Gate guard/Cryo team: Inform PSS team</details> </guidance> </pv> <pv name="AccODH-AT:ODH-ACS-034:Failure"> <description>Device failure</description> - <latching>true</latching> - <annunciating>true</annunciating> + <latching>false</latching> + <annunciating>false</annunciating> <guidance> <title>[Operator Action]</title> <details>AccODH-AT:ODH-ACS-034 in EEx4 section of the accelerator tunnel failure @@ -592,18 +666,18 @@ Call cryo on call </pv> <pv name="AccODH-AT:ODH-ACS-035:Failure"> <description>Device failure</description> - <latching>true</latching> - <annunciating>true</annunciating> + <latching>false</latching> + <annunciating>false</annunciating> <guidance> <title>[Operator Action]</title> - <details>AccODH-AT:ODH-ACS-035 in EEx4 section of the accelerator tunnel failure + <details>AccODH-AT:ODH-ACS-035 in DL section of the accelerator tunnel failure - MCR/Gate guard/Cryo team: Inform PSS team</details> </guidance> </pv> <pv name="AccODH-AT:ODH-ACS-036:Failure"> <description>Device failure</description> - <latching>true</latching> - <annunciating>true</annunciating> + <latching>false</latching> + <annunciating>false</annunciating> <guidance> <title>[Operator Action]</title> <details>AccODH-AT:ODH-ACS-036 in A2T section of the accelerator tunnel failure @@ -612,8 +686,8 @@ Call cryo on call </pv> <pv name="AccODH-AT:ODH-ACS-037:Failure"> <description>Device failure</description> - <latching>true</latching> - <annunciating>true</annunciating> + <latching>false</latching> + <annunciating>false</annunciating> <guidance> <title>[Operator Action]</title> <details>AccODH-AT:ODH-ACS-037 in A2T section of the accelerator tunnel failure @@ -624,8 +698,8 @@ Call cryo on call <component name="FAS"> <pv name="AccODH-AT::EvacAlmSts_Failure"> <description>Output failure</description> - <latching>true</latching> - <annunciating>true</annunciating> + <latching>false</latching> + <annunciating>false</annunciating> <guidance> <title>[Operator Action]</title> <details>Evacuation alarm interface failure @@ -634,8 +708,8 @@ Call cryo on call </pv> <pv name="AccODH-AT::ConfAlmSts_Failure"> <description>Output failure</description> - <latching>true</latching> - <annunciating>true</annunciating> + <latching>false</latching> + <annunciating>false</annunciating> <guidance> <title>[Operator Action]</title> <details>Confirmed alarm interface failure @@ -647,11 +721,11 @@ Call cryo on call <component name="O2IM1"> <pv name="AccODH-AT:ODH-O2iM-001:O2Below18"> <description>ODH Alarm (Oxygen below 18%)</description> - <latching>true</latching> - <annunciating>true</annunciating> + <latching>false</latching> + <annunciating>false</annunciating> <guidance> <title>[Operator Action]</title> - <details>AccODH-AT:ODH-O2iM-001 in SPK section of the accelerator tunnel ODH alarm- O2 less than 18% + <details>AccODH-AT:ODH-O2iM-001 monitoring SPK section of the accelerator tunnel ODH alarm- O2 less than 18% Call cryo on call - MCR: Follow ESS-3216323 - Gate guard: Follow ESS-2124375 @@ -660,11 +734,11 @@ Call cryo on call </pv> <pv name="AccODH-AT:ODH-O2iM-001:O2Below19_5"> <description>ODH Warning (Oxygen below 19.5%)</description> - <latching>true</latching> - <annunciating>true</annunciating> + <latching>false</latching> + <annunciating>false</annunciating> <guidance> <title>[Operator Action]</title> - <details>AccODH-AT:ODH-O2iM-001 in SPK section of the accelerator tunnel ODH warning- O2 less than 19.5% + <details>AccODH-AT:ODH-O2iM-001 monitoring SPK section of the accelerator tunnel ODH warning- O2 less than 19.5% Call cryo on call - MCR: Follow ESS-3216323 - Gate guard: Follow ESS-2124375 @@ -677,26 +751,26 @@ Call cryo on call <annunciating>false</annunciating> <guidance> <title>[Operator Action]</title> - <details>AccODH-AT:ODH-O2iM-001 in the SPK section of the accelerator tunnel is in maintenance mode</details> + <details>AccODH-AT:ODH-O2iM-001 monitoring SPK section of the accelerator tunnel is in maintenance mode</details> </guidance> </pv> <pv name="AccODH-AT:ODH-O2iM-001:Disconnected"> <description>Monitor lost connection</description> - <latching>true</latching> - <annunciating>true</annunciating> + <latching>false</latching> + <annunciating>false</annunciating> <guidance> <title>[Operator Action]</title> - <details>AccODH-AT:ODH-O2iM-001 in the SPK section of the accelerator tunnel has lost connection + <details>AccODH-AT:ODH-O2iM-001 monitoring SPK section of the accelerator tunnel has lost connection - MCR/Gate guard/Cryo team: Inform PSS team</details> </guidance> </pv> <pv name="AccODH-AT:ODH-O2iM-001:Failure"> <description>Monitor failure</description> - <latching>true</latching> - <annunciating>true</annunciating> + <latching>false</latching> + <annunciating>false</annunciating> <guidance> <title>[Operator Action]</title> - <details>AccODH-AT:ODH-O2iM-001 in the SPK section of the accelerator tunnel failure + <details>AccODH-AT:ODH-O2iM-001 monitoring SPK section of the accelerator tunnel failure - MCR/Gate guard/Cryo team: Inform PSS team</details> </guidance> </pv> @@ -706,7 +780,7 @@ Call cryo on call <annunciating>false</annunciating> <guidance> <title>[Operator Action]</title> - <details>AccODH-AT:ODH-O2iM-001 in the SPK section of the accelerator tunnel analogue input is out of range + <details>AccODH-AT:ODH-O2iM-001 monitoring SPK section of the accelerator tunnel analogue input is out of range - MCR/Gate guard/Cryo team: Inform PSS team</details> </guidance> </pv> @@ -714,11 +788,11 @@ Call cryo on call <component name="O2IM2"> <pv name="AccODH-AT:ODH-O2iM-002:O2Below18"> <description>ODH Alarm (Oxygen below 18%)</description> - <latching>true</latching> - <annunciating>true</annunciating> + <latching>false</latching> + <annunciating>false</annunciating> <guidance> <title>[Operator Action]</title> - <details>AccODH-AT:ODH-O2iM-002 in SPK section of the accelerator tunnel ODH alarm- O2 less than 18% + <details>AccODH-AT:ODH-O2iM-002 monitoring SPK section of the accelerator tunnel ODH alarm- O2 less than 18% Call cryo on call - MCR: Follow ESS-3216323 - Gate guard: Follow ESS-2124375 @@ -727,11 +801,11 @@ Call cryo on call </pv> <pv name="AccODH-AT:ODH-O2iM-002:O2Below19_5"> <description>ODH Warning (Oxygen below 19.5%)</description> - <latching>true</latching> - <annunciating>true</annunciating> + <latching>false</latching> + <annunciating>false</annunciating> <guidance> <title>[Operator Action]</title> - <details>AccODH-AT:ODH-O2iM-002 in SPK section of the accelerator tunnel ODH warning- O2 less than 19.5% + <details>AccODH-AT:ODH-O2iM-002 monitoring SPK section of the accelerator tunnel ODH warning- O2 less than 19.5% Call cryo on call - MCR: Follow ESS-3216323 - Gate guard: Follow ESS-2124375 @@ -744,26 +818,26 @@ Call cryo on call <annunciating>false</annunciating> <guidance> <title>[Operator Action]</title> - <details>AccODH-AT:ODH-O2iM-002 in the SPK section of the accelerator tunnel is in maintenance mode</details> + <details>AccODH-AT:ODH-O2iM-002 monitoring SPK section of the accelerator tunnel is in maintenance mode</details> </guidance> </pv> <pv name="AccODH-AT:ODH-O2iM-002:Disconnected"> <description>Monitor lost connection</description> - <latching>true</latching> - <annunciating>true</annunciating> + <latching>false</latching> + <annunciating>false</annunciating> <guidance> <title>[Operator Action]</title> - <details>AccODH-AT:ODH-O2iM-002 in the SPK section of the accelerator tunnel has lost connection + <details>AccODH-AT:ODH-O2iM-002 monitoring SPK section of the accelerator tunnel has lost connection - MCR/Gate guard/Cryo team: Inform PSS team</details> </guidance> </pv> <pv name="AccODH-AT:ODH-O2iM-002:Failure"> <description>Monitor failure</description> - <latching>true</latching> - <annunciating>true</annunciating> + <latching>false</latching> + <annunciating>false</annunciating> <guidance> <title>[Operator Action]</title> - <details>AccODH-AT:ODH-O2iM-002 in the SPK section of the accelerator tunnel failure + <details>AccODH-AT:ODH-O2iM-002 monitoring SPK section of the accelerator tunnel failure - MCR/Gate guard/Cryo team: Inform PSS team</details> </guidance> </pv> @@ -773,7 +847,7 @@ Call cryo on call <annunciating>false</annunciating> <guidance> <title>[Operator Action]</title> - <details>AccODH-AT:ODH-O2iM-002 in the SPK section of the accelerator tunnel analogue input is out of range + <details>AccODH-AT:ODH-O2iM-002 monitoring SPK section of the accelerator tunnel analogue input is out of range - MCR/Gate guard/Cryo team: Inform PSS team</details> </guidance> </pv> @@ -781,11 +855,11 @@ Call cryo on call <component name="O2IM3"> <pv name="AccODH-AT:ODH-O2iM-003:O2Below18"> <description>ODH Alarm (Oxygen below 18%)</description> - <latching>true</latching> - <annunciating>true</annunciating> + <latching>false</latching> + <annunciating>false</annunciating> <guidance> <title>[Operator Action]</title> - <details>AccODH-AT:ODH-O2iM-003 in SPK section of the accelerator tunnel ODH alarm- O2 less than 18% + <details>AccODH-AT:ODH-O2iM-003 monitoring SPK section of the accelerator tunnel ODH alarm- O2 less than 18% Call cryo on call - MCR: Follow ESS-3216323 - Gate guard: Follow ESS-2124375 @@ -794,11 +868,11 @@ Call cryo on call </pv> <pv name="AccODH-AT:ODH-O2iM-003:O2Below19_5"> <description>ODH Warning (Oxygen below 19.5%)</description> - <latching>true</latching> - <annunciating>true</annunciating> + <latching>false</latching> + <annunciating>false</annunciating> <guidance> <title>[Operator Action]</title> - <details>AccODH-AT:ODH-O2iM-003 in SPK section of the accelerator tunnel ODH warning- O2 less than 19.5% + <details>AccODH-AT:ODH-O2iM-003 monitoring SPK section of the accelerator tunnel ODH warning- O2 less than 19.5% Call cryo on call - MCR: Follow ESS-3216323 - Gate guard: Follow ESS-2124375 @@ -811,26 +885,26 @@ Call cryo on call <annunciating>false</annunciating> <guidance> <title>[Operator Action]</title> - <details>AccODH-AT:ODH-O2iM-003 in the SPK section of the accelerator tunnel is in maintenance mode</details> + <details>AccODH-AT:ODH-O2iM-003 monitoring SPK section of the accelerator tunnel is in maintenance mode</details> </guidance> </pv> <pv name="AccODH-AT:ODH-O2iM-003:Disconnected"> <description>Monitor lost connection</description> - <latching>true</latching> - <annunciating>true</annunciating> + <latching>false</latching> + <annunciating>false</annunciating> <guidance> <title>[Operator Action]</title> - <details>AccODH-AT:ODH-O2iM-003 in the SPK section of the accelerator tunnel has lost connection + <details>AccODH-AT:ODH-O2iM-003 monitoring SPK section of the accelerator tunnel has lost connection - MCR/Gate guard/Cryo team: Inform PSS team</details> </guidance> </pv> <pv name="AccODH-AT:ODH-O2iM-003:Failure"> <description>Monitor failure</description> - <latching>true</latching> - <annunciating>true</annunciating> + <latching>false</latching> + <annunciating>false</annunciating> <guidance> <title>[Operator Action]</title> - <details>AccODH-AT:ODH-O2iM-003 in the SPK section of the accelerator tunnel failure + <details>AccODH-AT:ODH-O2iM-003 monitoring SPK section of the accelerator tunnel failure - MCR/Gate guard/Cryo team: Inform PSS team</details> </guidance> </pv> @@ -840,7 +914,7 @@ Call cryo on call <annunciating>false</annunciating> <guidance> <title>[Operator Action]</title> - <details>AccODH-AT:ODH-O2iM-003 in the SPK section of the accelerator tunnel analogue input is out of range + <details>AccODH-AT:ODH-O2iM-003 monitoring SPK section of the accelerator tunnel analogue input is out of range - MCR/Gate guard/Cryo team: Inform PSS team</details> </guidance> </pv> @@ -848,11 +922,11 @@ Call cryo on call <component name="O2IM4"> <pv name="AccODH-AT:ODH-O2iM-004:O2Below18"> <description>ODH Alarm (Oxygen below 18%)</description> - <latching>true</latching> - <annunciating>true</annunciating> + <latching>false</latching> + <annunciating>false</annunciating> <guidance> <title>[Operator Action]</title> - <details>AccODH-AT:ODH-O2iM-004 in MBL section of the accelerator tunnel ODH alarm- O2 less than 18% + <details>AccODH-AT:ODH-O2iM-004 monitoring MBL section of the accelerator tunnel ODH alarm- O2 less than 18% Call cryo on call - MCR: Follow ESS-3216323 - Gate guard: Follow ESS-2124375 @@ -861,11 +935,11 @@ Call cryo on call </pv> <pv name="AccODH-AT:ODH-O2iM-004:O2Below19_5"> <description>ODH Warning (Oxygen below 19.5%)</description> - <latching>true</latching> - <annunciating>true</annunciating> + <latching>false</latching> + <annunciating>false</annunciating> <guidance> <title>[Operator Action]</title> - <details>AccODH-AT:ODH-O2iM-004 in MBL section of the accelerator tunnel ODH warning- O2 less than 19.5% + <details>AccODH-AT:ODH-O2iM-004 monitoring MBL section of the accelerator tunnel ODH warning- O2 less than 19.5% Call cryo on call - MCR: Follow ESS-3216323 - Gate guard: Follow ESS-2124375 @@ -878,26 +952,26 @@ Call cryo on call <annunciating>false</annunciating> <guidance> <title>[Operator Action]</title> - <details>AccODH-AT:ODH-O2iM-004 in the MBL section of the accelerator tunnel is in maintenance mode</details> + <details>AccODH-AT:ODH-O2iM-004 monitoring MBL section of the accelerator tunnel is in maintenance mode</details> </guidance> </pv> <pv name="AccODH-AT:ODH-O2iM-004:Disconnected"> <description>Monitor lost connection</description> - <latching>true</latching> - <annunciating>true</annunciating> + <latching>false</latching> + <annunciating>false</annunciating> <guidance> <title>[Operator Action]</title> - <details>AccODH-AT:ODH-O2iM-004 in the MBL section of the accelerator tunnel has lost connection + <details>AccODH-AT:ODH-O2iM-004 monitoring MBL section of the accelerator tunnel has lost connection - MCR/Gate guard/Cryo team: Inform PSS team</details> </guidance> </pv> <pv name="AccODH-AT:ODH-O2iM-004:Failure"> <description>Monitor failure</description> - <latching>true</latching> - <annunciating>true</annunciating> + <latching>false</latching> + <annunciating>false</annunciating> <guidance> <title>[Operator Action]</title> - <details>AccODH-AT:ODH-O2iM-004 in the MBL section of the accelerator tunnel failure + <details>AccODH-AT:ODH-O2iM-004 monitoring MBL section of the accelerator tunnel failure - MCR/Gate guard/Cryo team: Inform PSS team</details> </guidance> </pv> @@ -907,7 +981,7 @@ Call cryo on call <annunciating>false</annunciating> <guidance> <title>[Operator Action]</title> - <details>AccODH-AT:ODH-O2iM-004 in the MBL section of the accelerator tunnel analogue input is out of range + <details>AccODH-AT:ODH-O2iM-004 monitoring MBL section of the accelerator tunnel analogue input is out of range - MCR/Gate guard/Cryo team: Inform PSS team</details> </guidance> </pv> @@ -915,11 +989,11 @@ Call cryo on call <component name="O2IM5"> <pv name="AccODH-AT:ODH-O2iM-005:O2Below18"> <description>ODH Alarm (Oxygen below 18%)</description> - <latching>true</latching> - <annunciating>true</annunciating> + <latching>false</latching> + <annunciating>false</annunciating> <guidance> <title>[Operator Action]</title> - <details>AccODH-AT:ODH-O2iM-005 in MBL section of the accelerator tunnel ODH alarm- O2 less than 18% + <details>AccODH-AT:ODH-O2iM-005 monitoring MBL section of the accelerator tunnel ODH alarm- O2 less than 18% Call cryo on call - MCR: Follow ESS-3216323 - Gate guard: Follow ESS-2124375 @@ -928,11 +1002,11 @@ Call cryo on call </pv> <pv name="AccODH-AT:ODH-O2iM-005:O2Below19_5"> <description>ODH Warning (Oxygen below 19.5%)</description> - <latching>true</latching> - <annunciating>true</annunciating> + <latching>false</latching> + <annunciating>false</annunciating> <guidance> <title>[Operator Action]</title> - <details>AccODH-AT:ODH-O2iM-005 in MBL section of the accelerator tunnel ODH warning- O2 less than 19.5% + <details>AccODH-AT:ODH-O2iM-005 monitoring MBL section of the accelerator tunnel ODH warning- O2 less than 19.5% Call cryo on call - MCR: Follow ESS-3216323 - Gate guard: Follow ESS-2124375 @@ -945,26 +1019,26 @@ Call cryo on call <annunciating>false</annunciating> <guidance> <title>[Operator Action]</title> - <details>AccODH-AT:ODH-O2iM-005 in the MBL section of the accelerator tunnel is in maintenance mode</details> + <details>AccODH-AT:ODH-O2iM-005 monitoring MBL section of the accelerator tunnel is in maintenance mode</details> </guidance> </pv> <pv name="AccODH-AT:ODH-O2iM-005:Disconnected"> <description>Monitor lost connection</description> - <latching>true</latching> - <annunciating>true</annunciating> + <latching>false</latching> + <annunciating>false</annunciating> <guidance> <title>[Operator Action]</title> - <details>AccODH-AT:ODH-O2iM-005 in the MBL section of the accelerator tunnel has lost connection + <details>AccODH-AT:ODH-O2iM-005 monitoring MBL section of the accelerator tunnel has lost connection - MCR/Gate guard/Cryo team: Inform PSS team</details> </guidance> </pv> <pv name="AccODH-AT:ODH-O2iM-005:Failure"> <description>Monitor failure</description> - <latching>true</latching> - <annunciating>true</annunciating> + <latching>false</latching> + <annunciating>false</annunciating> <guidance> <title>[Operator Action]</title> - <details>AccODH-AT:ODH-O2iM-005 in the MBL section of the accelerator tunnel failure + <details>AccODH-AT:ODH-O2iM-005 monitoring MBL section of the accelerator tunnel failure - MCR/Gate guard/Cryo team: Inform PSS team</details> </guidance> </pv> @@ -974,7 +1048,7 @@ Call cryo on call <annunciating>false</annunciating> <guidance> <title>[Operator Action]</title> - <details>AccODH-AT:ODH-O2iM-005 in the MBL section of the accelerator tunnel analogue input is out of range + <details>AccODH-AT:ODH-O2iM-005 monitoring MBL section of the accelerator tunnel analogue input is out of range - MCR/Gate guard/Cryo team: Inform PSS team</details> </guidance> </pv> @@ -982,11 +1056,11 @@ Call cryo on call <component name="O2IM6"> <pv name="AccODH-AT:ODH-O2iM-006:O2Below18"> <description>ODH Alarm (Oxygen below 18%)</description> - <latching>true</latching> - <annunciating>true</annunciating> + <latching>false</latching> + <annunciating>false</annunciating> <guidance> <title>[Operator Action]</title> - <details>AccODH-AT:ODH-O2iM-006 in MBL section of the accelerator tunnel ODH alarm- O2 less than 18% + <details>AccODH-AT:ODH-O2iM-006 monitoring MBL section of the accelerator tunnel ODH alarm- O2 less than 18% Call cryo on call - MCR: Follow ESS-3216323 - Gate guard: Follow ESS-2124375 @@ -995,11 +1069,11 @@ Call cryo on call </pv> <pv name="AccODH-AT:ODH-O2iM-006:O2Below19_5"> <description>ODH Warning (Oxygen below 19.5%)</description> - <latching>true</latching> - <annunciating>true</annunciating> + <latching>false</latching> + <annunciating>false</annunciating> <guidance> <title>[Operator Action]</title> - <details>AccODH-AT:ODH-O2iM-006 in MBL section of the accelerator tunnel ODH warning- O2 less than 19.5% + <details>AccODH-AT:ODH-O2iM-006 monitoring MBL section of the accelerator tunnel ODH warning- O2 less than 19.5% Call cryo on call - MCR: Follow ESS-3216323 - Gate guard: Follow ESS-2124375 @@ -1012,26 +1086,26 @@ Call cryo on call <annunciating>false</annunciating> <guidance> <title>[Operator Action]</title> - <details>AccODH-AT:ODH-O2iM-006 in the MBL section of the accelerator tunnel is in maintenance mode</details> + <details>AccODH-AT:ODH-O2iM-006 monitoring MBL section of the accelerator tunnel is in maintenance mode</details> </guidance> </pv> <pv name="AccODH-AT:ODH-O2iM-006:Disconnected"> <description>Monitor lost connection</description> - <latching>true</latching> - <annunciating>true</annunciating> + <latching>false</latching> + <annunciating>false</annunciating> <guidance> <title>[Operator Action]</title> - <details>AccODH-AT:ODH-O2iM-006 in the MBL section of the accelerator tunnel has lost connection + <details>AccODH-AT:ODH-O2iM-006 monitoring MBL section of the accelerator tunnel has lost connection - MCR/Gate guard/Cryo team: Inform PSS team</details> </guidance> </pv> <pv name="AccODH-AT:ODH-O2iM-006:Failure"> <description>Monitor failure</description> - <latching>true</latching> - <annunciating>true</annunciating> + <latching>false</latching> + <annunciating>false</annunciating> <guidance> <title>[Operator Action]</title> - <details>AccODH-AT:ODH-O2iM-006 in the MBL section of the accelerator tunnel failure + <details>AccODH-AT:ODH-O2iM-006 monitoring MBL section of the accelerator tunnel failure - MCR/Gate guard/Cryo team: Inform PSS team</details> </guidance> </pv> @@ -1041,7 +1115,7 @@ Call cryo on call <annunciating>false</annunciating> <guidance> <title>[Operator Action]</title> - <details>AccODH-AT:ODH-O2iM-006 in the MBL section of the accelerator tunnel analogue input is out of range + <details>AccODH-AT:ODH-O2iM-006 monitoring MBL section of the accelerator tunnel analogue input is out of range - MCR/Gate guard/Cryo team: Inform PSS team</details> </guidance> </pv> @@ -1049,11 +1123,11 @@ Call cryo on call <component name="O2IM7"> <pv name="AccODH-AT:ODH-O2iM-007:O2Below18"> <description>ODH Alarm (Oxygen below 18%)</description> - <latching>true</latching> - <annunciating>true</annunciating> + <latching>false</latching> + <annunciating>false</annunciating> <guidance> <title>[Operator Action]</title> - <details>AccODH-AT:ODH-O2iM-007 in MBL section of the accelerator tunnel ODH alarm- O2 less than 18% + <details>AccODH-AT:ODH-O2iM-007 monitoring MBL section of the accelerator tunnel ODH alarm- O2 less than 18% Call cryo on call - MCR: Follow ESS-3216323 - Gate guard: Follow ESS-2124375 @@ -1062,11 +1136,11 @@ Call cryo on call </pv> <pv name="AccODH-AT:ODH-O2iM-007:O2Below19_5"> <description>ODH Warning (Oxygen below 19.5%)</description> - <latching>true</latching> - <annunciating>true</annunciating> + <latching>false</latching> + <annunciating>false</annunciating> <guidance> <title>[Operator Action]</title> - <details>AccODH-AT:ODH-O2iM-007 in MBL section of the accelerator tunnel ODH warning- O2 less than 19.5% + <details>AccODH-AT:ODH-O2iM-007 monitoring MBL section of the accelerator tunnel ODH warning- O2 less than 19.5% Call cryo on call - MCR: Follow ESS-3216323 - Gate guard: Follow ESS-2124375 @@ -1079,26 +1153,26 @@ Call cryo on call <annunciating>false</annunciating> <guidance> <title>[Operator Action]</title> - <details>AccODH-AT:ODH-O2iM-007 in the MBL section of the accelerator tunnel is in maintenance mode</details> + <details>AccODH-AT:ODH-O2iM-007 monitoring MBL section of the accelerator tunnel is in maintenance mode</details> </guidance> </pv> <pv name="AccODH-AT:ODH-O2iM-007:Disconnected"> <description>Monitor lost connection</description> - <latching>true</latching> - <annunciating>true</annunciating> + <latching>false</latching> + <annunciating>false</annunciating> <guidance> <title>[Operator Action]</title> - <details>AccODH-AT:ODH-O2iM-007 in the MBL section of the accelerator tunnel has lost connection + <details>AccODH-AT:ODH-O2iM-007 monitoring MBL section of the accelerator tunnel has lost connection - MCR/Gate guard/Cryo team: Inform PSS team</details> </guidance> </pv> <pv name="AccODH-AT:ODH-O2iM-007:Failure"> <description>Monitor failure</description> - <latching>true</latching> - <annunciating>true</annunciating> + <latching>false</latching> + <annunciating>false</annunciating> <guidance> <title>[Operator Action]</title> - <details>AccODH-AT:ODH-O2iM-007 in the MBL section of the accelerator tunnel failure + <details>AccODH-AT:ODH-O2iM-007 monitoring MBL section of the accelerator tunnel failure - MCR/Gate guard/Cryo team: Inform PSS team</details> </guidance> </pv> @@ -1108,7 +1182,7 @@ Call cryo on call <annunciating>false</annunciating> <guidance> <title>[Operator Action]</title> - <details>AccODH-AT:ODH-O2iM-007 in the MBL section of the accelerator tunnel analogue input is out of range + <details>AccODH-AT:ODH-O2iM-007 monitoring MBL section of the accelerator tunnel analogue input is out of range - MCR/Gate guard/Cryo team: Inform PSS team</details> </guidance> </pv> @@ -1116,11 +1190,11 @@ Call cryo on call <component name="O2IM8"> <pv name="AccODH-AT:ODH-O2iM-008:O2Below18"> <description>ODH Alarm (Oxygen below 18%)</description> - <latching>true</latching> - <annunciating>true</annunciating> + <latching>false</latching> + <annunciating>false</annunciating> <guidance> <title>[Operator Action]</title> - <details>AccODH-AT:ODH-O2iM-008 in HBL section of the accelerator tunnel ODH alarm- O2 less than 18% + <details>AccODH-AT:ODH-O2iM-008 monitoring HBL section of the accelerator tunnel ODH alarm- O2 less than 18% Call cryo on call - MCR: Follow ESS-3216323 - Gate guard: Follow ESS-2124375 @@ -1129,11 +1203,11 @@ Call cryo on call </pv> <pv name="AccODH-AT:ODH-O2iM-008:O2Below19_5"> <description>ODH Warning (Oxygen below 19.5%)</description> - <latching>true</latching> - <annunciating>true</annunciating> + <latching>false</latching> + <annunciating>false</annunciating> <guidance> <title>[Operator Action]</title> - <details>AccODH-AT:ODH-O2iM-008 in HBL section of the accelerator tunnel ODH warning- O2 less than 19.5% + <details>AccODH-AT:ODH-O2iM-008 monitoring HBL section of the accelerator tunnel ODH warning- O2 less than 19.5% Call cryo on call - MCR: Follow ESS-3216323 - Gate guard: Follow ESS-2124375 @@ -1146,26 +1220,26 @@ Call cryo on call <annunciating>false</annunciating> <guidance> <title>[Operator Action]</title> - <details>AccODH-AT:ODH-O2iM-008 in the HBL section of the accelerator tunnel is in maintenance mode</details> + <details>AccODH-AT:ODH-O2iM-008 monitoring HBL section of the accelerator tunnel is in maintenance mode</details> </guidance> </pv> <pv name="AccODH-AT:ODH-O2iM-008:Disconnected"> <description>Monitor lost connection</description> - <latching>true</latching> - <annunciating>true</annunciating> + <latching>false</latching> + <annunciating>false</annunciating> <guidance> <title>[Operator Action]</title> - <details>AccODH-AT:ODH-O2iM-008 in the HBL section of the accelerator tunnel has lost connection + <details>AccODH-AT:ODH-O2iM-008 monitoring HBL section of the accelerator tunnel has lost connection - MCR/Gate guard/Cryo team: Inform PSS team</details> </guidance> </pv> <pv name="AccODH-AT:ODH-O2iM-008:Failure"> <description>Monitor failure</description> - <latching>true</latching> - <annunciating>true</annunciating> + <latching>false</latching> + <annunciating>false</annunciating> <guidance> <title>[Operator Action]</title> - <details>AccODH-AT:ODH-O2iM-008 in the HBL section of the accelerator tunnel failure + <details>AccODH-AT:ODH-O2iM-008 monitoring HBL section of the accelerator tunnel failure - MCR/Gate guard/Cryo team: Inform PSS team</details> </guidance> </pv> @@ -1175,7 +1249,7 @@ Call cryo on call <annunciating>false</annunciating> <guidance> <title>[Operator Action]</title> - <details>AccODH-AT:ODH-O2iM-008 in the HBL section of the accelerator tunnel analogue input is out of range + <details>AccODH-AT:ODH-O2iM-008 monitoring HBL section of the accelerator tunnel analogue input is out of range - MCR/Gate guard/Cryo team: Inform PSS team</details> </guidance> </pv> @@ -1183,11 +1257,11 @@ Call cryo on call <component name="O2IM9"> <pv name="AccODH-AT:ODH-O2iM-009:O2Below18"> <description>ODH Alarm (Oxygen below 18%)</description> - <latching>true</latching> - <annunciating>true</annunciating> + <latching>false</latching> + <annunciating>false</annunciating> <guidance> <title>[Operator Action]</title> - <details>AccODH-AT:ODH-O2iM-009 in HBL section of the accelerator tunnel ODH alarm- O2 less than 18% + <details>AccODH-AT:ODH-O2iM-009 monitoring HBL section of the accelerator tunnel ODH alarm- O2 less than 18% Call cryo on call - MCR: Follow ESS-3216323 - Gate guard: Follow ESS-2124375 @@ -1196,11 +1270,11 @@ Call cryo on call </pv> <pv name="AccODH-AT:ODH-O2iM-009:O2Below19_5"> <description>ODH Warning (Oxygen below 19.5%)</description> - <latching>true</latching> - <annunciating>true</annunciating> + <latching>false</latching> + <annunciating>false</annunciating> <guidance> <title>[Operator Action]</title> - <details>AccODH-AT:ODH-O2iM-009 in HBL section of the accelerator tunnel ODH warning- O2 less than 19.5% + <details>AccODH-AT:ODH-O2iM-009 monitoring HBL section of the accelerator tunnel ODH warning- O2 less than 19.5% Call cryo on call - MCR: Follow ESS-3216323 - Gate guard: Follow ESS-2124375 @@ -1213,26 +1287,26 @@ Call cryo on call <annunciating>false</annunciating> <guidance> <title>[Operator Action]</title> - <details>AccODH-AT:ODH-O2iM-009 in the HBL section of the accelerator tunnel is in maintenance mode</details> + <details>AccODH-AT:ODH-O2iM-009 monitoring HBL section of the accelerator tunnel is in maintenance mode</details> </guidance> </pv> <pv name="AccODH-AT:ODH-O2iM-009:Disconnected"> <description>Monitor lost connection</description> - <latching>true</latching> - <annunciating>true</annunciating> + <latching>false</latching> + <annunciating>false</annunciating> <guidance> <title>[Operator Action]</title> - <details>AccODH-AT:ODH-O2iM-009 in the HBL section of the accelerator tunnel has lost connection + <details>AccODH-AT:ODH-O2iM-009 monitoring HBL section of the accelerator tunnel has lost connection - MCR/Gate guard/Cryo team: Inform PSS team</details> </guidance> </pv> <pv name="AccODH-AT:ODH-O2iM-009:Failure"> <description>Monitor failure</description> - <latching>true</latching> - <annunciating>true</annunciating> + <latching>false</latching> + <annunciating>false</annunciating> <guidance> <title>[Operator Action]</title> - <details>AccODH-AT:ODH-O2iM-009 in the HBL section of the accelerator tunnel failure + <details>AccODH-AT:ODH-O2iM-009 monitoring HBL section of the accelerator tunnel failure - MCR/Gate guard/Cryo team: Inform PSS team</details> </guidance> </pv> @@ -1242,7 +1316,7 @@ Call cryo on call <annunciating>false</annunciating> <guidance> <title>[Operator Action]</title> - <details>AccODH-AT:ODH-O2iM-009 in the HBL section of the accelerator tunnel analogue input is out of range + <details>AccODH-AT:ODH-O2iM-009 monitoring HBL section of the accelerator tunnel analogue input is out of range - MCR/Gate guard/Cryo team: Inform PSS team</details> </guidance> </pv> @@ -1250,11 +1324,11 @@ Call cryo on call <component name="O2IM10"> <pv name="AccODH-AT:ODH-O2iM-010:O2Below18"> <description>ODH Alarm (Oxygen below 18%)</description> - <latching>true</latching> - <annunciating>true</annunciating> + <latching>false</latching> + <annunciating>false</annunciating> <guidance> <title>[Operator Action]</title> - <details>AccODH-AT:ODH-O2iM-010 in HBL section of the accelerator tunnel ODH alarm- O2 less than 18% + <details>AccODH-AT:ODH-O2iM-010 monitoring HBL section of the accelerator tunnel ODH alarm- O2 less than 18% Call cryo on call - MCR: Follow ESS-3216323 - Gate guard: Follow ESS-2124375 @@ -1263,11 +1337,11 @@ Call cryo on call </pv> <pv name="AccODH-AT:ODH-O2iM-010:O2Below19_5"> <description>ODH Warning (Oxygen below 19.5%)</description> - <latching>true</latching> - <annunciating>true</annunciating> + <latching>false</latching> + <annunciating>false</annunciating> <guidance> <title>[Operator Action]</title> - <details>AccODH-AT:ODH-O2iM-010 in HBL section of the accelerator tunnel ODH warning- O2 less than 19.5% + <details>AccODH-AT:ODH-O2iM-010 monitoring HBL section of the accelerator tunnel ODH warning- O2 less than 19.5% Call cryo on call - MCR: Follow ESS-3216323 - Gate guard: Follow ESS-2124375 @@ -1280,26 +1354,26 @@ Call cryo on call <annunciating>false</annunciating> <guidance> <title>[Operator Action]</title> - <details>AccODH-AT:ODH-O2iM-010 in the HBL section of the accelerator tunnel is in maintenance mode</details> + <details>AccODH-AT:ODH-O2iM-010 monitoring HBL section of the accelerator tunnel is in maintenance mode</details> </guidance> </pv> <pv name="AccODH-AT:ODH-O2iM-010:Disconnected"> <description>Monitor lost connection</description> - <latching>true</latching> - <annunciating>true</annunciating> + <latching>false</latching> + <annunciating>false</annunciating> <guidance> <title>[Operator Action]</title> - <details>AccODH-AT:ODH-O2iM-010 in the HBL section of the accelerator tunnel has lost connection + <details>AccODH-AT:ODH-O2iM-010 monitoring HBL section of the accelerator tunnel has lost connection - MCR/Gate guard/Cryo team: Inform PSS team</details> </guidance> </pv> <pv name="AccODH-AT:ODH-O2iM-010:Failure"> <description>Monitor failure</description> - <latching>true</latching> - <annunciating>true</annunciating> + <latching>false</latching> + <annunciating>false</annunciating> <guidance> <title>[Operator Action]</title> - <details>AccODH-AT:ODH-O2iM-010 in the HBL section of the accelerator tunnel failure + <details>AccODH-AT:ODH-O2iM-010 monitoring HBL section of the accelerator tunnel failure - MCR/Gate guard/Cryo team: Inform PSS team</details> </guidance> </pv> @@ -1309,7 +1383,7 @@ Call cryo on call <annunciating>false</annunciating> <guidance> <title>[Operator Action]</title> - <details>AccODH-AT:ODH-O2iM-010 in the HBL section of the accelerator tunnel analogue input is out of range + <details>AccODH-AT:ODH-O2iM-010 monitoring HBL section of the accelerator tunnel analogue input is out of range - MCR/Gate guard/Cryo team: Inform PSS team</details> </guidance> </pv> @@ -1317,11 +1391,11 @@ Call cryo on call <component name="O2IM11"> <pv name="AccODH-AT:ODH-O2iM-011:O2Below18"> <description>ODH Alarm (Oxygen below 18%)</description> - <latching>true</latching> - <annunciating>true</annunciating> + <latching>false</latching> + <annunciating>false</annunciating> <guidance> <title>[Operator Action]</title> - <details>AccODH-AT:ODH-O2iM-011 in HBL section of the accelerator tunnel ODH alarm- O2 less than 18% + <details>AccODH-AT:ODH-O2iM-011 monitoring HBL section of the accelerator tunnel ODH alarm- O2 less than 18% Call cryo on call - MCR: Follow ESS-3216323 - Gate guard: Follow ESS-2124375 @@ -1330,11 +1404,11 @@ Call cryo on call </pv> <pv name="AccODH-AT:ODH-O2iM-011:O2Below19_5"> <description>ODH Warning (Oxygen below 19.5%)</description> - <latching>true</latching> - <annunciating>true</annunciating> + <latching>false</latching> + <annunciating>false</annunciating> <guidance> <title>[Operator Action]</title> - <details>AccODH-AT:ODH-O2iM-011 in HBL section of the accelerator tunnel ODH warning- O2 less than 19.5% + <details>AccODH-AT:ODH-O2iM-011 monitoring HBL section of the accelerator tunnel ODH warning- O2 less than 19.5% Call cryo on call - MCR: Follow ESS-3216323 - Gate guard: Follow ESS-2124375 @@ -1347,26 +1421,26 @@ Call cryo on call <annunciating>false</annunciating> <guidance> <title>[Operator Action]</title> - <details>AccODH-AT:ODH-O2iM-011 in the HBL section of the accelerator tunnel is in maintenance mode</details> + <details>AccODH-AT:ODH-O2iM-011 monitoring HBL section of the accelerator tunnel is in maintenance mode</details> </guidance> </pv> <pv name="AccODH-AT:ODH-O2iM-011:Disconnected"> <description>Monitor lost connection</description> - <latching>true</latching> - <annunciating>true</annunciating> + <latching>false</latching> + <annunciating>false</annunciating> <guidance> <title>[Operator Action]</title> - <details>AccODH-AT:ODH-O2iM-011 in the HBL section of the accelerator tunnel has lost connection + <details>AccODH-AT:ODH-O2iM-011 monitoring HBL section of the accelerator tunnel has lost connection - MCR/Gate guard/Cryo team: Inform PSS team</details> </guidance> </pv> <pv name="AccODH-AT:ODH-O2iM-011:Failure"> <description>Monitor failure</description> - <latching>true</latching> - <annunciating>true</annunciating> + <latching>false</latching> + <annunciating>false</annunciating> <guidance> <title>[Operator Action]</title> - <details>AccODH-AT:ODH-O2iM-011 in the HBL section of the accelerator tunnel failure + <details>AccODH-AT:ODH-O2iM-011 monitoring HBL section of the accelerator tunnel failure - MCR/Gate guard/Cryo team: Inform PSS team</details> </guidance> </pv> @@ -1376,7 +1450,7 @@ Call cryo on call <annunciating>false</annunciating> <guidance> <title>[Operator Action]</title> - <details>AccODH-AT:ODH-O2iM-011 in the HBL section of the accelerator tunnel analogue input is out of range + <details>AccODH-AT:ODH-O2iM-011 monitoring HBL section of the accelerator tunnel analogue input is out of range - MCR/Gate guard/Cryo team: Inform PSS team</details> </guidance> </pv> @@ -1384,11 +1458,11 @@ Call cryo on call <component name="O2IM12"> <pv name="AccODH-AT:ODH-O2iM-012:O2Below18"> <description>ODH Alarm (Oxygen below 18%)</description> - <latching>true</latching> - <annunciating>true</annunciating> + <latching>false</latching> + <annunciating>false</annunciating> <guidance> <title>[Operator Action]</title> - <details>AccODH-AT:ODH-O2iM-012 in HBL section of the accelerator tunnel ODH alarm- O2 less than 18% + <details>AccODH-AT:ODH-O2iM-012 monitoring HBL section of the accelerator tunnel ODH alarm- O2 less than 18% Call cryo on call - MCR: Follow ESS-3216323 - Gate guard: Follow ESS-2124375 @@ -1397,11 +1471,11 @@ Call cryo on call </pv> <pv name="AccODH-AT:ODH-O2iM-012:O2Below19_5"> <description>ODH Warning (Oxygen below 19.5%)</description> - <latching>true</latching> - <annunciating>true</annunciating> + <latching>false</latching> + <annunciating>false</annunciating> <guidance> <title>[Operator Action]</title> - <details>AccODH-AT:ODH-O2iM-012 in HBL section of the accelerator tunnel ODH warning- O2 less than 19.5% + <details>AccODH-AT:ODH-O2iM-012 monitoring HBL section of the accelerator tunnel ODH warning- O2 less than 19.5% Call cryo on call - MCR: Follow ESS-3216323 - Gate guard: Follow ESS-2124375 @@ -1414,26 +1488,26 @@ Call cryo on call <annunciating>false</annunciating> <guidance> <title>[Operator Action]</title> - <details>AccODH-AT:ODH-O2iM-012 in the HBL section of the accelerator tunnel is in maintenance mode</details> + <details>AccODH-AT:ODH-O2iM-012 monitoring HBL section of the accelerator tunnel is in maintenance mode</details> </guidance> </pv> <pv name="AccODH-AT:ODH-O2iM-012:Disconnected"> <description>Monitor lost connection</description> - <latching>true</latching> - <annunciating>true</annunciating> + <latching>false</latching> + <annunciating>false</annunciating> <guidance> <title>[Operator Action]</title> - <details>AccODH-AT:ODH-O2iM-012 in the HBL section of the accelerator tunnel has lost connection + <details>AccODH-AT:ODH-O2iM-012 monitoring HBL section of the accelerator tunnel has lost connection - MCR/Gate guard/Cryo team: Inform PSS team</details> </guidance> </pv> <pv name="AccODH-AT:ODH-O2iM-012:Failure"> <description>Monitor failure</description> - <latching>true</latching> - <annunciating>true</annunciating> + <latching>false</latching> + <annunciating>false</annunciating> <guidance> <title>[Operator Action]</title> - <details>AccODH-AT:ODH-O2iM-012 in the HBL section of the accelerator tunnel failure + <details>AccODH-AT:ODH-O2iM-012 monitoring HBL section of the accelerator tunnel failure - MCR/Gate guard/Cryo team: Inform PSS team</details> </guidance> </pv> @@ -1443,7 +1517,7 @@ Call cryo on call <annunciating>false</annunciating> <guidance> <title>[Operator Action]</title> - <details>AccODH-AT:ODH-O2iM-012 in the HBL section of the accelerator tunnel analogue input is out of range + <details>AccODH-AT:ODH-O2iM-012 monitoring HBL section of the accelerator tunnel analogue input is out of range - MCR/Gate guard/Cryo team: Inform PSS team</details> </guidance> </pv> @@ -1451,11 +1525,11 @@ Call cryo on call <component name="O2IM13"> <pv name="AccODH-AT:ODH-O2iM-013:O2Below18"> <description>ODH Alarm (Oxygen below 18%)</description> - <latching>true</latching> - <annunciating>true</annunciating> + <latching>false</latching> + <annunciating>false</annunciating> <guidance> <title>[Operator Action]</title> - <details>AccODH-AT:ODH-O2iM-013 in HBL section of the accelerator tunnel ODH alarm- O2 less than 18% + <details>AccODH-AT:ODH-O2iM-013 monitoring HBL section of the accelerator tunnel ODH alarm- O2 less than 18% Call cryo on call - MCR: Follow ESS-3216323 - Gate guard: Follow ESS-2124375 @@ -1464,11 +1538,11 @@ Call cryo on call </pv> <pv name="AccODH-AT:ODH-O2iM-013:O2Below19_5"> <description>ODH Warning (Oxygen below 19.5%)</description> - <latching>true</latching> - <annunciating>true</annunciating> + <latching>false</latching> + <annunciating>false</annunciating> <guidance> <title>[Operator Action]</title> - <details>AccODH-AT:ODH-O2iM-013 in HBL section of the accelerator tunnel ODH warning- O2 less than 19.5% + <details>AccODH-AT:ODH-O2iM-013 monitoring HBL section of the accelerator tunnel ODH warning- O2 less than 19.5% Call cryo on call - MCR: Follow ESS-3216323 - Gate guard: Follow ESS-2124375 @@ -1481,26 +1555,26 @@ Call cryo on call <annunciating>false</annunciating> <guidance> <title>[Operator Action]</title> - <details>AccODH-AT:ODH-O2iM-013 in the HBL section of the accelerator tunnel is in maintenance mode</details> + <details>AccODH-AT:ODH-O2iM-013 monitoring HBL section of the accelerator tunnel is in maintenance mode</details> </guidance> </pv> <pv name="AccODH-AT:ODH-O2iM-013:Disconnected"> <description>Monitor lost connection</description> - <latching>true</latching> - <annunciating>true</annunciating> + <latching>false</latching> + <annunciating>false</annunciating> <guidance> <title>[Operator Action]</title> - <details>AccODH-AT:ODH-O2iM-013 in the HBL section of the accelerator tunnel has lost connection + <details>AccODH-AT:ODH-O2iM-013 monitoring HBL section of the accelerator tunnel has lost connection - MCR/Gate guard/Cryo team: Inform PSS team</details> </guidance> </pv> <pv name="AccODH-AT:ODH-O2iM-013:Failure"> <description>Monitor failure</description> - <latching>true</latching> - <annunciating>true</annunciating> + <latching>false</latching> + <annunciating>false</annunciating> <guidance> <title>[Operator Action]</title> - <details>AccODH-AT:ODH-O2iM-013 in the HBL section of the accelerator tunnel failure + <details>AccODH-AT:ODH-O2iM-013 monitoring HBL section of the accelerator tunnel failure - MCR/Gate guard/Cryo team: Inform PSS team</details> </guidance> </pv> @@ -1510,7 +1584,7 @@ Call cryo on call <annunciating>false</annunciating> <guidance> <title>[Operator Action]</title> - <details>AccODH-AT:ODH-O2iM-013 in the HBL section of the accelerator tunnel analogue input is out of range + <details>AccODH-AT:ODH-O2iM-013 monitoring HBL section of the accelerator tunnel analogue input is out of range - MCR/Gate guard/Cryo team: Inform PSS team</details> </guidance> </pv> @@ -1518,11 +1592,11 @@ Call cryo on call <component name="O2IM14"> <pv name="AccODH-AT:ODH-O2iM-014:O2Below18"> <description>ODH Alarm (Oxygen below 18%)</description> - <latching>true</latching> - <annunciating>true</annunciating> + <latching>false</latching> + <annunciating>false</annunciating> <guidance> <title>[Operator Action]</title> - <details>AccODH-AT:ODH-O2iM-014 in A2T section of the accelerator tunnel ODH alarm- O2 less than 18% + <details>AccODH-AT:ODH-O2iM-014 monitoring A2T section of the accelerator tunnel ODH alarm- O2 less than 18% Call cryo on call - MCR: Follow ESS-3216323 - Gate guard: Follow ESS-2124375 @@ -1531,11 +1605,11 @@ Call cryo on call </pv> <pv name="AccODH-AT:ODH-O2iM-014:O2Below19_5"> <description>ODH Warning (Oxygen below 19.5%)</description> - <latching>true</latching> - <annunciating>true</annunciating> + <latching>false</latching> + <annunciating>false</annunciating> <guidance> <title>[Operator Action]</title> - <details>AccODH-AT:ODH-O2iM-014 in A2T section of the accelerator tunnel ODH warning- O2 less than 19.5% + <details>AccODH-AT:ODH-O2iM-014 monitoring A2T section of the accelerator tunnel ODH warning- O2 less than 19.5% Call cryo on call - MCR: Follow ESS-3216323 - Gate guard: Follow ESS-2124375 @@ -1548,26 +1622,26 @@ Call cryo on call <annunciating>false</annunciating> <guidance> <title>[Operator Action]</title> - <details>AccODH-AT:ODH-O2iM-014 in the A2T section of the accelerator tunnel is in maintenance mode</details> + <details>AccODH-AT:ODH-O2iM-014 monitoring A2T section of the accelerator tunnel is in maintenance mode</details> </guidance> </pv> <pv name="AccODH-AT:ODH-O2iM-014:Disconnected"> <description>Monitor lost connection</description> - <latching>true</latching> - <annunciating>true</annunciating> + <latching>false</latching> + <annunciating>false</annunciating> <guidance> <title>[Operator Action]</title> - <details>AccODH-AT:ODH-O2iM-014 in the A2T section of the accelerator tunnel has lost connection + <details>AccODH-AT:ODH-O2iM-014 monitoring A2T section of the accelerator tunnel has lost connection - MCR/Gate guard/Cryo team: Inform PSS team</details> </guidance> </pv> <pv name="AccODH-AT:ODH-O2iM-014:Failure"> <description>Monitor failure</description> - <latching>true</latching> - <annunciating>true</annunciating> + <latching>false</latching> + <annunciating>false</annunciating> <guidance> <title>[Operator Action]</title> - <details>AccODH-AT:ODH-O2iM-014 in the A2T section of the accelerator tunnel failure + <details>AccODH-AT:ODH-O2iM-014 monitoring A2T section of the accelerator tunnel failure - MCR/Gate guard/Cryo team: Inform PSS team</details> </guidance> </pv> @@ -1577,7 +1651,7 @@ Call cryo on call <annunciating>false</annunciating> <guidance> <title>[Operator Action]</title> - <details>AccODH-AT:ODH-O2iM-014 in the A2T section of the accelerator tunnel analogue input is out of range + <details>AccODH-AT:ODH-O2iM-014 monitoring A2T section of the accelerator tunnel analogue input is out of range - MCR/Gate guard/Cryo team: Inform PSS team</details> </guidance> </pv> @@ -1586,8 +1660,8 @@ Call cryo on call <component name="PSS"> <pv name="AccODH-AT::PssAlmSts_Failure"> <description>Output failure</description> - <latching>true</latching> - <annunciating>true</annunciating> + <latching>false</latching> + <annunciating>false</annunciating> <guidance> <title>[Operator Action]</title> <details>PSS alarm interface failure @@ -1598,8 +1672,8 @@ Call cryo on call <component name="RSL"> <pv name="AccODH-AT:ODH-RSL-001:Failure"> <description>Device failure</description> - <latching>true</latching> - <annunciating>true</annunciating> + <latching>false</latching> + <annunciating>false</annunciating> <guidance> <title>[Operator Action]</title> <details>AccODH-AT:ODH-RSL-001 in NCL section of the accelerator tunnel failure @@ -1608,8 +1682,8 @@ Call cryo on call </pv> <pv name="AccODH-AT:ODH-RSL-002:Failure"> <description>Device failure</description> - <latching>true</latching> - <annunciating>true</annunciating> + <latching>false</latching> + <annunciating>false</annunciating> <guidance> <title>[Operator Action]</title> <details>AccODH-AT:ODH-RSL-002 in NCL section of the accelerator tunnel failure @@ -1618,8 +1692,8 @@ Call cryo on call </pv> <pv name="AccODH-AT:ODH-RSL-003:Failure"> <description>Device failure</description> - <latching>true</latching> - <annunciating>true</annunciating> + <latching>false</latching> + <annunciating>false</annunciating> <guidance> <title>[Operator Action]</title> <details>AccODH-AT:ODH-RSL-003 in NCL section of the accelerator tunnel failure @@ -1628,8 +1702,8 @@ Call cryo on call </pv> <pv name="AccODH-AT:ODH-RSL-004:Failure"> <description>Device failure</description> - <latching>true</latching> - <annunciating>true</annunciating> + <latching>false</latching> + <annunciating>false</annunciating> <guidance> <title>[Operator Action]</title> <details>AccODH-AT:ODH-RSL-004 in NCL section of the accelerator tunnel failure @@ -1638,8 +1712,8 @@ Call cryo on call </pv> <pv name="AccODH-AT:ODH-RSL-005:Failure"> <description>Device failure</description> - <latching>true</latching> - <annunciating>true</annunciating> + <latching>false</latching> + <annunciating>false</annunciating> <guidance> <title>[Operator Action]</title> <details>AccODH-AT:ODH-RSL-005 in NCL section of the accelerator tunnel failure @@ -1648,8 +1722,8 @@ Call cryo on call </pv> <pv name="AccODH-AT:ODH-RSL-006:Failure"> <description>Device failure</description> - <latching>true</latching> - <annunciating>true</annunciating> + <latching>false</latching> + <annunciating>false</annunciating> <guidance> <title>[Operator Action]</title> <details>AccODH-AT:ODH-RSL-006 in SPK section of the accelerator tunnel failure @@ -1658,8 +1732,8 @@ Call cryo on call </pv> <pv name="AccODH-AT:ODH-RSL-007:Failure"> <description>Device failure</description> - <latching>true</latching> - <annunciating>true</annunciating> + <latching>false</latching> + <annunciating>false</annunciating> <guidance> <title>[Operator Action]</title> <details>AccODH-AT:ODH-RSL-007 in SPK section of the accelerator tunnel failure @@ -1668,8 +1742,8 @@ Call cryo on call </pv> <pv name="AccODH-AT:ODH-RSL-008:Failure"> <description>Device failure</description> - <latching>true</latching> - <annunciating>true</annunciating> + <latching>false</latching> + <annunciating>false</annunciating> <guidance> <title>[Operator Action]</title> <details>AccODH-AT:ODH-RSL-008 in MBL section of the accelerator tunnel failure @@ -1678,8 +1752,8 @@ Call cryo on call </pv> <pv name="AccODH-AT:ODH-RSL-009:Failure"> <description>Device failure</description> - <latching>true</latching> - <annunciating>true</annunciating> + <latching>false</latching> + <annunciating>false</annunciating> <guidance> <title>[Operator Action]</title> <details>AccODH-AT:ODH-RSL-009 in EEx1 section of the accelerator tunnel failure @@ -1688,8 +1762,8 @@ Call cryo on call </pv> <pv name="AccODH-AT:ODH-RSL-010:Failure"> <description>Device failure</description> - <latching>true</latching> - <annunciating>true</annunciating> + <latching>false</latching> + <annunciating>false</annunciating> <guidance> <title>[Operator Action]</title> <details>AccODH-AT:ODH-RSL-010 in EEx1 section of the accelerator tunnel failure @@ -1698,8 +1772,8 @@ Call cryo on call </pv> <pv name="AccODH-AT:ODH-RSL-011:Failure"> <description>Device failure</description> - <latching>true</latching> - <annunciating>true</annunciating> + <latching>false</latching> + <annunciating>false</annunciating> <guidance> <title>[Operator Action]</title> <details>AccODH-AT:ODH-RSL-011 in MBL section of the accelerator tunnel failure @@ -1708,8 +1782,8 @@ Call cryo on call </pv> <pv name="AccODH-AT:ODH-RSL-012:Failure"> <description>Device failure</description> - <latching>true</latching> - <annunciating>true</annunciating> + <latching>false</latching> + <annunciating>false</annunciating> <guidance> <title>[Operator Action]</title> <details>AccODH-AT:ODH-RSL-012 in MBL section of the accelerator tunnel failure @@ -1718,8 +1792,8 @@ Call cryo on call </pv> <pv name="AccODH-AT:ODH-RSL-013:Failure"> <description>Device failure</description> - <latching>true</latching> - <annunciating>true</annunciating> + <latching>false</latching> + <annunciating>false</annunciating> <guidance> <title>[Operator Action]</title> <details>AccODH-AT:ODH-RSL-013 in HBL section of the accelerator tunnel failure @@ -1728,8 +1802,8 @@ Call cryo on call </pv> <pv name="AccODH-AT:ODH-RSL-014:Failure"> <description>Device failure</description> - <latching>true</latching> - <annunciating>true</annunciating> + <latching>false</latching> + <annunciating>false</annunciating> <guidance> <title>[Operator Action]</title> <details>AccODH-AT:ODH-RSL-014 in HBL section of the accelerator tunnel failure @@ -1738,8 +1812,8 @@ Call cryo on call </pv> <pv name="AccODH-AT:ODH-RSL-015:Failure"> <description>Device failure</description> - <latching>true</latching> - <annunciating>true</annunciating> + <latching>false</latching> + <annunciating>false</annunciating> <guidance> <title>[Operator Action]</title> <details>AccODH-AT:ODH-RSL-015 in HBL section of the accelerator tunnel failure @@ -1748,8 +1822,8 @@ Call cryo on call </pv> <pv name="AccODH-AT:ODH-RSL-016:Failure"> <description>Device failure</description> - <latching>true</latching> - <annunciating>true</annunciating> + <latching>false</latching> + <annunciating>false</annunciating> <guidance> <title>[Operator Action]</title> <details>AccODH-AT:ODH-RSL-016 in EEx2 section of the accelerator tunnel failure @@ -1758,8 +1832,8 @@ Call cryo on call </pv> <pv name="AccODH-AT:ODH-RSL-017:Failure"> <description>Device failure</description> - <latching>true</latching> - <annunciating>true</annunciating> + <latching>false</latching> + <annunciating>false</annunciating> <guidance> <title>[Operator Action]</title> <details>AccODH-AT:ODH-RSL-017 in EEx2 section of the accelerator tunnel failure @@ -1768,8 +1842,8 @@ Call cryo on call </pv> <pv name="AccODH-AT:ODH-RSL-018:Failure"> <description>Device failure</description> - <latching>true</latching> - <annunciating>true</annunciating> + <latching>false</latching> + <annunciating>false</annunciating> <guidance> <title>[Operator Action]</title> <details>AccODH-AT:ODH-RSL-018 in HBL section of the accelerator tunnel failure @@ -1778,8 +1852,8 @@ Call cryo on call </pv> <pv name="AccODH-AT:ODH-RSL-019:Failure"> <description>Device failure</description> - <latching>true</latching> - <annunciating>true</annunciating> + <latching>false</latching> + <annunciating>false</annunciating> <guidance> <title>[Operator Action]</title> <details>AccODH-AT:ODH-RSL-019 in HBL section of the accelerator tunnel failure @@ -1788,8 +1862,8 @@ Call cryo on call </pv> <pv name="AccODH-AT:ODH-RSL-020:Failure"> <description>Device failure</description> - <latching>true</latching> - <annunciating>true</annunciating> + <latching>false</latching> + <annunciating>false</annunciating> <guidance> <title>[Operator Action]</title> <details>AccODH-AT:ODH-RSL-020 in HBL section of the accelerator tunnel failure @@ -1798,8 +1872,8 @@ Call cryo on call </pv> <pv name="AccODH-AT:ODH-RSL-021:Failure"> <description>Device failure</description> - <latching>true</latching> - <annunciating>true</annunciating> + <latching>false</latching> + <annunciating>false</annunciating> <guidance> <title>[Operator Action]</title> <details>AccODH-AT:ODH-RSL-021 in HBL section of the accelerator tunnel failure @@ -1808,8 +1882,8 @@ Call cryo on call </pv> <pv name="AccODH-AT:ODH-RSL-022:Failure"> <description>Device failure</description> - <latching>true</latching> - <annunciating>true</annunciating> + <latching>false</latching> + <annunciating>false</annunciating> <guidance> <title>[Operator Action]</title> <details>AccODH-AT:ODH-RSL-022 in HEBT loading bay section of the accelerator tunnel failure @@ -1818,8 +1892,8 @@ Call cryo on call </pv> <pv name="AccODH-AT:ODH-RSL-023:Failure"> <description>Device failure</description> - <latching>true</latching> - <annunciating>true</annunciating> + <latching>false</latching> + <annunciating>false</annunciating> <guidance> <title>[Operator Action]</title> <details>AccODH-AT:ODH-RSL-023 in HEBT loading bay section of the accelerator tunnel failure @@ -1828,8 +1902,8 @@ Call cryo on call </pv> <pv name="AccODH-AT:ODH-RSL-024:Failure"> <description>Device failure</description> - <latching>true</latching> - <annunciating>true</annunciating> + <latching>false</latching> + <annunciating>false</annunciating> <guidance> <title>[Operator Action]</title> <details>AccODH-AT:ODH-RSL-024 in HEBT loading bay section of the accelerator tunnel failure @@ -1838,8 +1912,8 @@ Call cryo on call </pv> <pv name="AccODH-AT:ODH-RSL-025:Failure"> <description>Device failure</description> - <latching>true</latching> - <annunciating>true</annunciating> + <latching>false</latching> + <annunciating>false</annunciating> <guidance> <title>[Operator Action]</title> <details>AccODH-AT:ODH-RSL-025 in HEBT section of the accelerator tunnel failure @@ -1848,8 +1922,8 @@ Call cryo on call </pv> <pv name="AccODH-AT:ODH-RSL-026:Failure"> <description>Device failure</description> - <latching>true</latching> - <annunciating>true</annunciating> + <latching>false</latching> + <annunciating>false</annunciating> <guidance> <title>[Operator Action]</title> <details>AccODH-AT:ODH-RSL-026 in EEx3 section of the accelerator tunnel failure @@ -1858,8 +1932,8 @@ Call cryo on call </pv> <pv name="AccODH-AT:ODH-RSL-027:Failure"> <description>Device failure</description> - <latching>true</latching> - <annunciating>true</annunciating> + <latching>false</latching> + <annunciating>false</annunciating> <guidance> <title>[Operator Action]</title> <details>AccODH-AT:ODH-RSL-027 in EEx3 section of the accelerator tunnel failure @@ -1868,8 +1942,8 @@ Call cryo on call </pv> <pv name="AccODH-AT:ODH-RSL-028:Failure"> <description>Device failure</description> - <latching>true</latching> - <annunciating>true</annunciating> + <latching>false</latching> + <annunciating>false</annunciating> <guidance> <title>[Operator Action]</title> <details>AccODH-AT:ODH-RSL-028 in HEBT loading bay section of the accelerator tunnel failure @@ -1878,8 +1952,8 @@ Call cryo on call </pv> <pv name="AccODH-AT:ODH-RSL-029:Failure"> <description>Device failure</description> - <latching>true</latching> - <annunciating>true</annunciating> + <latching>false</latching> + <annunciating>false</annunciating> <guidance> <title>[Operator Action]</title> <details>AccODH-AT:ODH-RSL-029 in HEBT section of the accelerator tunnel failure @@ -1888,8 +1962,8 @@ Call cryo on call </pv> <pv name="AccODH-AT:ODH-RSL-030:Failure"> <description>Device failure</description> - <latching>true</latching> - <annunciating>true</annunciating> + <latching>false</latching> + <annunciating>false</annunciating> <guidance> <title>[Operator Action]</title> <details>AccODH-AT:ODH-RSL-030 in HEBT section of the accelerator tunnel failure @@ -1898,8 +1972,8 @@ Call cryo on call </pv> <pv name="AccODH-AT:ODH-RSL-031:Failure"> <description>Device failure</description> - <latching>true</latching> - <annunciating>true</annunciating> + <latching>false</latching> + <annunciating>false</annunciating> <guidance> <title>[Operator Action]</title> <details>AccODH-AT:ODH-RSL-031 in HEBT section of the accelerator tunnel failure @@ -1908,8 +1982,8 @@ Call cryo on call </pv> <pv name="AccODH-AT:ODH-RSL-032:Failure"> <description>Device failure</description> - <latching>true</latching> - <annunciating>true</annunciating> + <latching>false</latching> + <annunciating>false</annunciating> <guidance> <title>[Operator Action]</title> <details>AccODH-AT:ODH-RSL-032 in DL section of the accelerator tunnel failure @@ -1918,18 +1992,18 @@ Call cryo on call </pv> <pv name="AccODH-AT:ODH-RSL-033:Failure"> <description>Device failure</description> - <latching>true</latching> - <annunciating>true</annunciating> + <latching>false</latching> + <annunciating>false</annunciating> <guidance> <title>[Operator Action]</title> - <details>AccODH-AT:ODH-RSL-033 in EEx4 section of the accelerator tunnel failure + <details>AccODH-AT:ODH-RSL-033 in EEx4 section of the accelerator tunnel failure - MCR/Gate guard/Cryo team: Inform PSS team</details> </guidance> </pv> <pv name="AccODH-AT:ODH-RSL-034:Failure"> <description>Device failure</description> - <latching>true</latching> - <annunciating>true</annunciating> + <latching>false</latching> + <annunciating>false</annunciating> <guidance> <title>[Operator Action]</title> <details>AccODH-AT:ODH-RSL-034 in EEx4 section of the accelerator tunnel failure @@ -1938,18 +2012,18 @@ Call cryo on call </pv> <pv name="AccODH-AT:ODH-RSL-035:Failure"> <description>Device failure</description> - <latching>true</latching> - <annunciating>true</annunciating> + <latching>false</latching> + <annunciating>false</annunciating> <guidance> <title>[Operator Action]</title> - <details>AccODH-AT:ODH-RSL-035 in DL section of the accelerator tunnel failure + <details>AccODH-AT:ODH-RSL-035 in DL section of the accelerator tunnel failure - MCR/Gate guard/Cryo team: Inform PSS team</details> </guidance> </pv> <pv name="AccODH-AT:ODH-RSL-036:Failure"> <description>Device failure</description> - <latching>true</latching> - <annunciating>true</annunciating> + <latching>false</latching> + <annunciating>false</annunciating> <guidance> <title>[Operator Action]</title> <details>AccODH-AT:ODH-RSL-036 in A2T section of the accelerator tunnel failure @@ -1958,8 +2032,8 @@ Call cryo on call </pv> <pv name="AccODH-AT:ODH-RSL-037:Failure"> <description>Device failure</description> - <latching>true</latching> - <annunciating>true</annunciating> + <latching>false</latching> + <annunciating>false</annunciating> <guidance> <title>[Operator Action]</title> <details>AccODH-AT:ODH-RSL-037 in A2T section of the accelerator tunnel failure @@ -1971,7 +2045,7 @@ Call cryo on call <component name="CTLG"> <pv name="CTLG-CS:ODH-Area:Alrm"> <description>Zone ODH Alarm (Oxygen below 18%)</description> - <latching>true</latching> + <latching>false</latching> <annunciating>true</annunciating> <guidance> <title>[Operator Action]</title> @@ -1984,7 +2058,7 @@ Call cryo on call </pv> <pv name="CTLG-CS:ODH-Area:Warning"> <description>Zone ODH Warning (Oxygen below 19.5%)</description> - <latching>true</latching> + <latching>false</latching> <annunciating>true</annunciating> <guidance> <title>[Operator Action]</title> @@ -1997,7 +2071,7 @@ Call cryo on call </pv> <pv name="CTLG-CS:ODH-Area:Error"> <description>Zone oxygen monitor error</description> - <latching>true</latching> + <latching>false</latching> <annunciating>true</annunciating> <guidance> <title>[Operator Action]</title> @@ -2069,7 +2143,7 @@ Call cryo on call <component name="O2IM20"> <pv name="CTLG-CS:ODH-O2iM-20:O2Below18"> <description>ODH Alarm (Oxygen below 18%)</description> - <latching>true</latching> + <latching>false</latching> <annunciating>false</annunciating> <guidance> <title>[Operator Action]</title> @@ -2082,7 +2156,7 @@ Call cryo on call </pv> <pv name="CTLG-CS:ODH-O2iM-20:O2Below19_5"> <description>ODH Warning (Oxygen below 19.5%)</description> - <latching>true</latching> + <latching>false</latching> <annunciating>false</annunciating> <guidance> <title>[Operator Action]</title> @@ -2104,7 +2178,7 @@ Call cryo on call </pv> <pv name="CTLG-CS:ODH-O2iM-20:Disconnected"> <description>Monitor lost connection</description> - <latching>true</latching> + <latching>false</latching> <annunciating>false</annunciating> <guidance> <title>[Operator Action]</title> @@ -2114,7 +2188,7 @@ Call cryo on call </pv> <pv name="CTLG-CS:ODH-O2iM-20:Failure"> <description>Monitor failure</description> - <latching>true</latching> + <latching>false</latching> <annunciating>false</annunciating> <guidance> <title>[Operator Action]</title> @@ -2136,7 +2210,7 @@ Call cryo on call <component name="O2IM21"> <pv name="CTLG-CS:ODH-O2iM-21:O2Below18"> <description>ODH Alarm (Oxygen below 18%)</description> - <latching>true</latching> + <latching>false</latching> <annunciating>false</annunciating> <guidance> <title>[Operator Action]</title> @@ -2149,7 +2223,7 @@ Call cryo on call </pv> <pv name="CTLG-CS:ODH-O2iM-21:O2Below19_5"> <description>ODH Warning (Oxygen below 19.5%)</description> - <latching>true</latching> + <latching>false</latching> <annunciating>false</annunciating> <guidance> <title>[Operator Action]</title> @@ -2171,7 +2245,7 @@ Call cryo on call </pv> <pv name="CTLG-CS:ODH-O2iM-21:Disconnected"> <description>Monitor lost connection</description> - <latching>true</latching> + <latching>false</latching> <annunciating>false</annunciating> <guidance> <title>[Operator Action]</title> @@ -2181,7 +2255,7 @@ Call cryo on call </pv> <pv name="CTLG-CS:ODH-O2iM-21:Failure"> <description>Monitor failure</description> - <latching>true</latching> + <latching>false</latching> <annunciating>false</annunciating> <guidance> <title>[Operator Action]</title> @@ -2203,7 +2277,7 @@ Call cryo on call <component name="O2IM22"> <pv name="CTLG-CS:ODH-O2iM-22:O2Below18"> <description>ODH Alarm (Oxygen below 18%)</description> - <latching>true</latching> + <latching>false</latching> <annunciating>false</annunciating> <guidance> <title>[Operator Action]</title> @@ -2216,7 +2290,7 @@ Call cryo on call </pv> <pv name="CTLG-CS:ODH-O2iM-22:O2Below19_5"> <description>ODH Warning (Oxygen below 19.5%)</description> - <latching>true</latching> + <latching>false</latching> <annunciating>false</annunciating> <guidance> <title>[Operator Action]</title> @@ -2238,7 +2312,7 @@ Call cryo on call </pv> <pv name="CTLG-CS:ODH-O2iM-22:Disconnected"> <description>Monitor lost connection</description> - <latching>true</latching> + <latching>false</latching> <annunciating>false</annunciating> <guidance> <title>[Operator Action]</title> @@ -2248,7 +2322,7 @@ Call cryo on call </pv> <pv name="CTLG-CS:ODH-O2iM-22:Failure"> <description>Monitor failure</description> - <latching>true</latching> + <latching>false</latching> <annunciating>false</annunciating> <guidance> <title>[Operator Action]</title> @@ -2272,7 +2346,7 @@ Call cryo on call <component name="CXH"> <pv name="CXB-CXH:ODH-Area:Alrm"> <description>Zone ODH Alarm (Oxygen below 18%)</description> - <latching>true</latching> + <latching>false</latching> <annunciating>true</annunciating> <guidance> <title>[Operator Action]</title> @@ -2285,7 +2359,7 @@ Call cryo on call </pv> <pv name="CXB-CXH:ODH-Area:Warning"> <description>Zone ODH Warning (Oxygen below 19.5%)</description> - <latching>true</latching> + <latching>false</latching> <annunciating>true</annunciating> <guidance> <title>[Operator Action]</title> @@ -2298,7 +2372,7 @@ Call cryo on call </pv> <pv name="CXB-CXH:ODH-Area:Error"> <description>Zone oxygen monitor error</description> - <latching>true</latching> + <latching>false</latching> <annunciating>true</annunciating> <guidance> <title>[Operator Action]</title> @@ -2370,7 +2444,7 @@ Call cryo on call <component name="O2IM13"> <pv name="CXB-CXH:ODH-O2iM-13:O2Below18"> <description>ODH Alarm (Oxygen below 18%)</description> - <latching>true</latching> + <latching>false</latching> <annunciating>false</annunciating> <guidance> <title>[Operator Action]</title> @@ -2383,7 +2457,7 @@ Call cryo on call </pv> <pv name="CXB-CXH:ODH-O2iM-13:O2Below19_5"> <description>ODH Warning (Oxygen below 19.5%)</description> - <latching>true</latching> + <latching>false</latching> <annunciating>false</annunciating> <guidance> <title>[Operator Action]</title> @@ -2405,7 +2479,7 @@ Call cryo on call </pv> <pv name="CXB-CXH:ODH-O2iM-13:Disconnected"> <description>Monitor lost connection</description> - <latching>true</latching> + <latching>false</latching> <annunciating>false</annunciating> <guidance> <title>[Operator Action]</title> @@ -2415,7 +2489,7 @@ Call cryo on call </pv> <pv name="CXB-CXH:ODH-O2iM-13:Failure"> <description>Monitor failure</description> - <latching>true</latching> + <latching>false</latching> <annunciating>false</annunciating> <guidance> <title>[Operator Action]</title> @@ -2437,7 +2511,7 @@ Call cryo on call <component name="O2IM14"> <pv name="CXB-CXH:ODH-O2iM-14:O2Below18"> <description>ODH Alarm (Oxygen below 18%)</description> - <latching>true</latching> + <latching>false</latching> <annunciating>false</annunciating> <guidance> <title>[Operator Action]</title> @@ -2450,7 +2524,7 @@ Call cryo on call </pv> <pv name="CXB-CXH:ODH-O2iM-14:O2Below19_5"> <description>ODH Warning (Oxygen below 19.5%)</description> - <latching>true</latching> + <latching>false</latching> <annunciating>false</annunciating> <guidance> <title>[Operator Action]</title> @@ -2472,7 +2546,7 @@ Call cryo on call </pv> <pv name="CXB-CXH:ODH-O2iM-14:Disconnected"> <description>Monitor lost connection</description> - <latching>true</latching> + <latching>false</latching> <annunciating>false</annunciating> <guidance> <title>[Operator Action]</title> @@ -2482,7 +2556,7 @@ Call cryo on call </pv> <pv name="CXB-CXH:ODH-O2iM-14:Failure"> <description>Monitor failure</description> - <latching>true</latching> + <latching>false</latching> <annunciating>false</annunciating> <guidance> <title>[Operator Action]</title> @@ -2504,7 +2578,7 @@ Call cryo on call <component name="O2IM16"> <pv name="CXB-CXH:ODH-O2iM-16:O2Below18"> <description>ODH Alarm (Oxygen below 18%)</description> - <latching>true</latching> + <latching>false</latching> <annunciating>false</annunciating> <guidance> <title>[Operator Action]</title> @@ -2517,7 +2591,7 @@ Call cryo on call </pv> <pv name="CXB-CXH:ODH-O2iM-16:O2Below19_5"> <description>ODH Warning (Oxygen below 19.5%)</description> - <latching>true</latching> + <latching>false</latching> <annunciating>false</annunciating> <guidance> <title>[Operator Action]</title> @@ -2539,7 +2613,7 @@ Call cryo on call </pv> <pv name="CXB-CXH:ODH-O2iM-16:Disconnected"> <description>Monitor lost connection</description> - <latching>true</latching> + <latching>false</latching> <annunciating>false</annunciating> <guidance> <title>[Operator Action]</title> @@ -2549,7 +2623,7 @@ Call cryo on call </pv> <pv name="CXB-CXH:ODH-O2iM-16:Failure"> <description>Monitor failure</description> - <latching>true</latching> + <latching>false</latching> <annunciating>false</annunciating> <guidance> <title>[Operator Action]</title> @@ -2571,7 +2645,7 @@ Call cryo on call <component name="O2IM17"> <pv name="CXB-CXH:ODH-O2iM-17:O2Below18"> <description>ODH Alarm (Oxygen below 18%)</description> - <latching>true</latching> + <latching>false</latching> <annunciating>false</annunciating> <guidance> <title>[Operator Action]</title> @@ -2584,7 +2658,7 @@ Call cryo on call </pv> <pv name="CXB-CXH:ODH-O2iM-17:O2Below19_5"> <description>ODH Warning (Oxygen below 19.5%)</description> - <latching>true</latching> + <latching>false</latching> <annunciating>false</annunciating> <guidance> <title>[Operator Action]</title> @@ -2606,7 +2680,7 @@ Call cryo on call </pv> <pv name="CXB-CXH:ODH-O2iM-17:Disconnected"> <description>Monitor lost connection</description> - <latching>true</latching> + <latching>false</latching> <annunciating>false</annunciating> <guidance> <title>[Operator Action]</title> @@ -2616,7 +2690,7 @@ Call cryo on call </pv> <pv name="CXB-CXH:ODH-O2iM-17:Failure"> <description>Monitor failure</description> - <latching>true</latching> + <latching>false</latching> <annunciating>false</annunciating> <guidance> <title>[Operator Action]</title> @@ -2640,7 +2714,7 @@ Call cryo on call <component name="DS"> <pv name="HCB-DogSh:ODH-Area:Alrm"> <description>Zone ODH Alarm (Oxygen below 18%)</description> - <latching>true</latching> + <latching>false</latching> <annunciating>true</annunciating> <guidance> <title>[Operator Action]</title> @@ -2653,7 +2727,7 @@ Call cryo on call </pv> <pv name="HCB-DogSh:ODH-Area:Warning"> <description>Zone ODH Warning (Oxygen below 19.5%)</description> - <latching>true</latching> + <latching>false</latching> <annunciating>true</annunciating> <guidance> <title>[Operator Action]</title> @@ -2666,7 +2740,7 @@ Call cryo on call </pv> <pv name="HCB-DogSh:ODH-Area:Error"> <description>Zone oxygen monitor error</description> - <latching>true</latching> + <latching>false</latching> <annunciating>true</annunciating> <guidance> <title>[Operator Action]</title> @@ -2738,7 +2812,7 @@ Call cryo on call <component name="O2IM12"> <pv name="HCB-DogSh:ODH-O2iM-12:O2Below18"> <description>ODH Alarm (Oxygen below 18%)</description> - <latching>true</latching> + <latching>false</latching> <annunciating>false</annunciating> <guidance> <title>[Operator Action]</title> @@ -2751,7 +2825,7 @@ Call cryo on call </pv> <pv name="HCB-DogSh:ODH-O2iM-12:O2Below19_5"> <description>ODH Warning (Oxygen below 19.5%)</description> - <latching>true</latching> + <latching>false</latching> <annunciating>false</annunciating> <guidance> <title>[Operator Action]</title> @@ -2773,7 +2847,7 @@ Call cryo on call </pv> <pv name="HCB-DogSh:ODH-O2iM-12:Disconnected"> <description>Monitor lost connection</description> - <latching>true</latching> + <latching>false</latching> <annunciating>false</annunciating> <guidance> <title>[Operator Action]</title> @@ -2783,7 +2857,7 @@ Call cryo on call </pv> <pv name="HCB-DogSh:ODH-O2iM-12:Failure"> <description>Monitor failure</description> - <latching>true</latching> + <latching>false</latching> <annunciating>false</annunciating> <guidance> <title>[Operator Action]</title> @@ -2807,7 +2881,7 @@ Call cryo on call <component name="HCB"> <pv name="HCB-ACH:ODH-Area:Alrm"> <description>Zone ODH Alarm (Oxygen below 18%)</description> - <latching>true</latching> + <latching>false</latching> <annunciating>true</annunciating> <guidance> <title>[Operator Action]</title> @@ -2820,7 +2894,7 @@ Call cryo on call </pv> <pv name="HCB-ACH:ODH-Area:Warning"> <description>Zone ODH Warning (Oxygen below 19.5%)</description> - <latching>true</latching> + <latching>false</latching> <annunciating>true</annunciating> <guidance> <title>[Operator Action]</title> @@ -2833,7 +2907,7 @@ Call cryo on call </pv> <pv name="HCB-ACH:ODH-Area:Error"> <description>Zone oxygen monitor error</description> - <latching>true</latching> + <latching>false</latching> <annunciating>true</annunciating> <guidance> <title>[Operator Action]</title> @@ -2905,7 +2979,7 @@ Call cryo on call <component name="O2IM2"> <pv name="HCB-ACH:ODH-O2iM-2:O2Below18"> <description>ODH Alarm (Oxygen below 18%)</description> - <latching>true</latching> + <latching>false</latching> <annunciating>false</annunciating> <guidance> <title>[Operator Action]</title> @@ -2918,7 +2992,7 @@ Call cryo on call </pv> <pv name="HCB-ACH:ODH-O2iM-2:O2Below19_5"> <description>ODH Warning (Oxygen below 19.5%)</description> - <latching>true</latching> + <latching>false</latching> <annunciating>false</annunciating> <guidance> <title>[Operator Action]</title> @@ -2940,7 +3014,7 @@ Call cryo on call </pv> <pv name="HCB-ACH:ODH-O2iM-2:Disconnected"> <description>Monitor lost connection</description> - <latching>true</latching> + <latching>false</latching> <annunciating>false</annunciating> <guidance> <title>[Operator Action]</title> @@ -2950,7 +3024,7 @@ Call cryo on call </pv> <pv name="HCB-ACH:ODH-O2iM-2:Failure"> <description>Monitor failure</description> - <latching>true</latching> + <latching>false</latching> <annunciating>false</annunciating> <guidance> <title>[Operator Action]</title> @@ -2972,7 +3046,7 @@ Call cryo on call <component name="O2IM3"> <pv name="HCB-ACH:ODH-O2iM-3:O2Below18"> <description>ODH Alarm (Oxygen below 18%)</description> - <latching>true</latching> + <latching>false</latching> <annunciating>false</annunciating> <guidance> <title>[Operator Action]</title> @@ -2985,7 +3059,7 @@ Call cryo on call </pv> <pv name="HCB-ACH:ODH-O2iM-3:O2Below19_5"> <description>ODH Warning (Oxygen below 19.5%)</description> - <latching>true</latching> + <latching>false</latching> <annunciating>false</annunciating> <guidance> <title>[Operator Action]</title> @@ -3007,7 +3081,7 @@ Call cryo on call </pv> <pv name="HCB-ACH:ODH-O2iM-3:Disconnected"> <description>Monitor lost connection</description> - <latching>true</latching> + <latching>false</latching> <annunciating>false</annunciating> <guidance> <title>[Operator Action]</title> @@ -3017,7 +3091,7 @@ Call cryo on call </pv> <pv name="HCB-ACH:ODH-O2iM-3:Failure"> <description>Monitor failure</description> - <latching>true</latching> + <latching>false</latching> <annunciating>false</annunciating> <guidance> <title>[Operator Action]</title> @@ -3039,7 +3113,7 @@ Call cryo on call <component name="O2IM4"> <pv name="HCB-ACH:ODH-O2iM-4:O2Below18"> <description>ODH Alarm (Oxygen below 18%)</description> - <latching>true</latching> + <latching>false</latching> <annunciating>false</annunciating> <guidance> <title>[Operator Action]</title> @@ -3052,7 +3126,7 @@ Call cryo on call </pv> <pv name="HCB-ACH:ODH-O2iM-4:O2Below19_5"> <description>ODH Warning (Oxygen below 19.5%)</description> - <latching>true</latching> + <latching>false</latching> <annunciating>false</annunciating> <guidance> <title>[Operator Action]</title> @@ -3074,7 +3148,7 @@ Call cryo on call </pv> <pv name="HCB-ACH:ODH-O2iM-4:Disconnected"> <description>Monitor lost connection</description> - <latching>true</latching> + <latching>false</latching> <annunciating>false</annunciating> <guidance> <title>[Operator Action]</title> @@ -3084,7 +3158,7 @@ Call cryo on call </pv> <pv name="HCB-ACH:ODH-O2iM-4:Failure"> <description>Monitor failure</description> - <latching>true</latching> + <latching>false</latching> <annunciating>false</annunciating> <guidance> <title>[Operator Action]</title> @@ -3106,7 +3180,7 @@ Call cryo on call <component name="O2IM5"> <pv name="HCB-ACH:ODH-O2iM-5:O2Below18"> <description>ODH Alarm (Oxygen below 18%)</description> - <latching>true</latching> + <latching>false</latching> <annunciating>false</annunciating> <guidance> <title>[Operator Action]</title> @@ -3119,7 +3193,7 @@ Call cryo on call </pv> <pv name="HCB-ACH:ODH-O2iM-5:O2Below19_5"> <description>ODH Warning (Oxygen below 19.5%)</description> - <latching>true</latching> + <latching>false</latching> <annunciating>false</annunciating> <guidance> <title>[Operator Action]</title> @@ -3141,7 +3215,7 @@ Call cryo on call </pv> <pv name="HCB-ACH:ODH-O2iM-5:Disconnected"> <description>Monitor lost connection</description> - <latching>true</latching> + <latching>false</latching> <annunciating>false</annunciating> <guidance> <title>[Operator Action]</title> @@ -3151,7 +3225,7 @@ Call cryo on call </pv> <pv name="HCB-ACH:ODH-O2iM-5:Failure"> <description>Monitor failure</description> - <latching>true</latching> + <latching>false</latching> <annunciating>false</annunciating> <guidance> <title>[Operator Action]</title> @@ -3173,7 +3247,7 @@ Call cryo on call <component name="O2IM6"> <pv name="HCB-TCH:ODH-O2iM-6:O2Below18"> <description>ODH Alarm (Oxygen below 18%)</description> - <latching>true</latching> + <latching>false</latching> <annunciating>false</annunciating> <guidance> <title>[Operator Action]</title> @@ -3186,7 +3260,7 @@ Call cryo on call </pv> <pv name="HCB-TCH:ODH-O2iM-6:O2Below19_5"> <description>ODH Warning (Oxygen below 19.5%)</description> - <latching>true</latching> + <latching>false</latching> <annunciating>false</annunciating> <guidance> <title>[Operator Action]</title> @@ -3208,7 +3282,7 @@ Call cryo on call </pv> <pv name="HCB-TCH:ODH-O2iM-6:Disconnected"> <description>Monitor lost connection</description> - <latching>true</latching> + <latching>false</latching> <annunciating>false</annunciating> <guidance> <title>[Operator Action]</title> @@ -3218,7 +3292,7 @@ Call cryo on call </pv> <pv name="HCB-TCH:ODH-O2iM-6:Failure"> <description>Monitor failure</description> - <latching>true</latching> + <latching>false</latching> <annunciating>false</annunciating> <guidance> <title>[Operator Action]</title> @@ -3240,7 +3314,7 @@ Call cryo on call <component name="O2IM8"> <pv name="HCB-TCH:ODH-O2iM-8:O2Below18"> <description>ODH Alarm (Oxygen below 18%)</description> - <latching>true</latching> + <latching>false</latching> <annunciating>false</annunciating> <guidance> <title>[Operator Action]</title> @@ -3253,7 +3327,7 @@ Call cryo on call </pv> <pv name="HCB-TCH:ODH-O2iM-8:O2Below19_5"> <description>ODH Warning (Oxygen below 19.5%)</description> - <latching>true</latching> + <latching>false</latching> <annunciating>false</annunciating> <guidance> <title>[Operator Action]</title> @@ -3275,7 +3349,7 @@ Call cryo on call </pv> <pv name="HCB-TCH:ODH-O2iM-8:Disconnected"> <description>Monitor lost connection</description> - <latching>true</latching> + <latching>false</latching> <annunciating>false</annunciating> <guidance> <title>[Operator Action]</title> @@ -3285,7 +3359,7 @@ Call cryo on call </pv> <pv name="HCB-TCH:ODH-O2iM-8:Failure"> <description>Monitor failure</description> - <latching>true</latching> + <latching>false</latching> <annunciating>false</annunciating> <guidance> <title>[Operator Action]</title> @@ -3307,7 +3381,7 @@ Call cryo on call <component name="O2IM9"> <pv name="HCB-TCH:ODH-O2iM-9:O2Below18"> <description>ODH Alarm (Oxygen below 18%)</description> - <latching>true</latching> + <latching>false</latching> <annunciating>false</annunciating> <guidance> <title>[Operator Action]</title> @@ -3320,7 +3394,7 @@ Call cryo on call </pv> <pv name="HCB-TCH:ODH-O2iM-9:O2Below19_5"> <description>ODH Warning (Oxygen below 19.5%)</description> - <latching>true</latching> + <latching>false</latching> <annunciating>false</annunciating> <guidance> <title>[Operator Action]</title> @@ -3342,7 +3416,7 @@ Call cryo on call </pv> <pv name="HCB-TCH:ODH-O2iM-9:Disconnected"> <description>Monitor lost connection</description> - <latching>true</latching> + <latching>false</latching> <annunciating>false</annunciating> <guidance> <title>[Operator Action]</title> @@ -3352,7 +3426,7 @@ Call cryo on call </pv> <pv name="HCB-TCH:ODH-O2iM-9:Failure"> <description>Monitor failure</description> - <latching>true</latching> + <latching>false</latching> <annunciating>false</annunciating> <guidance> <title>[Operator Action]</title> @@ -3374,7 +3448,7 @@ Call cryo on call <component name="O2IM10"> <pv name="HCB-HPGS:ODH-O2iM-10:O2Below18"> <description>ODH Alarm (Oxygen below 18%)</description> - <latching>true</latching> + <latching>false</latching> <annunciating>false</annunciating> <guidance> <title>[Operator Action]</title> @@ -3387,7 +3461,7 @@ Call cryo on call </pv> <pv name="HCB-HPGS:ODH-O2iM-10:O2Below19_5"> <description>ODH Warning (Oxygen below 19.5%)</description> - <latching>true</latching> + <latching>false</latching> <annunciating>false</annunciating> <guidance> <title>[Operator Action]</title> @@ -3409,7 +3483,7 @@ Call cryo on call </pv> <pv name="HCB-HPGS:ODH-O2iM-10:Disconnected"> <description>Monitor lost connection</description> - <latching>true</latching> + <latching>false</latching> <annunciating>false</annunciating> <guidance> <title>[Operator Action]</title> @@ -3419,7 +3493,7 @@ Call cryo on call </pv> <pv name="HCB-HPGS:ODH-O2iM-10:Failure"> <description>Monitor failure</description> - <latching>true</latching> + <latching>false</latching> <annunciating>false</annunciating> <guidance> <title>[Operator Action]</title> @@ -3443,7 +3517,7 @@ Call cryo on call <component name="TS2"> <pv name="KG-GTA:ODH-Area-001:Alrm"> <description>Zone ODH Alarm (Oxygen below 18%)</description> - <latching>true</latching> + <latching>false</latching> <annunciating>true</annunciating> <guidance> <title>[Operator Action]</title> @@ -3456,7 +3530,7 @@ Call cryo on call </pv> <pv name="KG-GTA:ODH-Area-001:Warning"> <description>Zone ODH Warning (Oxygen below 19.5%)</description> - <latching>true</latching> + <latching>false</latching> <annunciating>true</annunciating> <guidance> <title>[Operator Action]</title> @@ -3469,7 +3543,7 @@ Call cryo on call </pv> <pv name="KG-GTA:ODH-Area-001:Error"> <description>Zone oxygen monitor error</description> - <latching>true</latching> + <latching>false</latching> <annunciating>true</annunciating> <guidance> <title>[Operator Action]</title> @@ -3541,7 +3615,7 @@ Call cryo on call <component name="O2IM23"> <pv name="KG-GTA:ODH-O2iM-23:O2Below18"> <description>ODH Alarm (Oxygen below 18%)</description> - <latching>true</latching> + <latching>false</latching> <annunciating>false</annunciating> <guidance> <title>[Operator Action]</title> @@ -3554,7 +3628,7 @@ Call cryo on call </pv> <pv name="KG-GTA:ODH-O2iM-23:O2Below19_5"> <description>ODH Warning (Oxygen below 19.5%)</description> - <latching>true</latching> + <latching>false</latching> <annunciating>false</annunciating> <guidance> <title>[Operator Action]</title> @@ -3576,7 +3650,7 @@ Call cryo on call </pv> <pv name="KG-GTA:ODH-O2iM-23:Disconnected"> <description>Monitor lost connection</description> - <latching>true</latching> + <latching>false</latching> <annunciating>false</annunciating> <guidance> <title>[Operator Action]</title> @@ -3586,7 +3660,7 @@ Call cryo on call </pv> <pv name="KG-GTA:ODH-O2iM-23:Failure"> <description>Monitor failure</description> - <latching>true</latching> + <latching>false</latching> <annunciating>false</annunciating> <guidance> <title>[Operator Action]</title> @@ -3608,7 +3682,7 @@ Call cryo on call <component name="O2IM24"> <pv name="KG-GTA:ODH-O2iM-24:O2Below18"> <description>ODH Alarm (Oxygen below 18%)</description> - <latching>true</latching> + <latching>false</latching> <annunciating>false</annunciating> <guidance> <title>[Operator Action]</title> @@ -3621,7 +3695,7 @@ Call cryo on call </pv> <pv name="KG-GTA:ODH-O2iM-24:O2Below19_5"> <description>ODH Warning (Oxygen below 19.5%)</description> - <latching>true</latching> + <latching>false</latching> <annunciating>false</annunciating> <guidance> <title>[Operator Action]</title> @@ -3643,7 +3717,7 @@ Call cryo on call </pv> <pv name="KG-GTA:ODH-O2iM-24:Disconnected"> <description>Monitor lost connection</description> - <latching>true</latching> + <latching>false</latching> <annunciating>false</annunciating> <guidance> <title>[Operator Action]</title> @@ -3653,7 +3727,7 @@ Call cryo on call </pv> <pv name="KG-GTA:ODH-O2iM-24:Failure"> <description>Monitor failure</description> - <latching>true</latching> + <latching>false</latching> <annunciating>false</annunciating> <guidance> <title>[Operator Action]</title> @@ -3668,6 +3742,1692 @@ Call cryo on call <guidance> <title>[Operator Action]</title> <details>KG-GTA:ODH-O2iM-24 in TS2 analogue input is out of range +- MCR/Gate guard/Cryo team: Inform PSS team</details> + </guidance> + </pv> + </component> + </component> + </component> + <component name="TS"> + <pv name="TgtGDS::CV82095FBError"> + <description>Valve has a feedback error</description> + <latching>false</latching> + <annunciating>false</annunciating> + <guidance> + <title>[Operator Action]</title> + <details>CV-82095 in A2T room (D02.115.4005) has a feedback error. +- MCR/Gate guard/Cryo team: Inform PSS team</details> + </guidance> + </pv> + <pv name="TgtGDS::CV62001FBError"> + <description>Valve has a feedback error</description> + <latching>false</latching> + <annunciating>false</annunciating> + <guidance> + <title>[Operator Action]</title> + <details>CV-62001 in H2 room (D02.150.4018) has a feedback error. +- MCR/Gate guard/Cryo team: Inform PSS team</details> + </guidance> + </pv> + <pv name="TgtGDS::Tripped"> + <description>SIF1 Tripped (High hydrogen concentration in target station)</description> + <latching>false</latching> + <annunciating>false</annunciating> + <guidance> + <title>[Operator Action]</title> + <details>SIF1 Tripped (High hydrogen concentration in target station). +- MCR/Gate guard/Cryo team: Inform PSS team +</details> + </guidance> + </pv> + <pv name="TgtGDS::SafetyResetRequired"> + <description>Safety Reset Required</description> + <latching>false</latching> + <annunciating>false</annunciating> + <guidance> + <title>[Operator Action]</title> + <details>H2 part of target station gas detection system needs to be reset. +Inform PSS team +- MCR: Reset the SIF thru. OPI or HMI in D02</details> + </guidance> + </pv> + <pv name="TgtGDS::ReintRequired"> + <description>Safety IO Reintegration Required</description> + <latching>false</latching> + <annunciating>false</annunciating> + <guidance> + <title>[Operator Action]</title> + <details>H2 part of target station gas detection system needs to be reset. +Inform PSS team +- MCR: Reintegrate thru. OPI or HMI in D02</details> + </guidance> + </pv> + <pv name="TgtGDS::StartUp"> + <description>PLC Startup detected, reset required</description> + <latching>false</latching> + <annunciating>false</annunciating> + <guidance> + <title>[Operator Action]</title> + <details>PLC Startup detected, reset required +Inform PSS team +- MCR: Reset the SIF thru. OPI or HMI in D02</details> + </guidance> + </pv> + <component name="LVL085"> + <pv name="TgtGDS:ODH-Area-085:Alrm"> + <description>Zone ODH Alarm (Oxygen below 18%)</description> + <latching>false</latching> + <annunciating>false</annunciating> + <guidance> + <title>[Operator Action]</title> + <details>D02.085 zone gas evacuation alarm due to O2 less than 18% +Call cryo on call +- MCR: Follow ESS-3216323 +- Gate guard: Follow ESS-2124375 +- Cryo team: Follow ESS-1788930</details> + </guidance> + </pv> + <pv name="TgtGDS:ODH-Area-085:Warning"> + <description>Zone ODH Warning (Oxygen below 19.5%)</description> + <latching>false</latching> + <annunciating>false</annunciating> + <guidance> + <title>[Operator Action]</title> + <details>D02.085 zone ODH warning due to O2 less than 19.5% +Call cryo on call +- MCR: Follow ESS-3216323 +- Gate guard: Follow ESS-2124375 +- Cryo team: Follow ESS-1788930</details> + </guidance> + </pv> + <pv name="TgtGDS:ODH-Area-085:Error"> + <description>Zone oxygen monitor error</description> + <latching>false</latching> + <annunciating>false</annunciating> + <guidance> + <title>[Operator Action]</title> + <details>D02.085 zone gas evacuation alarm due to an error +- MCR/Gate guard/Cryo team: Inform PSS team</details> + </guidance> + </pv> + <pv name="TgtGDS:ODH-Area-085:Attention"> + <description>Zone minor issue</description> + <latching>false</latching> + <annunciating>false</annunciating> + <guidance> + <title>[Operator Action]</title> + <details>D02.085 zone has a minor issue +- MCR/Gate guard/Cryo team: Inform PSS team</details> + </guidance> + </pv> + <pv name="TgtGDS:ODH-Area-085:Maintenance"> + <description>Zone oxygen monitor in maintenance mode</description> + <latching>false</latching> + <annunciating>false</annunciating> + <guidance> + <title>[Operator Action]</title> + <details>D02.085 zone is in maintenance mode</details> + </guidance> + </pv> + <pv name="TgtGDS:ODH-Area-085:HwError"> + <description>Zone PLC HW failure</description> + <latching>false</latching> + <annunciating>false</annunciating> + <guidance> + <title>[Operator Action]</title> + <details>D02.085 zone has a PLC HW failure +- MCR/Gate guard/Cryo team: Inform PSS team</details> + </guidance> + </pv> + <pv name="TgtGDS:ODH-Area-085:BatteryLow"> + <description>Zone UPS battery low alarm while buffering</description> + <latching>false</latching> + <annunciating>false</annunciating> + <guidance> + <title>[Operator Action]</title> + <details>D02.085 zone gas evacuation alarm due to low battery alarm +- MCR/Gate guard/Cryo team: Inform PSS team</details> + </guidance> + </pv> + <pv name="TgtGDS:ODH-Area-085:ConfirmedAlrm"> + <description>Zone ODH confirmed alarm</description> + <latching>false</latching> + <annunciating>false</annunciating> + <guidance> + <title>[Operator Action]</title> + <details>D02.085 zone ODH confirmed alarm due to O2 less than 18% for more than one min or two monitors detect O2 less than 18% +Call cryo on call +- MCR: Follow ESS-3216323 +- Gate guard: Follow ESS-2124375 +- Cryo team: Follow ESS-1788930</details> + </guidance> + </pv> + <pv name="TgtGDS:ODH-Area-085:StartUp"> + <description>Zone equipment starting-up</description> + <latching>false</latching> + <annunciating>false</annunciating> + <guidance> + <title>[Operator Action]</title> + <details>D02.085 zone is in start-up mode</details> + </guidance> + </pv> + <pv name="TgtGDS:ODH-Area-085:Muted"> + <description>Zone audible alarm muted</description> + <latching>false</latching> + <annunciating>false</annunciating> + <guidance> + <title>[Operator Action]</title> + <details>D02.085 zone is muted</details> + </guidance> + </pv> + <pv name="TgtGDS:ODH-Area-085:DeviceFailure"> + <description>Zone alarm device failure</description> + <latching>false</latching> + <annunciating>false</annunciating> + <guidance> + <title>[Operator Action]</title> + <details>D02.085 zone ODH alarm device failure +- MCR/Gate guard/Cryo team: Inform PSS team</details> + </guidance> + </pv> + <component name="ACS"> + <pv name="TgtGDS:ODH-ACS-002:Failure"> + <description>Device failure</description> + <latching>false</latching> + <annunciating>false</annunciating> + <guidance> + <title>[Operator Action]</title> + <details>TgtGDS:ODH-ACS-002 in utility 085a (D02.085.3064) failure +- MCR/Gate guard/Cryo team: Inform PSS team</details> + </guidance> + </pv> + <pv name="TgtGDS:ODH-ACS-004:Failure"> + <description>Device failure</description> + <latching>false</latching> + <annunciating>false</annunciating> + <guidance> + <title>[Operator Action]</title> + <details>TgtGDS:ODH-ACS-004 in Stair 005 (D02.085.3061) failure +- MCR/Gate guard/Cryo team: Inform PSS team</details> + </guidance> + </pv> + <pv name="TgtGDS:ODH-ACS-005:Failure"> + <description>Device failure</description> + <latching>false</latching> + <annunciating>false</annunciating> + <guidance> + <title>[Operator Action]</title> + <details>TgtGDS:ODH-ACS-005 in Lift hall level (D02.085.3063) failure +- MCR/Gate guard/Cryo team: Inform PSS team</details> + </guidance> + </pv> + <pv name="TgtGDS:ODH-ACS-007:Failure"> + <description>Device failure</description> + <latching>false</latching> + <annunciating>false</annunciating> + <guidance> + <title>[Operator Action]</title> + <details>TgtGDS:ODH-ACS-007 in utility 085b (D02.085.3067) failure +- MCR/Gate guard/Cryo team: Inform PSS team</details> + </guidance> + </pv> + <pv name="TgtGDS:ODH-ACS-009:Failure"> + <description>Device failure</description> + <latching>false</latching> + <annunciating>false</annunciating> + <guidance> + <title>[Operator Action]</title> + <details>TgtGDS:ODH-ACS-009 in Utility 091 SW (D02.091.4003) failure +- MCR/Gate guard/Cryo team: Inform PSS team</details> + </guidance> + </pv> + </component> + <component name="O2IM"> + <component name="O2IM1"> + <pv name="TgtGDS:ODH-O2iM-001:O2Below18"> + <description>ODH Alarm (Oxygen below 18%)</description> + <latching>false</latching> + <annunciating>false</annunciating> + <guidance> + <title>[Operator Action]</title> + <details>TgtGDS:ODH-O2iM-001 monitoring utility 085b (D02.085.3067) ODH alarm- O2 less than 18% +Call cryo on call +- MCR: Follow ESS-3216323 +- Gate guard: Follow ESS-2124375 +- Cryo team: Follow ESS-1788930</details> + </guidance> + </pv> + <pv name="TgtGDS:ODH-O2iM-001:O2Below19_5"> + <description>ODH Warning (Oxygen below 19.5%)</description> + <latching>false</latching> + <annunciating>false</annunciating> + <guidance> + <title>[Operator Action]</title> + <details>TgtGDS:ODH-O2iM-001 monitoring utility 085b (D02.085.3067) ODH warning- O2 less than 19.5% +Call cryo on call +- MCR: Follow ESS-3216323 +- Gate guard: Follow ESS-2124375 +- Cryo team: Follow ESS-1788930</details> + </guidance> + </pv> + <pv name="TgtGDS:ODH-O2iM-001:Maintenance"> + <description>Monitor maintenance mode</description> + <latching>false</latching> + <annunciating>false</annunciating> + <guidance> + <title>[Operator Action]</title> + <details>TgtGDS:ODH-O2iM-001 monitoring utility 085b (D02.085.3067) is in maintenance mode</details> + </guidance> + </pv> + <pv name="TgtGDS:ODH-O2iM-001:Disconnected"> + <description>Monitor lost connection</description> + <latching>false</latching> + <annunciating>false</annunciating> + <guidance> + <title>[Operator Action]</title> + <details>TgtGDS:ODH-O2iM-001 monitoring utility 085b (D02.085.3067) has lost connection +- MCR/Gate guard/Cryo team: Inform PSS team</details> + </guidance> + </pv> + <pv name="TgtGDS:ODH-O2iM-001:Failure"> + <description>Monitor failure</description> + <latching>false</latching> + <annunciating>false</annunciating> + <guidance> + <title>[Operator Action]</title> + <details>TgtGDS:ODH-O2iM-001 monitoring utility 085b (D02.085.3067) failure +- MCR/Gate guard/Cryo team: Inform PSS team</details> + </guidance> + </pv> + <pv name="TgtGDS:ODH-O2iM-001:AiBadValue"> + <description>Oxygen level value is not valid</description> + <latching>false</latching> + <annunciating>false</annunciating> + <guidance> + <title>[Operator Action]</title> + <details>TgtGDS:ODH-O2iM-001 monitoring utility 085b (D02.085.3067) analogue input is out of range +- MCR/Gate guard/Cryo team: Inform PSS team</details> + </guidance> + </pv> + </component> + </component> + <component name="RSL"> + <pv name="TgtGDS:ODH-RSL-001:Failure"> + <description>Device failure</description> + <latching>false</latching> + <annunciating>false</annunciating> + <guidance> + <title>[Operator Action]</title> + <details>TgtGDS:ODH-RSL-001 in utility 085a (D02.085.3064) failure +- MCR/Gate guard/Cryo team: Inform PSS team</details> + </guidance> + </pv> + <pv name="TgtGDS:ODH-RSL-002:Failure"> + <description>Device failure</description> + <latching>false</latching> + <annunciating>false</annunciating> + <guidance> + <title>[Operator Action]</title> + <details>TgtGDS:ODH-RSL-002 in utility 085a (D02.085.3064) failure +- MCR/Gate guard/Cryo team: Inform PSS team</details> + </guidance> + </pv> + <pv name="TgtGDS:ODH-RSL-003:Failure"> + <description>Device failure</description> + <latching>false</latching> + <annunciating>false</annunciating> + <guidance> + <title>[Operator Action]</title> + <details>TgtGDS:ODH-RSL-003 in utility 085a (D02.085.3064) failure +- MCR/Gate guard/Cryo team: Inform PSS team</details> + </guidance> + </pv> + <pv name="TgtGDS:ODH-RSL-004:Failure"> + <description>Device failure</description> + <latching>false</latching> + <annunciating>false</annunciating> + <guidance> + <title>[Operator Action]</title> + <details>TgtGDS:ODH-RSL-004 in Stair level 005 (D02.085.3061) failure +- MCR/Gate guard/Cryo team: Inform PSS team</details> + </guidance> + </pv> + <pv name="TgtGDS:ODH-RSL-005:Failure"> + <description>Device failure</description> + <latching>false</latching> + <annunciating>false</annunciating> + <guidance> + <title>[Operator Action]</title> + <details>TgtGDS:ODH-RSL-005 in Lift hall (D02.115.3063) failure +- MCR/Gate guard/Cryo team: Inform PSS team</details> + </guidance> + </pv> + <pv name="TgtGDS:ODH-RSL-006:Failure"> + <description>Device failure</description> + <latching>false</latching> + <annunciating>false</annunciating> + <guidance> + <title>[Operator Action]</title> + <details>TgtGDS:ODH-RSL-006 in utility 085b (D02.085.3067) failure +- MCR/Gate guard/Cryo team: Inform PSS team</details> + </guidance> + </pv> + <pv name="TgtGDS:ODH-RSL-007:Failure"> + <description>Device failure</description> + <latching>false</latching> + <annunciating>false</annunciating> + <guidance> + <title>[Operator Action]</title> + <details>TgtGDS:ODH-RSL-007 in utility 085b (D02.085.3067) failure +- MCR/Gate guard/Cryo team: Inform PSS team</details> + </guidance> + </pv> + <pv name="TgtGDS:ODH-RSL-008:Failure"> + <description>Device failure</description> + <latching>false</latching> + <annunciating>false</annunciating> + <guidance> + <title>[Operator Action]</title> + <details>TgtGDS:ODH-RSL-008 in utility 085b (D02.085.3067) failure +- MCR/Gate guard/Cryo team: Inform PSS team</details> + </guidance> + </pv> + <pv name="TgtGDS:ODH-RSL-009:Failure"> + <description>Device failure</description> + <latching>false</latching> + <annunciating>false</annunciating> + <guidance> + <title>[Operator Action]</title> + <details>TgtGDS:ODH-RSL-009 in Utility 091 SW (D02.091.4003) failure +- MCR/Gate guard/Cryo team: Inform PSS team</details> + </guidance> + </pv> + </component> + </component> + <component name="LVL115E"> + <pv name="TgtGDS:ODH-AreaE-115:Attention"> + <description>Zone minor issue</description> + <latching>false</latching> + <annunciating>false</annunciating> + <guidance> + <title>[Operator Action]</title> + <details>D02.115E zone has a minor issue +- MCR/Gate guard/Cryo team: Inform PSS team</details> + </guidance> + </pv> + <pv name="TgtGDS:ODH-AreaE-115:HwError"> + <description>Zone PLC HW failure</description> + <latching>false</latching> + <annunciating>false</annunciating> + <guidance> + <title>[Operator Action]</title> + <details>D02.115E zone has a PLC HW failure +- MCR/Gate guard/Cryo team: Inform PSS team</details> + </guidance> + </pv> + <pv name="TgtGDS:ODH-AreaE-115:Muted"> + <description>Zone audible alarm muted</description> + <latching>false</latching> + <annunciating>false</annunciating> + <guidance> + <title>[Operator Action]</title> + <details>D02.115E zone is muted</details> + </guidance> + </pv> + <pv name="TgtGDS:ODH-AreaE-115:DeviceFailure"> + <description>Zone alarm device failure</description> + <latching>false</latching> + <annunciating>false</annunciating> + <guidance> + <title>[Operator Action]</title> + <details>D02.115E zone ODH alarm device failure +- MCR/Gate guard/Cryo team: Inform PSS team</details> + </guidance> + </pv> + <pv name="TgtGDS:ODH-AreaE-115:FirstStgAlarm"> + <description>Zone 1st stage alarm (Hydrogen level above 10% LEL)</description> + <latching>false</latching> + <annunciating>false</annunciating> + <guidance> + <title>[Operator Action]</title> + <details>D02.115E zone gas evacuation alarm due to H2 above 10%LEL +Call cryo on call +- MCR: Follow ESS-3216323 +- Gate guard: Follow ESS-2124375 +- Cryo team: Follow ESS-5533654</details> + </guidance> + </pv> + <pv name="TgtGDS:ODH-AreaE-115:SecondStgAlarm"> + <description>Zone 2nd stage alarm (Hydrogen level above 25% LEL)</description> + <latching>false</latching> + <annunciating>false</annunciating> + <guidance> + <title>[Operator Action]</title> + <details>D02.115E zone gas evacuation alarm due to H2 above 25%LEL +Call cryo on call +- MCR: Follow ESS-3216323 +- Gate guard: Follow ESS-2124375 +- Cryo team: Follow ESS-5533654</details> + </guidance> + </pv> + <pv name="TgtGDS:ODH-AreaE-115:SpecialState"> + <description>Zone special state</description> + <latching>false</latching> + <annunciating>false</annunciating> + <guidance> + <title>[Operator Action]</title> + <details>D02.115E zone is in special state +- MCR/Gate guard/Cryo team: Inform PSS team</details> + </guidance> + </pv> + <pv name="TgtGDS:ODH-AreaE-115:H2_ConfirmedAlarm"> + <description>Zone H2 confirmed alarm</description> + <latching>false</latching> + <annunciating>false</annunciating> + <guidance> + <title>[Operator Action]</title> + <details>D02.115E zone gas evacuation alarm due to H2 above 100%LEL or two monitors detect H2 above 25% +Call cryo on call +- MCR: Follow ESS-3216323 +- Gate guard: Follow ESS-2124375 +- Cryo team: Follow ESS-5533654</details> + </guidance> + </pv> + <component name="ACS"> + <pv name="TgtGDS:ODH-ACS-021:Failure"> + <description>Device failure</description> + <latching>false</latching> + <annunciating>false</annunciating> + <guidance> + <title>[Operator Action]</title> + <details>TgtGDS:ODH-ACS-021 in Connection cell (D02.115.4001) failure +- MCR/Gate guard/Cryo team: Inform PSS team</details> + </guidance> + </pv> + <pv name="TgtGDS:ODH-ACS-025:Failure"> + <description>Device failure</description> + <latching>false</latching> + <annunciating>false</annunciating> + <guidance> + <title>[Operator Action]</title> + <details>TgtGDS:ODH-ACS-025 in A2T room (D02.115.4005) failure +- MCR/Gate guard/Cryo team: Inform PSS team</details> + </guidance> + </pv> + </component> + <component name="H2MON"> + <component name="H2MON1"> + <pv name="TgtGDS:ODH-H2Mon-001:H2Above10"> + <description>1st stage alarm (Hydrogen level above 10% LEL)</description> + <latching>false</latching> + <annunciating>false</annunciating> + <guidance> + <title>[Operator Action]</title> + <details>TgtGDS:ODH-H2Mon-001 monitoring A2T room (D02.115.4005) 1st stage H2 alarm- H2 above 10% LEL +Call cryo on call +- MCR: Follow ESS-3216323 +- Gate guard: Follow ESS-2124375 +- Cryo team: Follow ESS-5533654</details> + </guidance> + </pv> + <pv name="TgtGDS:ODH-H2Mon-001:H2Above25"> + <description>2nd stage alarm (Hydrogen level above 25% LEL)</description> + <latching>false</latching> + <annunciating>false</annunciating> + <guidance> + <title>[Operator Action]</title> + <details>TgtGDS:ODH-H2Mon-001 monitoring A2T room (D02.115.4005) 2nd stage H2 alarm- H2 above 25% LEL +Call cryo on call +- MCR: Follow ESS-3216323 +- Gate guard: Follow ESS-2124375 +- Cryo team: Follow ESS-5533654</details> + </guidance> + </pv> + <pv name="TgtGDS:ODH-H2Mon-001:H2Above100"> + <description>Hydrogen level above 100% LEL</description> + <latching>false</latching> + <annunciating>false</annunciating> + <guidance> + <title>[Operator Action]</title> + <details>TgtGDS:ODH-H2Mon-001 monitoring A2T room (D02.115.4005) H2 confirmed alarm- H2 above 100% LEL +Call cryo on call +- MCR: Follow ESS-3216323 +- Gate guard: Follow ESS-2124375 +- Cryo team: Follow ESS-5533654</details> + </guidance> + </pv> + <pv name="TgtGDS:ODH-H2Mon-001:SpecialState"> + <description>Special state</description> + <latching>false</latching> + <annunciating>false</annunciating> + <guidance> + <title>[Operator Action]</title> + <details>TgtGDS:ODH-H2Mon-001 monitoring A2T room (D02.115.4005) is in special state +- MCR/Gate guard/Cryo team: Inform PSS team</details> + </guidance> + </pv> + <pv name="TgtGDS:ODH-H2Mon-001:AiBadValue"> + <description>H2 level AI ADC code out of range</description> + <latching>false</latching> + <annunciating>false</annunciating> + <guidance> + <title>[Operator Action]</title> + <details>TgtGDS:ODH-H2Mon-001 monitoring A2T room (D02.115.4005) analogue input is out of range +- MCR/Gate guard/Cryo team: Inform PSS team</details> + </guidance> + </pv> + </component> + <component name="H2MON2"> + <pv name="TgtGDS:ODH-H2Mon-002:H2Above10"> + <description>1st stage alarm (Hydrogen level above 10% LEL)</description> + <latching>false</latching> + <annunciating>false</annunciating> + <guidance> + <title>[Operator Action]</title> + <details>TgtGDS:ODH-H2Mon-002 monitoring A2T room (D02.115.4005) 1st stage H2 alarm- H2 above 10% LEL +Call cryo on call +- MCR: Follow ESS-3216323 +- Gate guard: Follow ESS-2124375 +- Cryo team: Follow ESS-5533654</details> + </guidance> + </pv> + <pv name="TgtGDS:ODH-H2Mon-002:H2Above25"> + <description>2nd stage alarm (Hydrogen level above 25% LEL)</description> + <latching>false</latching> + <annunciating>false</annunciating> + <guidance> + <title>[Operator Action]</title> + <details>TgtGDS:ODH-H2Mon-002 monitoring A2T room (D02.115.4005) 2nd stage H2 alarm- H2 above 25% LEL +Call cryo on call +- MCR: Follow ESS-3216323 +- Gate guard: Follow ESS-2124375 +- Cryo team: Follow ESS-5533654</details> + </guidance> + </pv> + <pv name="TgtGDS:ODH-H2Mon-002:H2Above100"> + <description>Hydrogen level above 100% LEL</description> + <latching>false</latching> + <annunciating>false</annunciating> + <guidance> + <title>[Operator Action]</title> + <details>TgtGDS:ODH-H2Mon-002 monitoring A2T room (D02.115.4005) H2 confirmed alarm- H2 above 100% LEL +Call cryo on call +- MCR: Follow ESS-3216323 +- Gate guard: Follow ESS-2124375 +- Cryo team: Follow ESS-5533654</details> + </guidance> + </pv> + <pv name="TgtGDS:ODH-H2Mon-002:SpecialState"> + <description>Special state</description> + <latching>false</latching> + <annunciating>false</annunciating> + <guidance> + <title>[Operator Action]</title> + <details>TgtGDS:ODH-H2Mon-002 monitoring A2T room (D02.115.4005) is in special state +- MCR/Gate guard/Cryo team: Inform PSS team</details> + </guidance> + </pv> + <pv name="TgtGDS:ODH-H2Mon-002:AiBadValue"> + <description>H2 level AI ADC code out of range</description> + <latching>false</latching> + <annunciating>false</annunciating> + <guidance> + <title>[Operator Action]</title> + <details>TgtGDS:ODH-H2Mon-002 monitoring A2T room (D02.115.4005) analogue input is out of range +- MCR/Gate guard/Cryo team: Inform PSS team</details> + </guidance> + </pv> + </component> + <component name="H2MON3"> + <pv name="TgtGDS:ODH-H2Mon-003:H2Above10"> + <description>1st stage alarm (Hydrogen level above 10% LEL)</description> + <latching>false</latching> + <annunciating>false</annunciating> + <guidance> + <title>[Operator Action]</title> + <details>TgtGDS:ODH-H2Mon-003 monitoring A2T room (D02.115.4005) 1st stage H2 alarm- H2 above 10% LEL +Call cryo on call +- MCR: Follow ESS-3216323 +- Gate guard: Follow ESS-2124375 +- Cryo team: Follow ESS-5533654</details> + </guidance> + </pv> + <pv name="TgtGDS:ODH-H2Mon-003:H2Above25"> + <description>2nd stage alarm (Hydrogen level above 25% LEL)</description> + <latching>false</latching> + <annunciating>false</annunciating> + <guidance> + <title>[Operator Action]</title> + <details>TgtGDS:ODH-H2Mon-003 monitoring A2T room (D02.115.4005) 2nd stage H2 alarm- H2 above 25% LEL +Call cryo on call +- MCR: Follow ESS-3216323 +- Gate guard: Follow ESS-2124375 +- Cryo team: Follow ESS-5533654</details> + </guidance> + </pv> + <pv name="TgtGDS:ODH-H2Mon-003:H2Above100"> + <description>Hydrogen level above 100% LEL</description> + <latching>false</latching> + <annunciating>false</annunciating> + <guidance> + <title>[Operator Action]</title> + <details>TgtGDS:ODH-H2Mon-003 monitoring A2T room (D02.115.4005) H2 confirmed alarm- H2 above 100% LEL +Call cryo on call +- MCR: Follow ESS-3216323 +- Gate guard: Follow ESS-2124375 +- Cryo team: Follow ESS-5533654</details> + </guidance> + </pv> + <pv name="TgtGDS:ODH-H2Mon-003:SpecialState"> + <description>Special state</description> + <latching>false</latching> + <annunciating>false</annunciating> + <guidance> + <title>[Operator Action]</title> + <details>TgtGDS:ODH-H2Mon-003 monitoring A2T room (D02.115.4005) is in special state +- MCR/Gate guard/Cryo team: Inform PSS team</details> + </guidance> + </pv> + <pv name="TgtGDS:ODH-H2Mon-003:AiBadValue"> + <description>H2 level AI ADC code out of range</description> + <latching>false</latching> + <annunciating>false</annunciating> + <guidance> + <title>[Operator Action]</title> + <details>TgtGDS:ODH-H2Mon-003 monitoring A2T room (D02.115.4005) analogue input is out of range +- MCR/Gate guard/Cryo team: Inform PSS team</details> + </guidance> + </pv> + </component> + </component> + <component name="RSL"> + <pv name="TgtGDS:ODH-RSL-021:Failure"> + <description>Device failure</description> + <latching>false</latching> + <annunciating>false</annunciating> + <guidance> + <title>[Operator Action]</title> + <details>TgtGDS:ODH-RSL-021 in Connection cell (D02.115.4001) failure +- MCR/Gate guard/Cryo team: Inform PSS team</details> + </guidance> + </pv> + <pv name="TgtGDS:ODH-RSL-022:Failure"> + <description>Device failure</description> + <latching>false</latching> + <annunciating>false</annunciating> + <guidance> + <title>[Operator Action]</title> + <details>TgtGDS:ODH-RSL-022 in A2T room (D02.115.4005) failure +- MCR/Gate guard/Cryo team: Inform PSS team</details> + </guidance> + </pv> + <pv name="TgtGDS:ODH-RSL-023:Failure"> + <description>Device failure</description> + <latching>false</latching> + <annunciating>false</annunciating> + <guidance> + <title>[Operator Action]</title> + <details>TgtGDS:ODH-RSL-023 in A2T room (D02.115.4005) failure +- MCR/Gate guard/Cryo team: Inform PSS team</details> + </guidance> + </pv> + <pv name="TgtGDS:ODH-RSL-024:Failure"> + <description>Device failure</description> + <latching>false</latching> + <annunciating>false</annunciating> + <guidance> + <title>[Operator Action]</title> + <details>TgtGDS:ODH-RSL-024 in A2T room (D02.115.4005) failure +- MCR/Gate guard/Cryo team: Inform PSS team</details> + </guidance> + </pv> + <pv name="TgtGDS:ODH-RSL-025:Failure"> + <description>Device failure</description> + <latching>false</latching> + <annunciating>false</annunciating> + <guidance> + <title>[Operator Action]</title> + <details>TgtGDS:ODH-RSL-025 in A2T room (D02.115.4005) failure +- MCR/Gate guard/Cryo team: Inform PSS team</details> + </guidance> + </pv> + </component> + </component> + <component name="LVL115W"> + <pv name="TgtGDS:ODH-AreaW-115:Alrm"> + <description>Zone ODH Alarm (Oxygen below 18%)</description> + <latching>false</latching> + <annunciating>false</annunciating> + <guidance> + <title>[Operator Action]</title> + <details>D02.115W zone gas evacuation alarm due to O2 less than 18% +Call cryo on call +- MCR: Follow ESS-3216323 +- Gate guard: Follow ESS-2124375 +- Cryo team: Follow ESS-1788930</details> + </guidance> + </pv> + <pv name="TgtGDS:ODH-AreaW-115:Warning"> + <description>Zone ODH Warning (Oxygen below 19.5%)</description> + <latching>false</latching> + <annunciating>false</annunciating> + <guidance> + <title>[Operator Action]</title> + <details>D02.115W zone ODH warning due to O2 less than 19.5% +Call cryo on call +- MCR: Follow ESS-3216323 +- Gate guard: Follow ESS-2124375 +- Cryo team: Follow ESS-1788930</details> + </guidance> + </pv> + <pv name="TgtGDS:ODH-AreaW-115:Error"> + <description>Zone oxygen monitor error</description> + <latching>false</latching> + <annunciating>false</annunciating> + <guidance> + <title>[Operator Action]</title> + <details>D02.115W zone gas evacuation alarm due to an error +- MCR/Gate guard/Cryo team: Inform PSS team</details> + </guidance> + </pv> + <pv name="TgtGDS:ODH-AreaW-115:Attention"> + <description>Zone minor issue</description> + <latching>false</latching> + <annunciating>false</annunciating> + <guidance> + <title>[Operator Action]</title> + <details>D02.115W zone has a minor issue +- MCR/Gate guard/Cryo team: Inform PSS team</details> + </guidance> + </pv> + <pv name="TgtGDS:ODH-AreaW-115:Maintenance"> + <description>Zone oxygen monitor in maintenance mode</description> + <latching>false</latching> + <annunciating>false</annunciating> + <guidance> + <title>[Operator Action]</title> + <details>D02.115W zone is in maintenance mode</details> + </guidance> + </pv> + <pv name="TgtGDS:ODH-AreaW-115:HwError"> + <description>Zone PLC HW failure</description> + <latching>false</latching> + <annunciating>false</annunciating> + <guidance> + <title>[Operator Action]</title> + <details>D02.115W zone has a PLC HW failure +- MCR/Gate guard/Cryo team: Inform PSS team</details> + </guidance> + </pv> + <pv name="TgtGDS:ODH-AreaW-115:BatteryLow"> + <description>Zone UPS battery low alarm while buffering</description> + <latching>false</latching> + <annunciating>false</annunciating> + <guidance> + <title>[Operator Action]</title> + <details>D02.115W zone gas evacuation alarm due to low battery alarm +- MCR/Gate guard/Cryo team: Inform PSS team</details> + </guidance> + </pv> + <pv name="TgtGDS:ODH-AreaW-115:ConfirmedAlrm"> + <description>Zone ODH confirmed alarm</description> + <latching>false</latching> + <annunciating>false</annunciating> + <guidance> + <title>[Operator Action]</title> + <details>D02.115W zone ODH confirmed alarm due to O2 less than 18% for more than one min or two monitors detect O2 less than 18% +Call cryo on call +- MCR: Follow ESS-3216323 +- Gate guard: Follow ESS-2124375 +- Cryo team: Follow ESS-1788930</details> + </guidance> + </pv> + <pv name="TgtGDS:ODH-AreaW-115:StartUp"> + <description>Zone equipment starting-up</description> + <latching>false</latching> + <annunciating>false</annunciating> + <guidance> + <title>[Operator Action]</title> + <details>D02.115W zone is in start-up mode</details> + </guidance> + </pv> + <pv name="TgtGDS:ODH-AreaW-115:Muted"> + <description>Zone audible alarm muted</description> + <latching>false</latching> + <annunciating>false</annunciating> + <guidance> + <title>[Operator Action]</title> + <details>D02.115W zone is muted</details> + </guidance> + </pv> + <pv name="TgtGDS:ODH-AreaW-115:DeviceFailure"> + <description>Zone alarm device failure</description> + <latching>false</latching> + <annunciating>false</annunciating> + <guidance> + <title>[Operator Action]</title> + <details>D02.115W zone ODH alarm device failure +- MCR/Gate guard/Cryo team: Inform PSS team</details> + </guidance> + </pv> + <component name="ACS"> + <pv name="TgtGDS:ODH-ACS-010:Failure"> + <description>Device failure</description> + <latching>false</latching> + <annunciating>false</annunciating> + <guidance> + <title>[Operator Action]</title> + <details>TgtGDS:ODH-ACS-010 in Target HVAC (D02.115.3051) failure +- MCR/Gate guard/Cryo team: Inform PSS team</details> + </guidance> + </pv> + <pv name="TgtGDS:ODH-ACS-011:Failure"> + <description>Device failure</description> + <latching>false</latching> + <annunciating>false</annunciating> + <guidance> + <title>[Operator Action]</title> + <details>TgtGDS:ODH-ACS-011 in utility 115a (D02.115.3064) failure +- MCR/Gate guard/Cryo team: Inform PSS team</details> + </guidance> + </pv> + <pv name="TgtGDS:ODH-ACS-014:Failure"> + <description>Device failure</description> + <latching>false</latching> + <annunciating>false</annunciating> + <guidance> + <title>[Operator Action]</title> + <details>TgtGDS:ODH-ACS-014 in Stair 005 (D02.115.3061) failure +- MCR/Gate guard/Cryo team: Inform PSS team</details> + </guidance> + </pv> + <pv name="TgtGDS:ODH-ACS-015:Failure"> + <description>Device failure</description> + <latching>false</latching> + <annunciating>false</annunciating> + <guidance> + <title>[Operator Action]</title> + <details>TgtGDS:ODH-ACS-015 in Lift hall (D02.115.3063) failure +- MCR/Gate guard/Cryo team: Inform PSS team</details> + </guidance> + </pv> + <pv name="TgtGDS:ODH-ACS-017:Failure"> + <description>Device failure</description> + <latching>false</latching> + <annunciating>false</annunciating> + <guidance> + <title>[Operator Action]</title> + <details>TgtGDS:ODH-ACS-017 in utility 085b (D02.085.3067) failure +- MCR/Gate guard/Cryo team: Inform PSS team</details> + </guidance> + </pv> + <pv name="TgtGDS:ODH-ACS-019:Failure"> + <description>Device failure</description> + <latching>false</latching> + <annunciating>false</annunciating> + <guidance> + <title>[Operator Action]</title> + <details>TgtGDS:ODH-ACS-019 in utility 085c (D02.115.4003) failure +- MCR/Gate guard/Cryo team: Inform PSS team</details> + </guidance> + </pv> + </component> + <component name="O2IM"> + <component name="O2IM2"> + <pv name="TgtGDS:ODH-O2iM-002:O2Below18"> + <description>ODH Alarm (Oxygen below 18%)</description> + <latching>false</latching> + <annunciating>false</annunciating> + <guidance> + <title>[Operator Action]</title> + <details>TgtGDS:ODH-O2iM-002 monitoring utility 115a (D02.115.3064) ODH alarm- O2 less than 18% +Call cryo on call +- MCR: Follow ESS-3216323 +- Gate guard: Follow ESS-2124375 +- Cryo team: Follow ESS-1788930</details> + </guidance> + </pv> + <pv name="TgtGDS:ODH-O2iM-002:O2Below19_5"> + <description>ODH Warning (Oxygen below 19.5%)</description> + <latching>false</latching> + <annunciating>false</annunciating> + <guidance> + <title>[Operator Action]</title> + <details>TgtGDS:ODH-O2iM-002 monitoring utility 115a (D02.115.3064) ODH warning- O2 less than 19.5% +Call cryo on call +- MCR: Follow ESS-3216323 +- Gate guard: Follow ESS-2124375 +- Cryo team: Follow ESS-1788930</details> + </guidance> + </pv> + <pv name="TgtGDS:ODH-O2iM-002:Maintenance"> + <description>Monitor maintenance mode</description> + <latching>false</latching> + <annunciating>false</annunciating> + <guidance> + <title>[Operator Action]</title> + <details>TgtGDS:ODH-O2iM-002 monitoring utility 115a (D02.115.3064) is in maintenance mode</details> + </guidance> + </pv> + <pv name="TgtGDS:ODH-O2iM-002:Disconnected"> + <description>Monitor lost connection</description> + <latching>false</latching> + <annunciating>false</annunciating> + <guidance> + <title>[Operator Action]</title> + <details>TgtGDS:ODH-O2iM-002 monitoring utility 115a (D02.115.3064) has lost connection +- MCR/Gate guard/Cryo team: Inform PSS team</details> + </guidance> + </pv> + <pv name="TgtGDS:ODH-O2iM-002:Failure"> + <description>Monitor failure</description> + <latching>false</latching> + <annunciating>false</annunciating> + <guidance> + <title>[Operator Action]</title> + <details>TgtGDS:ODH-O2iM-002 monitoring utility 115a (D02.115.3064) failure +- MCR/Gate guard/Cryo team: Inform PSS team</details> + </guidance> + </pv> + <pv name="TgtGDS:ODH-O2iM-002:AiBadValue"> + <description>Oxygen level value is not valid</description> + <latching>false</latching> + <annunciating>false</annunciating> + <guidance> + <title>[Operator Action]</title> + <details>TgtGDS:ODH-O2iM-002 monitoring utility 115a (D02.115.3064) analogue input is out of range +- MCR/Gate guard/Cryo team: Inform PSS team</details> + </guidance> + </pv> + </component> + <component name="O2IM3"> + <pv name="TgtGDS:ODH-O2iM-003:O2Below18"> + <description>ODH Alarm (Oxygen below 18%)</description> + <latching>false</latching> + <annunciating>false</annunciating> + <guidance> + <title>[Operator Action]</title> + <details>TgtGDS:ODH-O2iM-003 monitoring utility 115c +(D02.115.4003) ODH alarm- O2 less than 18% +Call cryo on call +- MCR: Follow ESS-3216323 +- Gate guard: Follow ESS-2124375 +- Cryo team: Follow ESS-1788930</details> + </guidance> + </pv> + <pv name="TgtGDS:ODH-O2iM-003:O2Below19_5"> + <description>ODH Warning (Oxygen below 19.5%)</description> + <latching>false</latching> + <annunciating>false</annunciating> + <guidance> + <title>[Operator Action]</title> + <details>TgtGDS:ODH-O2iM-003 monitoring utility 115c +(D02.115.4003) ODH warning- O2 less than 19.5% +Call cryo on call +- MCR: Follow ESS-3216323 +- Gate guard: Follow ESS-2124375 +- Cryo team: Follow ESS-1788930</details> + </guidance> + </pv> + <pv name="TgtGDS:ODH-O2iM-003:Maintenance"> + <description>Monitor maintenance mode</description> + <latching>false</latching> + <annunciating>false</annunciating> + <guidance> + <title>[Operator Action]</title> + <details>TgtGDS:ODH-O2iM-003 monitoring utility 115c +(D02.115.4003) is in maintenance mode</details> + </guidance> + </pv> + <pv name="TgtGDS:ODH-O2iM-003:Disconnected"> + <description>Monitor lost connection</description> + <latching>false</latching> + <annunciating>false</annunciating> + <guidance> + <title>[Operator Action]</title> + <details>TgtGDS:ODH-O2iM-003 monitoring utility 115c +(D02.115.4003) has lost connection +- MCR/Gate guard/Cryo team: Inform PSS team</details> + </guidance> + </pv> + <pv name="TgtGDS:ODH-O2iM-003:Failure"> + <description>Monitor failure</description> + <latching>false</latching> + <annunciating>false</annunciating> + <guidance> + <title>[Operator Action]</title> + <details>TgtGDS:ODH-O2iM-003 monitoring utility 115c +(D02.115.4003) failure +- MCR/Gate guard/Cryo team: Inform PSS team</details> + </guidance> + </pv> + <pv name="TgtGDS:ODH-O2iM-003:AiBadValue"> + <description>Oxygen level value is not valid</description> + <latching>false</latching> + <annunciating>false</annunciating> + <guidance> + <title>[Operator Action]</title> + <details>TgtGDS:ODH-O2iM-003 monitoring utility 115c +(D02.115.4003) analogue input is out of range +- MCR/Gate guard/Cryo team: Inform PSS team</details> + </guidance> + </pv> + </component> + </component> + <component name="RSL"> + <pv name="TgtGDS:ODH-RSL-010:Failure"> + <description>Device failure</description> + <latching>false</latching> + <annunciating>false</annunciating> + <guidance> + <title>[Operator Action]</title> + <details>TgtGDS:ODH-RSL-010 in Target HVAC (D02.115.3051) failure +- MCR/Gate guard/Cryo team: Inform PSS team</details> + </guidance> + </pv> + <pv name="TgtGDS:ODH-RSL-011:Failure"> + <description>Device failure</description> + <latching>false</latching> + <annunciating>false</annunciating> + <guidance> + <title>[Operator Action]</title> + <details>TgtGDS:ODH-RSL-011 in utility 115a (D02.115.3064) failure +- MCR/Gate guard/Cryo team: Inform PSS team</details> + </guidance> + </pv> + <pv name="TgtGDS:ODH-RSL-012:Failure"> + <description>Device failure</description> + <latching>false</latching> + <annunciating>false</annunciating> + <guidance> + <title>[Operator Action]</title> + <details>TgtGDS:ODH-RSL-012 in utility 115a (D02.115.3064) failure +- MCR/Gate guard/Cryo team: Inform PSS team</details> + </guidance> + </pv> + <pv name="TgtGDS:ODH-RSL-013:Failure"> + <description>Device failure</description> + <latching>false</latching> + <annunciating>false</annunciating> + <guidance> + <title>[Operator Action]</title> + <details>TgtGDS:ODH-RSL-013 in utility 115a (D02.115.3064) failure +- MCR/Gate guard/Cryo team: Inform PSS team</details> + </guidance> + </pv> + <pv name="TgtGDS:ODH-RSL-014:Failure"> + <description>Device failure</description> + <latching>false</latching> + <annunciating>false</annunciating> + <guidance> + <title>[Operator Action]</title> + <details>TgtGDS:ODH-RSL-014 in Stair 005 (D02.115.3061) failure +- MCR/Gate guard/Cryo team: Inform PSS team</details> + </guidance> + </pv> + <pv name="TgtGDS:ODH-RSL-015:Failure"> + <description>Device failure</description> + <latching>false</latching> + <annunciating>false</annunciating> + <guidance> + <title>[Operator Action]</title> + <details>TgtGDS:ODH-RSL-015 in Lift hall (D02.115.3063) failure +- MCR/Gate guard/Cryo team: Inform PSS team</details> + </guidance> + </pv> + <pv name="TgtGDS:ODH-RSL-016:Failure"> + <description>Device failure</description> + <latching>false</latching> + <annunciating>false</annunciating> + <guidance> + <title>[Operator Action]</title> + <details>TgtGDS:ODH-RSL-016 in utility 115b (D02.115.3067) failure +- MCR/Gate guard/Cryo team: Inform PSS team</details> + </guidance> + </pv> + <pv name="TgtGDS:ODH-RSL-017:Failure"> + <description>Device failure</description> + <latching>false</latching> + <annunciating>false</annunciating> + <guidance> + <title>[Operator Action]</title> + <details>TgtGDS:ODH-RSL-017 in utility 115b (D02.115.3067) failure +- MCR/Gate guard/Cryo team: Inform PSS team</details> + </guidance> + </pv> + <pv name="TgtGDS:ODH-RSL-018:Failure"> + <description>Device failure</description> + <latching>false</latching> + <annunciating>false</annunciating> + <guidance> + <title>[Operator Action]</title> + <details>TgtGDS:ODH-RSL-018 in utility 115b (D02.115.3067) failure +- MCR/Gate guard/Cryo team: Inform PSS team</details> + </guidance> + </pv> + <pv name="TgtGDS:ODH-RSL-019:Failure"> + <description>Device failure</description> + <latching>false</latching> + <annunciating>false</annunciating> + <guidance> + <title>[Operator Action]</title> + <details>TgtGDS:ODH-RSL-019 in utility 115c (D02.115.4003) failure +- MCR/Gate guard/Cryo team: Inform PSS team</details> + </guidance> + </pv> + <pv name="TgtGDS:ODH-RSL-020:Failure"> + <description>Device failure</description> + <latching>false</latching> + <annunciating>false</annunciating> + <guidance> + <title>[Operator Action]</title> + <details>TgtGDS:ODH-RSL-020 in utility 115c (D02.115.4003) failure +- MCR/Gate guard/Cryo team: Inform PSS team</details> + </guidance> + </pv> + </component> + </component> + <component name="LVL150"> + <pv name="TgtGDS:ODH-Area-150:Alrm"> + <description>Zone ODH Alarm (Oxygen below 18%)</description> + <latching>false</latching> + <annunciating>false</annunciating> + <guidance> + <title>[Operator Action]</title> + <details>D02.150 zone gas evacuation alarm due to O2 less than 18% +Call cryo on call +- MCR: Follow ESS-3216323 +- Gate guard: Follow ESS-2124375 +- Cryo team: Follow ESS-5533654</details> + </guidance> + </pv> + <pv name="TgtGDS:ODH-Area-150:Warning"> + <description>Zone ODH Warning (Oxygen below 19.5%)</description> + <latching>false</latching> + <annunciating>false</annunciating> + <guidance> + <title>[Operator Action]</title> + <details>D02.150 zone ODH warning due to O2 less than 19.5% +Call cryo on call +- MCR: Follow ESS-3216323 +- Gate guard: Follow ESS-2124375 +- Cryo team: Follow ESS-1788930</details> + </guidance> + </pv> + <pv name="TgtGDS:ODH-Area-150:Error"> + <description>Zone oxygen monitor error</description> + <latching>false</latching> + <annunciating>false</annunciating> + <guidance> + <title>[Operator Action]</title> + <details>D02.150 zone gas evacuation alarm due to an error +- MCR/Gate guard/Cryo team: Inform PSS team</details> + </guidance> + </pv> + <pv name="TgtGDS:ODH-Area-150:Attention"> + <description>Zone minor issue</description> + <latching>false</latching> + <annunciating>false</annunciating> + <guidance> + <title>[Operator Action]</title> + <details>D02.150 zone has a minor issue +- MCR/Gate guard/Cryo team: Inform PSS team</details> + </guidance> + </pv> + <pv name="TgtGDS:ODH-Area-150:Maintenance"> + <description>Zone oxygen monitor in maintenance mode</description> + <latching>false</latching> + <annunciating>false</annunciating> + <guidance> + <title>[Operator Action]</title> + <details>D02.150 zone is in maintenance mode</details> + </guidance> + </pv> + <pv name="TgtGDS:ODH-Area-150:HwError"> + <description>Zone PLC HW failure</description> + <latching>false</latching> + <annunciating>false</annunciating> + <guidance> + <title>[Operator Action]</title> + <details>D02.150 zone has a PLC HW failure +- MCR/Gate guard/Cryo team: Inform PSS team</details> + </guidance> + </pv> + <pv name="TgtGDS:ODH-Area-150:BatteryLow"> + <description>Zone UPS battery low alarm while buffering</description> + <latching>false</latching> + <annunciating>false</annunciating> + <guidance> + <title>[Operator Action]</title> + <details>D02.150 zone gas evacuation alarm due to low battery alarm +- MCR/Gate guard/Cryo team: Inform PSS team</details> + </guidance> + </pv> + <pv name="TgtGDS:ODH-Area-150:ConfirmedAlrm"> + <description>Zone ODH confirmed alarm</description> + <latching>false</latching> + <annunciating>false</annunciating> + <guidance> + <title>[Operator Action]</title> + <details>D02.150 zone ODH confirmed alarm due to O2 less than 18% for more than one min or two monitors detect O2 less than 18% +Call cryo on call +- MCR: Follow ESS-3216323 +- Gate guard: Follow ESS-2124375 +- Cryo team: Follow ESS-1788930</details> + </guidance> + </pv> + <pv name="TgtGDS:ODH-Area-150:StartUp"> + <description>Zone equipment starting-up</description> + <latching>false</latching> + <annunciating>false</annunciating> + <guidance> + <title>[Operator Action]</title> + <details>D02.150 zone is in start-up mode</details> + </guidance> + </pv> + <pv name="TgtGDS:ODH-Area-150:Muted"> + <description>Zone audible alarm muted</description> + <latching>false</latching> + <annunciating>false</annunciating> + <guidance> + <title>[Operator Action]</title> + <details>D02.150 zone is muted</details> + </guidance> + </pv> + <pv name="TgtGDS:ODH-Area-150:DeviceFailure"> + <description>Zone alarm device failure</description> + <latching>false</latching> + <annunciating>false</annunciating> + <guidance> + <title>[Operator Action]</title> + <details>D02.150 zone ODH alarm device failure +- MCR/Gate guard/Cryo team: Inform PSS team</details> + </guidance> + </pv> + <pv name="TgtGDS:ODH-Area-150:FirstStgAlarm"> + <description>Zone 1st stage alarm (Hydrogen level above 10% LEL)</description> + <latching>false</latching> + <annunciating>false</annunciating> + <guidance> + <title>[Operator Action]</title> + <details>D02.150 zone gas evacuation alarm due to H2 above 10%LEL +Call cryo on call +- MCR: Follow ESS-3216323 +- Gate guard: Follow ESS-2124375 +- Cryo team: Follow ESS-5533654</details> + </guidance> + </pv> + <pv name="TgtGDS:ODH-Area-150:SecondStgAlarm"> + <description>Zone 2nd stage alarm (Hydrogen level above 25% LEL)</description> + <latching>false</latching> + <annunciating>false</annunciating> + <guidance> + <title>[Operator Action]</title> + <details>D02.150 zone gas evacuation alarm due to H2 above 25%LEL +Call cryo on call +- MCR: Follow ESS-3216323 +- Gate guard: Follow ESS-2124375 +- Cryo team: Follow ESS-5533654</details> + </guidance> + </pv> + <pv name="TgtGDS:ODH-Area-150:SpecialState"> + <description>Zone special state</description> + <latching>false</latching> + <annunciating>false</annunciating> + <guidance> + <title>[Operator Action]</title> + <details>D02.150 zone is in special state +- MCR/Gate guard/Cryo team: Inform PSS team</details> + </guidance> + </pv> + <pv name="TgtGDS:ODH-Area-150:H2_ConfirmedAlarm"> + <description>Zone H2 confirmed alarm</description> + <latching>false</latching> + <annunciating>false</annunciating> + <guidance> + <title>[Operator Action]</title> + <details>D02.150 zone gas evacuation alarm due to H2 above 100%LEL or two monitors detect H2 above 25% +Call cryo on call +- MCR: Follow ESS-3216323 +- Gate guard: Follow ESS-2124375 +- Cryo team: Follow ESS-5533654</details> + </guidance> + </pv> + <component name="ACS"> + <pv name="TgtGDS:ODH-ACS-026:Failure"> + <description>Device failure</description> + <latching>false</latching> + <annunciating>false</annunciating> + <guidance> + <title>[Operator Action]</title> + <details>TgtGDS:ODH-ACS-026 in Target HVAC (D02.150.4015) failure +- MCR/Gate guard/Cryo team: Inform PSS team</details> + </guidance> + </pv> + <pv name="TgtGDS:ODH-ACS-027:Failure"> + <description>Device failure</description> + <latching>false</latching> + <annunciating>false</annunciating> + <guidance> + <title>[Operator Action]</title> + <details>TgtGDS:ODH-ACS-027 in Hydrogen Control (D02.150.4017) failure +- MCR/Gate guard/Cryo team: Inform PSS team</details> + </guidance> + </pv> + <pv name="TgtGDS:ODH-ACS-029:Failure"> + <description>Device failure</description> + <latching>false</latching> + <annunciating>false</annunciating> + <guidance> + <title>[Operator Action]</title> + <details>TgtGDS:ODH-ACS-029 in H2 room (D02.150.4018) failure +- MCR/Gate guard/Cryo team: Inform PSS team</details> + </guidance> + </pv> + </component> + <component name="H2MON"> + <component name="H2MON4"> + <pv name="TgtGDS:ODH-H2Mon-004:H2Above10"> + <description>1st stage alarm (Hydrogen level above 10% LEL)</description> + <latching>false</latching> + <annunciating>false</annunciating> + <guidance> + <title>[Operator Action]</title> + <details>TgtGDS:ODH-H2Mon-004 monitoring A2T room (D02.115.4005) 1st stage H2 alarm- H2 above 10% LEL +Call cryo on call +- MCR: Follow ESS-3216323 +- Gate guard: Follow ESS-2124375 +- Cryo team: Follow ESS-5533654</details> + </guidance> + </pv> + <pv name="TgtGDS:ODH-H2Mon-004:H2Above25"> + <description>2nd stage alarm (Hydrogen level above 25% LEL)</description> + <latching>false</latching> + <annunciating>false</annunciating> + <guidance> + <title>[Operator Action]</title> + <details>TgtGDS:ODH-H2Mon-004 monitoring A2T room (D02.115.4005) 2nd stage H2 alarm- H2 above 25% LEL +Call cryo on call +- MCR: Follow ESS-3216323 +- Gate guard: Follow ESS-2124375 +- Cryo team: Follow ESS-5533654</details> + </guidance> + </pv> + <pv name="TgtGDS:ODH-H2Mon-004:H2Above100"> + <description>Hydrogen level above 100% LEL</description> + <latching>false</latching> + <annunciating>false</annunciating> + <guidance> + <title>[Operator Action]</title> + <details>TgtGDS:ODH-H2Mon-004 monitoring A2T room (D02.115.4005) H2 confirmed alarm- H2 above 100% LEL +Call cryo on call +- MCR: Follow ESS-3216323 +- Gate guard: Follow ESS-2124375 +- Cryo team: Follow ESS-5533654</details> + </guidance> + </pv> + <pv name="TgtGDS:ODH-H2Mon-004:SpecialState"> + <description>Special state</description> + <latching>false</latching> + <annunciating>false</annunciating> + <guidance> + <title>[Operator Action]</title> + <details>TgtGDS:ODH-H2Mon-004 monitoring A2T room (D02.115.4005) is in special state +- MCR/Gate guard/Cryo team: Inform PSS team</details> + </guidance> + </pv> + <pv name="TgtGDS:ODH-H2Mon-004:AiBadValue"> + <description>H2 level AI ADC code out of range</description> + <latching>false</latching> + <annunciating>false</annunciating> + <guidance> + <title>[Operator Action]</title> + <details>TgtGDS:ODH-H2Mon-004 monitoring A2T room (D02.115.4005) analogue input is out of range +- MCR/Gate guard/Cryo team: Inform PSS team</details> + </guidance> + </pv> + </component> + <component name="H2MON5"> + <pv name="TgtGDS:ODH-H2Mon-005:H2Above10"> + <description>1st stage alarm (Hydrogen level above 10% LEL)</description> + <latching>false</latching> + <annunciating>false</annunciating> + <guidance> + <title>[Operator Action]</title> + <details>TgtGDS:ODH-H2Mon-005 monitoring H2 room (D02.150.4018) 1st stage H2 alarm- H2 above 10% LEL +Call cryo on call +- MCR: Follow ESS-3216323 +- Gate guard: Follow ESS-2124375 +- Cryo team: Follow ESS-5533654</details> + </guidance> + </pv> + <pv name="TgtGDS:ODH-H2Mon-005:H2Above25"> + <description>2nd stage alarm (Hydrogen level above 25% LEL)</description> + <latching>false</latching> + <annunciating>false</annunciating> + <guidance> + <title>[Operator Action]</title> + <details>TgtGDS:ODH-H2Mon-005 monitoring H2 room (D02.150.4018) 2nd stage H2 alarm- H2 above 25% LEL +Call cryo on call +- MCR: Follow ESS-3216323 +- Gate guard: Follow ESS-2124375 +- Cryo team: Follow ESS-5533654</details> + </guidance> + </pv> + <pv name="TgtGDS:ODH-H2Mon-005:H2Above100"> + <description>Hydrogen level above 100% LEL</description> + <latching>false</latching> + <annunciating>false</annunciating> + <guidance> + <title>[Operator Action]</title> + <details>TgtGDS:ODH-H2Mon-005 monitoring H2 room (D02.150.4018) H2 confirmed alarm- H2 above 100% LEL +Call cryo on call +- MCR: Follow ESS-3216323 +- Gate guard: Follow ESS-2124375 +- Cryo team: Follow ESS-5533654</details> + </guidance> + </pv> + <pv name="TgtGDS:ODH-H2Mon-005:SpecialState"> + <description>Special state</description> + <latching>false</latching> + <annunciating>false</annunciating> + <guidance> + <title>[Operator Action]</title> + <details>TgtGDS:ODH-H2Mon-005 monitoring H2 room (D02.150.4018) is in special state +- MCR/Gate guard/Cryo team: Inform PSS team</details> + </guidance> + </pv> + <pv name="TgtGDS:ODH-H2Mon-005:AiBadValue"> + <description>H2 level AI ADC code out of range</description> + <latching>false</latching> + <annunciating>false</annunciating> + <guidance> + <title>[Operator Action]</title> + <details>TgtGDS:ODH-H2Mon-005 monitoring H2 room (D02.150.4018) analogue input is out of range +- MCR/Gate guard/Cryo team: Inform PSS team</details> + </guidance> + </pv> + </component> + <component name="H2MON6"> + <pv name="TgtGDS:ODH-H2Mon-006:H2Above10"> + <description>1st stage alarm (Hydrogen level above 10% LEL)</description> + <latching>false</latching> + <annunciating>false</annunciating> + <guidance> + <title>[Operator Action]</title> + <details>TgtGDS:ODH-H2Mon-006 monitoring H2 room (D02.150.4018) 1st stage H2 alarm- H2 above 10% LEL +Call cryo on call +- MCR: Follow ESS-3216323 +- Gate guard: Follow ESS-2124375 +- Cryo team: Follow ESS-5533654</details> + </guidance> + </pv> + <pv name="TgtGDS:ODH-H2Mon-006:H2Above25"> + <description>2nd stage alarm (Hydrogen level above 25% LEL)</description> + <latching>false</latching> + <annunciating>false</annunciating> + <guidance> + <title>[Operator Action]</title> + <details>TgtGDS:ODH-H2Mon-006 monitoring H2 room (D02.150.4018) 2nd stage H2 alarm- H2 above 25% LEL +Call cryo on call +- MCR: Follow ESS-3216323 +- Gate guard: Follow ESS-2124375 +- Cryo team: Follow ESS-5533654</details> + </guidance> + </pv> + <pv name="TgtGDS:ODH-H2Mon-006:H2Above100"> + <description>Hydrogen level above 100% LEL</description> + <latching>false</latching> + <annunciating>false</annunciating> + <guidance> + <title>[Operator Action]</title> + <details>TgtGDS:ODH-H2Mon-006 monitoring H2 room (D02.150.4018) H2 confirmed alarm- H2 above 100% LEL +Call cryo on call +- MCR: Follow ESS-3216323 +- Gate guard: Follow ESS-2124375 +- Cryo team: Follow ESS-5533654</details> + </guidance> + </pv> + <pv name="TgtGDS:ODH-H2Mon-006:SpecialState"> + <description>Special state</description> + <latching>false</latching> + <annunciating>false</annunciating> + <guidance> + <title>[Operator Action]</title> + <details>TgtGDS:ODH-H2Mon-006 monitoring H2 room (D02.150.4018) is in special state +- MCR/Gate guard/Cryo team: Inform PSS team</details> + </guidance> + </pv> + <pv name="TgtGDS:ODH-H2Mon-006:AiBadValue"> + <description>H2 level AI ADC code out of range</description> + <latching>false</latching> + <annunciating>false</annunciating> + <guidance> + <title>[Operator Action]</title> + <details>TgtGDS:ODH-H2Mon-006 monitoring H2 room (D02.150.4018) analogue input is out of range +- MCR/Gate guard/Cryo team: Inform PSS team</details> + </guidance> + </pv> + </component> + </component> + <component name="O2IM"> + <component name="O2IM4"> + <pv name="TgtGDS:ODH-O2iM-004:O2Below18"> + <description>ODH Alarm (Oxygen below 18%)</description> + <latching>false</latching> + <annunciating>false</annunciating> + <guidance> + <title>[Operator Action]</title> + <details>TgtGDS:ODH-O2iM-004 monitoring H2 room (D02.150.4018) ODH alarm- O2 less than 18% +Call cryo on call +- MCR: Follow ESS-3216323 +- Gate guard: Follow ESS-2124375 +- Cryo team: Follow ESS-1788930</details> + </guidance> + </pv> + <pv name="TgtGDS:ODH-O2iM-004:O2Below19_5"> + <description>ODH Warning (Oxygen below 19.5%)</description> + <latching>false</latching> + <annunciating>false</annunciating> + <guidance> + <title>[Operator Action]</title> + <details>TgtGDS:ODH-O2iM-004 monitoring H2 room (D02.150.4018) ODH warning- O2 less than 19.5% +Call cryo on call +- MCR: Follow ESS-3216323 +- Gate guard: Follow ESS-2124375 +- Cryo team: Follow ESS-1788930</details> + </guidance> + </pv> + <pv name="TgtGDS:ODH-O2iM-004:Maintenance"> + <description>Monitor maintenance mode</description> + <latching>false</latching> + <annunciating>false</annunciating> + <guidance> + <title>[Operator Action]</title> + <details>TgtGDS:ODH-O2iM-004 monitoring H2 room (D02.150.4018) is in maintenance mode</details> + </guidance> + </pv> + <pv name="TgtGDS:ODH-O2iM-004:Disconnected"> + <description>Monitor lost connection</description> + <latching>false</latching> + <annunciating>false</annunciating> + <guidance> + <title>[Operator Action]</title> + <details>TgtGDS:ODH-O2iM-004 monitoring H2 room (D02.150.4018) has lost connection +- MCR/Gate guard/Cryo team: Inform PSS team</details> + </guidance> + </pv> + <pv name="TgtGDS:ODH-O2iM-004:Failure"> + <description>Monitor failure</description> + <latching>false</latching> + <annunciating>false</annunciating> + <guidance> + <title>[Operator Action]</title> + <details>TgtGDS:ODH-O2iM-004 monitoring H2 room (D02.150.4018) failure +- MCR/Gate guard/Cryo team: Inform PSS team</details> + </guidance> + </pv> + <pv name="TgtGDS:ODH-O2iM-004:AiBadValue"> + <description>Oxygen level value is not valid</description> + <latching>false</latching> + <annunciating>false</annunciating> + <guidance> + <title>[Operator Action]</title> + <details>TgtGDS:ODH-O2iM-004 monitoring H2 room (D02.150.4018) analogue input is out of range +- MCR/Gate guard/Cryo team: Inform PSS team</details> + </guidance> + </pv> + </component> + </component> + <component name="RSL"> + <pv name="TgtGDS:ODH-RSL-026:Failure"> + <description>Device failure</description> + <latching>false</latching> + <annunciating>false</annunciating> + <guidance> + <title>[Operator Action]</title> + <details>TgtGDS:ODH-RSL-026 in Target HVAC (D02.150.4015) failure +- MCR/Gate guard/Cryo team: Inform PSS team</details> + </guidance> + </pv> + <pv name="TgtGDS:ODH-RSL-027:Failure"> + <description>Device failure</description> + <latching>false</latching> + <annunciating>false</annunciating> + <guidance> + <title>[Operator Action]</title> + <details>TgtGDS:ODH-RSL-027 in Hydrogen Control (D02.150.4017) failure +- MCR/Gate guard/Cryo team: Inform PSS team</details> + </guidance> + </pv> + <pv name="TgtGDS:ODH-RSL-028:Failure"> + <description>Device failure</description> + <latching>false</latching> + <annunciating>false</annunciating> + <guidance> + <title>[Operator Action]</title> + <details>TgtGDS:ODH-RSL-028 in H2 room (D02.150.4018) failure +- MCR/Gate guard/Cryo team: Inform PSS team</details> + </guidance> + </pv> + <pv name="TgtGDS:ODH-RSL-029:Failure"> + <description>Device failure</description> + <latching>false</latching> + <annunciating>false</annunciating> + <guidance> + <title>[Operator Action]</title> + <details>TgtGDS:ODH-RSL-029 in H2 room (D02.150.4018) failure +- MCR/Gate guard/Cryo team: Inform PSS team</details> + </guidance> + </pv> + <pv name="TgtGDS:ODH-RSL-030:Failure"> + <description>Device failure</description> + <latching>false</latching> + <annunciating>false</annunciating> + <guidance> + <title>[Operator Action]</title> + <details>TgtGDS:ODH-RSL-030 in Stair 008 +(D02.115.4004) failure - MCR/Gate guard/Cryo team: Inform PSS team</details> </guidance> </pv>