diff --git a/alarm-01.tn.esss.lu.se/ACCP.xml b/alarm-01.tn.esss.lu.se/ACCP.xml
index 32e923ac2384bed411984616067451bf665077e0..808f359b9ca27234ce67199fb7e0960f1202044b 100644
--- a/alarm-01.tn.esss.lu.se/ACCP.xml
+++ b/alarm-01.tn.esss.lu.se/ACCP.xml
@@ -1,16 +1,5 @@
 <?xml version="1.0" encoding="UTF-8" standalone="yes"?>
-<config name="ACCP">								
-	<component name="BCP Compressor">										
-		<pv name="CrS-ACCP:Cryo-PT-91004:AH">										
-			<description>BCP compressor discharge pressure high</description>										
-			<latching>true</latching>										
-			<annunciating>true</annunciating>										
-			<guidance>										
-				<title>[Cryogenics Operator Action]</title>										
-				<details>Check operating data.\nCheck the position of the output control gate; correct if necessary</details>					
-			</guidance>										
-		</pv>										
-	</component>											
+<config name="ACCP">			
 	<component name="ACCP Adsorber">
 		<component name="ACCP 20K Adsorber">
 			<pv name="CrS-ACCP:CRYO-TT-31401:AH">
@@ -3865,4 +3854,297 @@
 			</pv>
 		</component>
 	</component>
+	<component name="BCP-Compressor">										
+		<pv name="CrS-ACCP:Cryo-C-91000:GroupTrp">										
+			<description>C91000 Compressor trip</description>										
+			<latching>true</latching>										
+			<annunciating>true</annunciating>										
+			<guidance>										
+					<title>[Cryo Operator Action]</title>										
+					<details>Check operating data..\nContac Aerzen support</details>										
+			</guidance>										
+		</pv>										
+		<pv name="CrS-ACCP:Cryo-PT-91004:Sta">										
+			<description>BCP compressor discharge pressure high</description>										
+			<latching>true</latching>										
+			<annunciating>true</annunciating>										
+			<guidance>										
+					<title>[Cryo Operator Action]</title>										
+					<details>Check operating data.\nCheck the position of the output control gate; correct if necessary.</details>										
+			</guidance>										
+		</pv>										
+	</component>										
+	<component name="BCP-Discharge-temperature">										
+		<pv name="CrS-ACCP:Cryo-TT-91202:Sta">										
+			<description>BCP discharge temperature high</description>										
+			<latching>true</latching>										
+			<annunciating>true</annunciating>										
+			<guidance>										
+					<title>[Cryo Operator Action]</title>										
+					<details>Check for correct pressure ration.\nCheck the oil injection volume; correct if necessary</details>										
+			</guidance>										
+		</pv>										
+	</component>										
+	<component name="BCP-Forward-oil">										
+		<pv name="CrS-ACCP:Cryo-TT-97030:Sta">										
+			<description>BCP forward oil temperature high</description>										
+			<latching>true</latching>										
+			<annunciating>true</annunciating>										
+			<guidance>										
+					<title>[Cryo Operator Action]</title>										
+					<details>Check operating data.\nContact Aerzen support</details>										
+			</guidance>										
+		</pv>										
+	</component>										
+	<component name="BCP-FR/DS">										
+		<pv name="CrS-ACCP:Cryo-VMT-91200:Sta">										
+			<description>BCP FR / DS / 45° housing vibration high</description>										
+			<latching>true</latching>										
+			<annunciating>true</annunciating>										
+			<guidance>										
+					<title>[Cryo Operator Action]</title>										
+					<details>Check operating data.\nCheck the oil drainage; ensure unobstructed backflow.\nContact Aerzen support</details>										
+			</guidance>										
+		</pv>										
+		<pv name="CrS-ACCP:Cryo-VMT-91201:Sta">										
+			<description>BCP FR / SS / 45° housing vibration high</description>										
+			<latching>true</latching>										
+			<annunciating>true</annunciating>										
+			<guidance>										
+					<title>[Cryo Operator Action]</title>										
+					<details>Check operating data.\nCheck the oil drainage; ensure unobstructed backflow.\nContact Aerzen support</details>										
+			</guidance>										
+		</pv>										
+		<pv name="CrS-ACCP:Cryo-TT-91210:Sta">										
+			<description>BCP FR/DS  bearing temperature high</description>										
+			<latching>true</latching>										
+			<annunciating>true</annunciating>										
+			<guidance>										
+					<title>[Cryo Operator Action]</title>										
+					<details>Check operating data.\Check the lube oil temperature and pressure; correct if necessary</details>										
+			</guidance>										
+		</pv>										
+	</component>										
+	<component name="BCP-FR/SS">										
+		<pv name="CrS-ACCP:Cryo-TT-91208:Sta">										
+			<description>BCP FR/SS bearing temperature high</description>										
+			<latching>true</latching>										
+			<annunciating>true</annunciating>										
+			<guidance>										
+					<title>[Cryo Operator Action]</title>										
+					<details>Check operating data.\Check the lube oil temperature and pressure; correct if necessary</details>										
+			</guidance>										
+		</pv>										
+	</component>										
+	<component name="BCP-Gas-cooler">										
+		<pv name="CrS-ACCP:Cryo-FT-98011:Sta">										
+			<description>BCP gas cooler cooling water volume flow low</description>										
+			<latching>true</latching>										
+			<annunciating>true</annunciating>										
+			<guidance>										
+					<title>[Cryo Operator Action]</title>										
+					<details>Check operating data..\nContact Aerzen support</details>										
+			</guidance>										
+		</pv>										
+	</component>										
+	<component name="BCP-Instrument">										
+		<pv name="CrS-ACCP:Cryo-PT-99005:Sta">										
+			<description>BCP instrument air pressure low</description>										
+			<latching>true</latching>										
+			<annunciating>true</annunciating>										
+			<guidance>										
+					<title>[Cryo Operator Action]</title>										
+					<details>1. Check operating data.2. Contact Instrument air supply.</details>										
+			</guidance>										
+		</pv>										
+	</component>										
+	<component name="BCP-Main-Motor">										
+		<pv name="CrS-ACCP:Cryo-FT-98003:Sta">										
+			<description>BCP main motor cooling water volume flow low</description>										
+			<latching>true</latching>										
+			<annunciating>true</annunciating>										
+			<guidance>										
+					<title>[Cryo Operator Action]</title>										
+					<details>Check operating data..\nContact Aerzen support</details>										
+			</guidance>										
+		</pv>										
+		<pv name="CrS-ACCP:Cryo-TT-91228:Sta">										
+			<description>BCP main motor drive end side bearing temperature high</description>										
+			<latching>true</latching>										
+			<annunciating>true</annunciating>										
+			<guidance>										
+					<title>[Cryo Operator Action]</title>										
+					<details>Check operating data..\nContact Aerzen support</details>										
+			</guidance>										
+		</pv>										
+		<pv name="CrS-ACCP:Cryo-TT-91226:Sta">										
+			<description>BCP main motor non driven end bearing temperature high</description>										
+			<latching>true</latching>										
+			<annunciating>true</annunciating>										
+			<guidance>										
+					<title>[Cryo Operator Action]</title>										
+					<details>Check operating data..\nContact Aerzen support</details>										
+			</guidance>										
+		</pv>										
+		<pv name="CrS-ACCP:Cryo-TT-91220:Sta">										
+			<description>BCP main motor winding temperature high</description>										
+			<latching>true</latching>										
+			<annunciating>true</annunciating>										
+			<guidance>										
+					<title>[Cryo Operator Action]</title>										
+					<details>Check operating data..\nContact Aerzen support</details>										
+			</guidance>										
+		</pv>										
+		<pv name="CrS-ACCP:Cryo-TT-91222:Sta">										
+			<description>BCP main motor winding temperature high</description>										
+			<latching>true</latching>										
+			<annunciating>true</annunciating>										
+			<guidance>										
+					<title>[Cryo Operator Action]</title>										
+					<details>Check operating data..\nContact Aerzen support</details>										
+			</guidance>										
+		</pv>										
+		<pv name="CrS-ACCP:Cryo-TT-21224:Sta">										
+			<description>BCP main motor winding temperature high</description>										
+			<latching>true</latching>										
+			<annunciating>true</annunciating>										
+			<guidance>										
+					<title>[Cryo Operator Action]</title>										
+					<details>Check operating data..\nContact Aerzen support</details>										
+			</guidance>										
+		</pv>													
+		<pv name="CrS-ACCP:Cryo-TT-91224:Sta">										
+			<description>BCP main motor winding temperature too high</description>										
+			<latching>true</latching>										
+			<annunciating>true</annunciating>										
+			<guidance>										
+					<title>[Cryo Operator Action]</title>										
+					<details>Check operating data..\nContact Aerzen support</details>										
+			</guidance>										
+		</pv>										
+	</component>										
+	<component name="BCP-MR/DS-Bearing">										
+		<pv name="CrS-ACCP:Cryo-TT-91206:Sta">										
+			<description>BCP MR/DS bearing temperature high</description>										
+			<latching>true</latching>										
+			<annunciating>true</annunciating>										
+			<guidance>										
+					<title>[Cryo Operator Action]</title>										
+					<details>Check operating data.\Check the lube oil temperature and pressure; correct if necessary</details>										
+			</guidance>										
+		</pv>										
+		<pv name="CrS-ACCP:Cryo-TT-91204:Sta">										
+			<description>BCP MR/SS bearing temperature high</description>										
+			<latching>true</latching>										
+			<annunciating>true</annunciating>										
+			<guidance>										
+					<title>[Cryo Operator Action]</title>										
+					<details>Check operating data.\Check the lube oil temperature and pressure; correct if necessary</details>										
+			</guidance>										
+		</pv>										
+	</component>										
+	<component name="BCP-Oil_and_Gas-Skid">										
+		<pv name="CrS-ACCP:Cryo-TT-91000:Sta">										
+			<description>BCP oil and gas skid after gas cooler temperature high</description>										
+			<latching>true</latching>										
+			<annunciating>true</annunciating>										
+			<guidance>										
+					<title>[Cryo Operator Action]</title>										
+					<details>Check operating data..\nContact Aerzen support</details>										
+			</guidance>										
+		</pv>										
+		<pv name="CrS-ACCP:Cryo-PDT-91012:Sta">										
+			<description>BCP oil and gas skid oil separator differential pressure high</description>										
+			<latching>true</latching>										
+			<annunciating>true</annunciating>										
+			<guidance>										
+					<title>[Cryo Operator Action]</title>										
+					<details>Check operating data..\nContact Aerzen support</details>										
+			</guidance>										
+		</pv>										
+	</component>										
+	<component name="BCP-Oil-Cooler">										
+		<pv name="CrS-ACCP:Cryo-FT-98010:Sta">										
+			<description>BCP oil cooler cooling water volume flow  low</description>										
+			<latching>true</latching>										
+			<annunciating>true</annunciating>										
+			<guidance>										
+					<title>[Cryo Operator Action]</title>										
+					<details>Check operating data..\nContact Aerzen support</details>										
+			</guidance>										
+		</pv>										
+	</component>										
+	<component name="BCP-Oil-Filter">										
+		<pv name="CrS-ACCP:Cryo-PDT-97040:Sta">										
+			<description>BCP oil filter differential pressure high</description>										
+			<latching>true</latching>										
+			<annunciating>true</annunciating>										
+			<guidance>										
+					<title>[Cryo Operator Action]</title>										
+					<details>Check operating data..\nManually switch to the clean oil filter (double oil filter system) at compressor skid.\nContact Aerzen support</details>										
+			</guidance>										
+		</pv>										
+	</component>										
+	<component name="BCP-Oil-Separator">										
+		<pv name="CrS-ACCP:Cryo-LT-97012:Sta">										
+			<description>BCP oil separator level high</description>										
+			<latching>true</latching>										
+			<annunciating>true</annunciating>										
+			<guidance>										
+					<title>[Cryo Operator Action]</title>										
+					<details>Check operating data..\nContact Aerzen support</details>										
+			</guidance>										
+		</pv>										
+	</component>										
+	<component name="BCP-Oil-Vessel">										
+		<pv name="CrS-ACCP:Cryo-LT-97010:Sta">										
+			<description>BCP oil vessel level high</description>										
+			<latching>true</latching>										
+			<annunciating>true</annunciating>										
+			<guidance>										
+					<title>[Cryo Operator Action]</title>										
+					<details>Check operating data..\nContact Aerzen support</details>										
+			</guidance>										
+		</pv>										
+		<pv name="CrS-ACCP:Cryo-TT-97040:Sta">										
+			<description>BCP oil vessel oil temperature low</description>										
+			<latching>true</latching>										
+			<annunciating>true</annunciating>										
+			<guidance>										
+					<title>[Cryo Operator Action]</title>										
+					<details>1. Check oil cooler output and adjust if necessary. 2. Replace oil pressure regulating valve.</details>										
+			</guidance>										
+		</pv>										
+	</component>										
+	<component name="BCP-Suction">										
+		<pv name="CrS-ACCP:Cryo-PT-91003:Sta">										
+			<description>BCP suction pressure high </description>										
+			<latching>true</latching>										
+			<annunciating>true</annunciating>										
+			<guidance>										
+					<title>[Cryo Operator Action]</title>										
+					<details>1. Generate even supply pressure. 2. Position the capacity slide valve correctly.</details>										
+			</guidance>										
+		</pv>										
+		<pv name="CrS-ACCP:Cryo-TT-91200:Sta">										
+			<description>BCP suction temperature high</description>										
+			<latching>true</latching>										
+			<annunciating>true</annunciating>										
+			<guidance>										
+					<title>[Cryo Operator Action]</title>										
+					<details>Ensure that the intake temperature is correct. Inform supervisor immediately.</details>										
+			</guidance>										
+		</pv>										
+	</component>										
+	<component name="BCP-Vmy">										
+		<pv name="CrS-ACCP:Cryo-PDT-97030:Sta">										
+			<description>BCP VMY oil pressure low</description>										
+			<latching>true</latching>										
+			<annunciating>true</annunciating>										
+			<guidance>										
+					<title>[Cryo Operator Action]</title>										
+					<details>1. Clean / replace the oil filter according chapter 7.3.12 (page 103). 2. Inform customer service. 3. Reduce oil injection rate. 4. Replace oil pressure regulating valve.</details>										
+			</guidance>										
+		</pv>										
+	</component>										
 </config>
\ No newline at end of file
diff --git a/alarm-01.tn.esss.lu.se/BCP.xml b/alarm-01.tn.esss.lu.se/BCP.xml
deleted file mode 100644
index d81cac742388fa6a3e7b4422c1968c48162aada5..0000000000000000000000000000000000000000
--- a/alarm-01.tn.esss.lu.se/BCP.xml
+++ /dev/null
@@ -1,13 +0,0 @@
-<config name="ACCP">										
-    <component name="BCP-Compressor">										
-        <pv name="CrS-ACCP:Cryo-C-91000:GroupTrp">										
-            <description>Check operating data..\nContac Aerzen support</description>										
-            <latching>true</latching>										
-            <annunciating>true</annunciating>										
-            <guidance>										
-                    <title>[Cryogenics Operator Action]</title>										
-                    <details>Check operating data..\nContact Aerzen support</details>										
-            </guidance>										
-        </pv>										
-    </component>										
-</config>										
\ No newline at end of file