Invalid newline characters within widget property not supporting multiple line characters
Multiple .bob-files have widgets with the pv_name field defined by multiline variables, which is not supported in Phoebus and causes some widgets to not always render a widget correctly (showing up as a permanently disconnected PV). To solve the issue, just remove the newlines in the files listed beneath. Person who found the issue is @waltherborg whilst person who found the root of the issue is @georgweiss.
OPI: opis//10-Engineer/10-ACC/999-RF/99-Shared/rflps/support/overview-mbl.bob
Issue:
<pv_name>$(PREFIX):RFS-FilPS-$(KLY)10:IMON-RB
</pv_name>
OPI: opis//10-Engineer/10-ACC/999-RF/99-Shared/rflps/support/overviewNCL_CPI.bob
Issue:
<pv_name>$(PREFIX):RFS-FilPS-$(KLY)10:Psu-IMON-RB
</pv_name>
OPI: opis//10-Engineer/10-ACC/999-RF/99-Shared/rflps/support/overviewNCL_Thales.bob
Issue:
<pv_name>$(PREFIX):RFS-Kly-110:PwrRfl-ROI-Val
</pv_name>
OPI: opis//10-Engineer/10-ACC/999-RF/99-Shared/rflps/support/overviewLAB010.bob
Issue:
<pv_name>$(PREFIX):RFS-FilPS-$(KLY)10:Psu-IMON-RB
</pv_name>