Skip to content
Snippets Groups Projects

Compare revisions

Changes are shown as if the source revision was being merged into the target revision. Learn more about comparing revisions.

Source

Select target project
No results found

Target

Select target project
  • accop/beast-config
  • alarm-server/alarm-server-config
  • rafaelmontano/beast-config
  • waynelewis/beast-config
  • krisztianloki/beast-config
  • miklosboros/beast-config
  • cryo/beast-config
  • pernilsson2/beast-config
  • andersharrisson/alarm-server-config
  • artempetrushenko/beast-config
  • gabrielfedel/beast-config
  • marcmunoz/beast-config
  • loranthorvath/alarm-server-config-thcslrnthrvth-1115
  • saeedhaghtalab/beast-config
  • antonisimelio/alarm-server-config
  • alfiorizzo/beast-config
  • danielecosco/alarm-server-config
  • laispessine/alarm-server-config
  • martinek/alarm-server-config
  • adalbertofontoura/alarm-server-config
  • SRF_Section/control-room-projects/alarm-server-config
  • dawiddwojewski/alarm-server-config
  • emilioasensiconejero/alarm-server-config
  • balazsmolnar/alarm-server-config
  • lucaporzio/alarm-server-config
  • attilahorvath/alarm-server-config
  • aminhosseini/alarm-server-config
  • domagaladominik/alarm-server-config
  • lucianocarneiro/alarm-server-config
  • gabrielfedel/alarm-server-config
  • balintepinger/alarm-server-config
  • dennishasselgren/alarm-server-config
  • haraldligander/alarm-server-config
  • stefanopavinato/alarm-server-config
  • wojciechbinczyk/alarm-server-config
  • markuskristensson/alarm-server-config
  • andrebengtsson/alarm-server-config
  • mateusznabywaniec/alarm-server-config
  • joricklochet/alarm-server-config-mrcs
  • joricklochet/alarm-server-config-tiwccs
  • joricklochet/alarm-server-config-tswcs
  • josecardoso/alarm-server-config
  • carlosneto/alarm-server-config
43 results
Show changes
Commits on Source (162)
Showing
with 54295 additions and 34958 deletions
......@@ -1668,6 +1668,15 @@
<details>Check vacuum sensor</details>
</guidance>
</pv>
<pv name="CrS-ACCP:CRYO-LT-63000:AL">
<description>Dewar Alarm Level Low</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Operator Action]</title>
<details>Check dewar level</details>
</guidance>
</pv>
<pv name="CrS-ACCP:CRYO-PT-39001:AH">
<description>Coldbox insulation vacuum high</description>
<latching>false</latching>
......@@ -3826,299 +3835,1269 @@
</guidance>
</pv>
</component>
</component>
<component name="BCP-Compressor">
<pv name="CrS-ACCP:Cryo-C-91000:GroupTrp">
<description>C91000 Compressor trip</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>Check operating data..\nContact Aerzen support</details>
</guidance>
</pv>
<pv name="CrS-ACCP:Cryo-C-91000:EmerStop">
<description>C91000 emergency stop BCP active</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<component name="ACCP WCS BCP Compressor">
<pv name="CrS-ACCP:Cryo-C-91000:GroupTrp">
<description> ACCP - C24000 Compressor group trip BCP</description>
<latching>false</latching>
<annunciating>true</annunciating>
<delay>4</delay>
<guidance>
<title>[Cryo Operator Action]</title>
<details>Call Cryo on-call +46 46 888 31 66 Tell them that ACCP BCP Compressor have tripped</details>
</guidance>
</pv>
<pv name="CrS-ACCP:Cryo-C-91000:PowerRailF">
<description> G901 Power-Rail fault</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>Check operating data..\nContact Aerzen support</details>
</guidance>
</pv>
<pv name="CrS-ACCP:Cryo-PT-91004:Sta">
<description>BCP compressor discharge pressure high</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>Check operating data.\nCheck the position of the output control gate; correct if necessary.</details>
</guidance>
</pv>
</component>
<component name="BCP-Instrument-Air">
<pv name="CrS-ACCP:Cryo-PT-98005:Sta">
<description>BCP instrument air pressure low</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>1. Check operating data.2. Contact Instrument Air supply.</details>
</guidance>
</pv>
</component>
<component name="BCP-Discharge-temperature">
<pv name="CrS-ACCP:Cryo-TT-91202:Sta">
<description>BCP discharge temperature high</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>Check for correct pressure ration.\nCheck the oil injection volume; correct if necessary</details>
</guidance>
</pv>
</component>
<component name="BCP-Forward-oil">
<pv name="CrS-ACCP:Cryo-TT-97030:Sta">
<description>BCP forward oil temperature high</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>Check operating data.\nContact Aerzen support</details>
</guidance>
</pv>
</component>
<component name="BCP-FR/DS">
<pv name="CrS-ACCP:Cryo-VMT-91200:Sta">
<description>BCP FR / DS / 45° housing vibration high</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>Check operating data.\nCheck the oil drainage; ensure unobstructed backflow.\nContact Aerzen support</details>
</guidance>
</pv>
<pv name="CrS-ACCP:Cryo-VMT-91201:Sta">
<description>BCP FR / SS / 45° housing vibration high</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>Check operating data.\nCheck the oil drainage; ensure unobstructed backflow.\nContact Aerzen support</details>
</guidance>
</pv>
<pv name="CrS-ACCP:Cryo-TT-91210:Sta">
<description>BCP FR/DS bearing temperature high</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>Check operating data.\Check the lube oil temperature and pressure; correct if necessary</details>
</guidance>
</pv>
</component>
<component name="BCP-FR/SS">
<pv name="CrS-ACCP:Cryo-TT-91208:Sta">
<description>BCP FR/SS bearing temperature high</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>Check operating data.\Check the lube oil temperature and pressure; correct if necessary</details>
</guidance>
</pv>
</component>
<component name="BCP-Gas-cooler">
<pv name="CrS-ACCP:Cryo-FT-98011:Sta">
<description>BCP gas cooler cooling water volume flow low</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>Check operating data..\nContact Aerzen support</details>
</guidance>
</pv>
</component>
<component name="BCP-Main-Motor">
<pv name="CrS-ACCP:Cryo-FT-98003:Sta">
<description>BCP main motor cooling water volume flow low</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>Check operating data..\nContact Aerzen support</details>
</guidance>
</pv>
<pv name="CrS-ACCP:Cryo-TT-91228:Sta">
<description>BCP main motor drive end side bearing temperature high</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>Check operating data..\nContact Aerzen support</details>
</guidance>
</pv>
<pv name="CrS-ACCP:Cryo-TT-91226:Sta">
<description>BCP main motor non driven end bearing temperature high</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>Check operating data..\nContact Aerzen support</details>
</guidance>
</pv>
<pv name="CrS-ACCP:Cryo-TT-91220:Sta">
<description>BCP main motor winding temperature high</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>Check operating data..\nContact Aerzen support</details>
</guidance>
</pv>
<pv name="CrS-ACCP:Cryo-TT-91222:Sta">
<description>BCP main motor winding temperature high</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>Check operating data..\nContact Aerzen support</details>
</guidance>
</pv>
<pv name="CrS-ACCP:Cryo-TT-91224:Sta">
<description>BCP main motor winding temperature too high</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>Check operating data..\nContact Aerzen support</details>
</guidance>
</pv>
</component>
<component name="BCP-MR/DS-Bearing">
<pv name="CrS-ACCP:Cryo-TT-91206:Sta">
<description>BCP MR/DS bearing temperature high</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>Check operating data.\Check the lube oil temperature and pressure; correct if necessary</details>
</guidance>
</pv>
<pv name="CrS-ACCP:Cryo-TT-91204:Sta">
<description>BCP MR/SS bearing temperature high</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>Check operating data.\Check the lube oil temperature and pressure; correct if necessary</details>
</guidance>
</pv>
</component>
<component name="BCP-Oil_and_Gas-Skid">
<pv name="CrS-ACCP:Cryo-TT-91000:Sta">
<description>BCP oil and gas skid after gas cooler temperature high</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>Check operating data..\nContact Aerzen support</details>
</guidance>
</pv>
<pv name="CrS-ACCP:Cryo-PDT-91012:Sta">
<description>BCP oil and gas skid oil separator differential pressure high</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>Check operating data..\nContact Aerzen support</details>
</guidance>
</pv>
</component>
<component name="BCP-Oil-Cooler">
<pv name="CrS-ACCP:Cryo-FT-98010:Sta">
<description>BCP oil cooler cooling water volume flow low</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>Check operating data..\nContact Aerzen support</details>
</guidance>
</pv>
</component>
<component name="BCP-Oil-Filter">
<pv name="CrS-ACCP:Cryo-PDT-97040:Sta">
<description>BCP oil filter differential pressure high</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>Check operating data..\nManually switch to the clean oil filter (double oil filter system) at compressor skid.\nContact Aerzen support</details>
</guidance>
</pv>
</component>
<component name="BCP-Oil-Separator">
<pv name="CrS-ACCP:Cryo-LT-97012:Sta">
<description>BCP oil separator level high</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>Check operating data..\nContact Aerzen support</details>
</guidance>
</pv>
</component>
<component name="BCP-Oil-Vessel">
<pv name="CrS-ACCP:Cryo-LT-97010:Sta">
<description>BCP oil vessel level high</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>Check operating data..\nContact Aerzen support</details>
</guidance>
</pv>
<pv name="CrS-ACCP:Cryo-TT-97040:Sta">
<description>BCP oil vessel oil temperature low</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>1. Check oil cooler output and adjust if necessary. 2. Replace oil pressure regulating valve.</details>
</guidance>
</pv>
</component>
<component name="BCP-Suction">
<pv name="CrS-ACCP:Cryo-PT-91003:Sta">
<description>BCP suction pressure high </description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>1. Generate even supply pressure. 2. Position the capacity slide valve correctly.</details>
</guidance>
</pv>
<pv name="CrS-ACCP:Cryo-TT-91200:Sta">
<description>BCP suction temperature high</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>Ensure that the intake temperature is correct. Inform supervisor immediately.</details>
</guidance>
</pv>
</component>
<component name="BCP-Vmy">
<pv name="CrS-ACCP:Cryo-PDT-97030:Sta">
<description>BCP VMY oil pressure low</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>1. Clean / replace the oil filter according chapter 7.3.12 (page 103). 2. Inform customer service. 3. Reduce oil injection rate. 4. Replace oil pressure regulating valve.</details>
</guidance>
</pv>
</guidance>
</pv>
<pv name="CrS-ACCP:Cryo-C-91000:PhaseSeqF">
<description> K11 Phase sequence fault</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>Check operating data..\nContact Aerzen support</details>
</guidance>
</pv>
<pv name="CrS-ACCP:Cryo-C-91000:OpticalLinkModF">
<description> K461 optical link modul fault </description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>Check operating data..\nContact Aerzen support</details>
</guidance>
</pv>
<pv name="CrS-ACCP:Cryo-C-91000:CommunicationTrip">
<description> Communication with ACCP fault</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>Check operating data..\nContact Aerzen support</details>
</guidance>
</pv>
<pv name="CrS-ACCP:Cryo-C-91000:StopTimeToLong">
<description> Comprerssor Stopping Time to long</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>Check operating data..\nContact Aerzen support</details>
</guidance>
</pv>
<pv name="CrS-ACCP:Cryo-C-91000:ExternalRelease">
<description> Compressor external release signal from ACCP Fault</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>Check operating data..\nContact Aerzen support</details>
</guidance>
</pv>
<pv name="CrS-ACCP:Cryo-C-91000:AllDrivesnotAuto">
<description> Compressor NOT all drives in Auto </description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>Check operating data..\n</details>
</guidance>
</pv>
<pv name="CrS-ACCP:Cryo-C-91000:StartTimeToLong">
<description> Compressor Start Time to long</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>Check operating data..\nContact Aerzen support</details>
</guidance>
</pv>
<pv name="CrS-ACCP:Cryo-C-91000:ControlVolFault">
<description> Control voltage A DC 24 V fault </description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>Check operating data..\nContact Aerzen support</details>
</guidance>
</pv>
<pv name="CrS-ACCP:Cryo-C-91000:ControlVolFault_1">
<description> Control voltage B DC 24 V fault </description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>Check operating data..\nContact Aerzen support</details>
</guidance>
</pv>
<pv name="CrS-ACCP:Cryo-C-91000:EmerStop">
<description> Emergency stop control cabinet active</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>Check Painel Emergency Stop push button</details>
</guidance>
</pv>
<pv name="CrS-ACCP:Cryo-CV-97020:Discrepancycontrol">
<description> CV 97020 capacity valve: Discrepancy control - feedback fault </description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>Check operating data..\nContact Aerzen support</details>
</guidance>
</pv>
<pv name="CrS-ACCP:Cryo-CV-91000:PositionFault">
<description> CV-91000 position fault bypass control valve </description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>Check operating data..\nContact Aerzen support</details>
</guidance>
</pv>
<pv name="CrS-ACCP:Cryo-CV-98010:PositionFault">
<description> CV-98010 position fault cooling water control valve motor </description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>Check operating data..\nContact Aerzen support</details>
</guidance>
</pv>
<pv name="CrS-ACCP:Cryo-CV-98011:PositionFault">
<description> CV-98011 position fault cooling water control valve oil cooler </description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>Check operating data..\nContact Aerzen support</details>
</guidance>
</pv>
<pv name="CrS-ACCP:Cryo-CV-98012:PositionFault">
<description> CV-98012 position fault cooling water control valve gas cooler </description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>Check operating data..\nContact Aerzen support</details>
</guidance>
</pv>
<pv name="CrS-ACCP:Cryo-EH-91000:Discrepancycontrol">
<description> EH-91000 Standstill heating main drive: Discrepancy control - feedback fault </description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>Check operating data..\nContact Aerzen support</details>
</guidance>
</pv>
<pv name="CrS-ACCP:Cryo-EH-91000:MotorprotectionSw">
<description> EH-91000 Standstill heating main drive: Motor protection switch </description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>Check operating data..\nContact Aerzen support</details>
</guidance>
</pv>
<pv name="CrS-ACCP:Cryo-EH-97201:Discrepancycontrol">
<description> EH-97201 oil heater: Discrepancy control - feedback faul </description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>Check operating data..\nContact Aerzen support</details>
</guidance>
</pv>
<pv name="CrS-ACCP:Cryo-EH-97201:MotorprotectionSw">
<description> EH-97201 oil heater: Motor protection switch </description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>Check operating data..\nContact Aerzen support</details>
</guidance>
</pv>
<pv name="CrS-ACCP:Cryo-FT-97000:LO">
<description> FT-97000 volume flow oil forward mechanical seal: Limit L </description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>Check operating data..\nContact Aerzen support</details>
</guidance>
</pv>
<pv name="CrS-ACCP:Cryo-FT-97000:LOLO">
<description> FT-97000 volume flow oil forward mechanical seal: Limit LL </description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>Check operating data..\nContact Aerzen support</details>
</guidance>
</pv>
<pv name="CrS-ACCP:Cryo-FT-97000:Qbad">
<description> FT-97000 volume flow oil forward mechanical seal: QBAD </description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>Check operating data..\nContact Aerzen support</details>
</guidance>
</pv>
<pv name="CrS-ACCP:Cryo-FT-98003:LO">
<description> FT-98003 volume flow cooling water motor: Limit L </description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>Check operating data..\nContact Aerzen support</details>
</guidance>
</pv>
<pv name="CrS-ACCP:Cryo-FT-98003:Qbad">
<description> FT-98003 volume flow cooling water motor: QBAD </description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>Check operating data..\nContact Aerzen support</details>
</guidance>
</pv>
<pv name="CrS-ACCP:Cryo-FT-98010:LO">
<description> FT-98010 volume flow cooling water oil cooler: Limit L </description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>Check operating data..\nContact Aerzen support</details>
</guidance>
</pv>
<pv name="CrS-ACCP:Cryo-FT-98010:Qbad">
<description> FT-98010 volume flow cooling water oil cooler: QBAD </description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>Check operating data..\nContact Aerzen support</details>
</guidance>
</pv>
<pv name="CrS-ACCP:Cryo-FT-98011:LO">
<description> FT-98011 volume flow cooling water gas cooler: Limit L </description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>Check operating data..\nContact Aerzen support</details>
</guidance>
</pv>
<pv name="CrS-ACCP:Cryo-FT-98011:Qbad">
<description> FT-98011 volume flow cooling water gas cooler: QBAD </description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>Check operating data..\nContact Aerzen support</details>
</guidance>
</pv>
<pv name="CrS-ACCP:Cryo-GT-91200:PositionFault">
<description> GT-91200 slide valve position: Position fault </description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>Check operating data..\nContact Aerzen support</details>
</guidance>
</pv>
<pv name="CrS-ACCP:Cryo-CV-91000:Sta">
<description> GT-91204 position transmitter bypass control valve: QBAD </description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>Check operating data..\nContact Aerzen support</details>
</guidance>
</pv>
<pv name="CrS-ACCP:Cryo-CV-97020:PositionFault">
<description> GT-91208 position transmitter slide valve speed control valve: Position fault </description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>Check operating data..\nContact Aerzen support</details>
</guidance>
</pv>
<pv name="CrS-ACCP:Cryo-CV-97020:Sta">
<description> GT-91208 position transmitter slide valve speed control valve: QBAD </description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>Check operating data..\nContact Aerzen support</details>
</guidance>
</pv>
<pv name="CrS-ACCP:Cryo-TV-97014:PositionFault">
<description> GT-97009 position transmitter oil temperature control valve: Position fault </description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>Check operating data..\nContact Aerzen support</details>
</guidance>
</pv>
<pv name="CrS-ACCP:Cryo-TV-97014:Sta">
<description> GT-97009 position transmitter oil temperature control valve: QBAD </description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>Check operating data..\nContact Aerzen support</details>
</guidance>
</pv>
<pv name="CrS-ACCP:Cryo-CV-98012:Sta">
<description> GT-98012 position transmitter cooling water control valve gas cooler: QBAD </description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>Check operating data..\nContact Aerzen support</details>
</guidance>
</pv>
<pv name="CrS-ACCP:Cryo-CV-98010:Sta">
<description> GT-98014 position transmitter cooling water control valve motor: QBAD </description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>Check operating data..\nContact Aerzen support</details>
</guidance>
</pv>
<pv name="CrS-ACCP:Cryo-CV-98011:Sta">
<description> GT-98015 position transmitter cooling water control valve oil cooler: QBAD </description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>Check operating data..\nContact Aerzen support</details>
</guidance>
</pv>
<pv name="CrS-ACCP:Cryo-C-91000:LS91220_LeakCoolWa">
<description> LS-91220 leakage cooling-water main drive </description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>Check operating data..\nContact Aerzen support</details>
</guidance>
</pv>
<pv name="CrS-ACCP:Cryo-LT-97010:HI">
<description> LT-97010 level oil vessel: Limit H </description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>Check operating data..\nContact Aerzen support</details>
</guidance>
</pv>
<pv name="CrS-ACCP:Cryo-LT-97010:LO">
<description> LT-97010 level oil vessel: Limit L </description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>Check operating data..\nContact Aerzen support</details>
</guidance>
</pv>
<pv name="CrS-ACCP:Cryo-LT-97010:Qbad">
<description> LT-97010 level oil vessel: QBAD </description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>Check operating data..\nContact Aerzen support</details>
</guidance>
</pv>
<pv name="CrS-ACCP:Cryo-LT-97012:HI">
<description> LT-97012 level oil separator: Limit H </description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>Check operating data..\nContact Aerzen support</details>
</guidance>
</pv>
<pv name="CrS-ACCP:Cryo-LT-97012:LO">
<description> LT-97012 level oil separator: Limit L </description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>Check operating data..\nContact Aerzen support</details>
</guidance>
</pv>
<pv name="CrS-ACCP:Cryo-LT-97012:Qbad">
<description> LT-97012 level oil separator: QBAD </description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>Check operating data..\nContact Aerzen support</details>
</guidance>
</pv>
<pv name="CrS-ACCP:Cryo-M-91000:Discrepancycontrol">
<description> M-91000 main drive: Discrepancy control - feedback fault </description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>Check operating data..\nContact Aerzen support</details>
</guidance>
</pv>
<pv name="CrS-ACCP:Cryo-M-91000:MotorprotectionSw">
<description> M-91000 main drive: Motor protection switch </description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>Check operating data..\nContact Aerzen support</details>
</guidance>
</pv>
<pv name="CrS-ACCP:Cryo-SC-97012A:Discrepancycontrol">
<description> M-97012A oil pump A: Discrepancy control - feedback fault </description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>Check operating data..\nContact Aerzen support</details>
</guidance>
</pv>
<pv name="CrS-ACCP:Cryo-SC-97012A:MotorprotectionSw">
<description> M-97012A oil pump A: Motor protection switch </description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>Check operating data..\nContact Aerzen support</details>
</guidance>
</pv>
<pv name="CrS-ACCP:Cryo-SC-97012B:Discrepancycontrol">
<description> M-97012B oil pump B: Discrepancy control - feedback fault </description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>Check operating data..\nContact Aerzen support</details>
</guidance>
</pv>
<pv name="CrS-ACCP:Cryo-SC-97012B:MotorprotectionSw">
<description> M-97012B oil pump B: Motor protection switch </description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>Check operating data..\nContact Aerzen support</details>
</guidance>
</pv>
<pv name="CrS-ACCP:Cryo-PDT-91005:HI">
<description> PDT-91005 differential pressure suction side block valve and suction strainer: Limit H </description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>Check operating data..\nContact Aerzen support</details>
</guidance>
</pv>
<pv name="CrS-ACCP:Cryo-PDT-91005:Qbad">
<description> PDT-91005 differential pressure suction side block valve and suction strainer: QBAD </description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>Check operating data..\nContact Aerzen support</details>
</guidance>
</pv>
<pv name="CrS-ACCP:Cryo-PDT-91006:HI">
<description> PDT-91006 025 bar differential pressure compressor: Limit H </description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>Check operating data..\nContact Aerzen support</details>
</guidance>
</pv>
<pv name="CrS-ACCP:Cryo-PDT-91006:HIHI">
<description> PDT-91006 025 bar differential pressure compressor: Limit HH </description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>Check operating data..\nContact Aerzen support</details>
</guidance>
</pv>
<pv name="CrS-ACCP:Cryo-PDT-91006:LO">
<description> PDT-91006 025 bar differential pressure compressor: Limit L </description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>Check operating data..\nContact Aerzen support</details>
</guidance>
</pv>
<pv name="CrS-ACCP:Cryo-PDT-91006:Qbad">
<description> PDT-91006 025 bar differential pressure compressor: QBAD </description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>Check operating data..\nContact Aerzen support</details>
</guidance>
</pv>
<pv name="CrS-ACCP:Cryo-PDT-91012:HI">
<description> PDT-91012 differential pressure oil separator: Limit H </description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>Check operating data..\nContact Aerzen support</details>
</guidance>
</pv>
<pv name="CrS-ACCP:Cryo-PDT-91012:Qbad">
<description> PDT-91012 differential pressure oil separator: QBAD </description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>Check operating data..\nContact Aerzen support</details>
</guidance>
</pv>
<pv name="CrS-ACCP:Cryo-PDT-97030:LO">
<description> PDT-97030 oil pressure VMY: Limit L </description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>1. Clean / replace the oil filter according chapter 7.3.12 (page 103). 2. Inform customer service. 3. Reduce oil injection rate. 4. Replace oil pressure regulating valve.</details>
</guidance>
</pv>
<pv name="CrS-ACCP:Cryo-PDT-97030:LOLO">
<description> PDT-97030 oil pressure VMY: Limit LL </description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>1. Clean / replace the oil filter according chapter 7.3.12 (page 103). 2. Inform customer service. 3. Reduce oil injection rate. 4. Replace oil pressure regulating valve.</details>
</guidance>
</pv>
<pv name="CrS-ACCP:Cryo-PDT-97030:Qbad">
<description> PDT-97030 oil pressure VMY: QBAD </description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>1. Clean / replace the oil filter according chapter 7.3.12 (page 103). 2. Inform customer service. 3. Reduce oil injection rate. 4. Replace oil pressure regulating valve.</details>
</guidance>
</pv>
<pv name="CrS-ACCP:Cryo-PDT-97040:HI">
<description> PDT-97040 differential pressure oil filter: Limit H </description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>Check operating data..\nManually switch to the clean oil filter (double oil filter system) at compressor skid.\nContact Aerzen support</details>
</guidance>
</pv>
<pv name="CrS-ACCP:Cryo-PDT-97040:Qbad">
<description> PDT-97040 differential pressure oil filter: QBAD </description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>Check operating data..\nContact Aerzen support</details>
</guidance>
</pv>
<pv name="CrS-ACCP:Cryo-PT-90000:HI">
<description> PT-90000 guard system pressure: Limit H </description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>Check operating data..\nContact Aerzen support</details>
</guidance>
</pv>
<pv name="CrS-ACCP:Cryo-PT-90000:LO">
<description> PT-90000 guard system pressure: Limit L </description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>Check operating data..\nContact Aerzen support</details>
</guidance>
</pv>
<pv name="CrS-ACCP:Cryo-PT-90000:Qbad">
<description> PT-90000 guard system pressure: QBAD </description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>Check operating data..\nContact Aerzen support</details>
</guidance>
</pv>
<pv name="CrS-ACCP:Cryo-PT-91000:HI">
<description> PT-91000 suction pressure after suction strainer: Limit H </description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>1. Generate even supply pressure. 2. Position the capacity slide valve correctly.</details>
</guidance>
</pv>
<pv name="CrS-ACCP:Cryo-PT-91000:LO">
<description> PT-91000 suction pressure after suction strainer: Limit L </description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>1. Generate even supply pressure. 2. Position the capacity slide valve correctly.</details>
</guidance>
</pv>
<pv name="CrS-ACCP:Cryo-PT-91000:LOLO">
<description> PT-91000 suction pressure after suction strainer: Limit LL </description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>1. Generate even supply pressure. 2. Position the capacity slide valve correctly.</details>
</guidance>
</pv>
<pv name="CrS-ACCP:Cryo-PT-91000:Qbad">
<description> PT-91000 suction pressure after suction strainer: QBAD </description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>1. Generate even supply pressure. 2. Position the capacity slide valve correctly.</details>
</guidance>
</pv>
<pv name="CrS-ACCP:Cryo-PT-91003:Qbad">
<description> PT-91003 suction pressure: Limit QBAD </description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>1. Generate even supply pressure. 2. Position the capacity slide valve correctly.</details>
</guidance>
</pv>
<pv name="CrS-ACCP:Cryo-PT-91004:HI">
<description> PT-91004 discharge pressure compressor: Limit H </description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>Check operating data.\nCheck the position of the output control gate; correct if necessary.</details>
</guidance>
</pv>
<pv name="CrS-ACCP:Cryo-PT-91004:HIHI">
<description> PT-91004 discharge pressure compressor: Limit HH </description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>Check operating data.\nCheck the position of the output control gate; correct if necessary.</details>
</guidance>
</pv>
<pv name="CrS-ACCP:Cryo-PT-91004:Qbad">
<description> PT-91004 discharge pressure compressor: QBAD </description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>Check operating data.\nCheck the position of the output control gate; correct if necessary.</details>
</guidance>
</pv>
<pv name="CrS-ACCP:Cryo-PT-91010:Qbad">
<description> PT-91010 discharge pressure after gas cooler: QBAD </description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>Check operating data..\nContact Aerzen support</details>
</guidance>
</pv>
<pv name="CrS-ACCP:Cryo-PT-98005:LO">
<description> PT-99005 Pressure instrument air: Limit L </description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>1. Check operating data.2. Contact Instrument air supply.</details>
</guidance>
</pv>
<pv name="CrS-ACCP:Cryo-PT-98005:Qbad">
<description> PT-99005 Pressure instrument air: Limit QBAD </description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>Check operating data..\nContact Aerzen support</details>
</guidance>
</pv>
<pv name="CrS-ACCP:Cryo-PV-91000:Discrepancycontrol">
<description> PV-91000 suction side valve: Discrepancy control - feedback fault </description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>Check operating data..\nContact Aerzen support</details>
</guidance>
</pv>
<pv name="CrS-ACCP:Cryo-PV-91000:ValveFault">
<description> PV-91000 suction side valve: Fault </description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>Check operating data..\nContact Aerzen support</details>
</guidance>
</pv>
<pv name="CrS-ACCP:Cryo-PV-97406:Discrepancycontrol">
<description> PV-97406 Oil injection valve: Discrepancy control - feedback fault </description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>Check operating data..\nContact Aerzen support</details>
</guidance>
</pv>
<pv name="CrS-ACCP:Cryo-PV-97406:ValveFault">
<description> PV-97406 Oil injection valve: Fault </description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>Check operating data..\nContact Aerzen support</details>
</guidance>
</pv>
<pv name="CrS-ACCP:Cryo-PV-97415:Discrepancycontrol">
<description> PV-97415 Oil pre-lubrication valve: Discrepancy control - feedback fault </description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>Check operating data..\nContact Aerzen support</details>
</guidance>
</pv>
<pv name="CrS-ACCP:Cryo-PV-97415:ValveFault">
<description> PV-97415 Oil pre-lubrication valve: Fault </description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>Check operating data..\nContact Aerzen support</details>
</guidance>
</pv>
<pv name="CrS-ACCP:Cryo-TT-91000:HI">
<description> TI-91000 temperature after gas cooler: Limit H </description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>Check operating data..\nContact Aerzen support</details>
</guidance>
</pv>
<pv name="CrS-ACCP:Cryo-TT-91000:HIHI">
<description> TI-91000 temperature after gas cooler: Limit HH </description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>Check operating data..\nContact Aerzen support</details>
</guidance>
</pv>
<pv name="CrS-ACCP:Cryo-TT-91000:Qbad">
<description> TI-91000 temperature after gas cooler: QBAD </description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>Check operating data..\nContact Aerzen support</details>
</guidance>
</pv>
<pv name="CrS-ACCP:Cryo-TT-91200:HI">
<description> TI-91200 suction temperature: Limit H </description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>Ensure that the intake temperature is correct. Inform supervisor immediately.</details>
</guidance>
</pv>
<pv name="CrS-ACCP:Cryo-TT-91200:LO">
<description> TI-91200 suction temperature: Limit L </description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>Ensure that the intake temperature is correct. Inform supervisor immediately.</details>
</guidance>
</pv>
<pv name="CrS-ACCP:Cryo-TT-91200:Qbad">
<description> TI-91200 suction temperature: QBAD </description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>Ensure that the intake temperature is correct. Inform supervisor immediately.</details>
</guidance>
</pv>
<pv name="CrS-ACCP:Cryo-TT-91202:HI">
<description> TI-91202 discharge temperature: Limit H </description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>Check for correct pressure ration.\nCheck the oil injection volume; correct if necessary</details>
</guidance>
</pv>
<pv name="CrS-ACCP:Cryo-TT-91202:HIHI">
<description> TI-91202 discharge temperature: Limit HH </description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>Check for correct pressure ration.\nCheck the oil injection volume; correct if necessary</details>
</guidance>
</pv>
<pv name="CrS-ACCP:Cryo-TT-91202:Qbad">
<description> TI-91202 discharge temperature: QBAD </description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>Check for correct pressure ration.\nCheck the oil injection volume; correct if necessary</details>
</guidance>
</pv>
<pv name="CrS-ACCP:Cryo-TT-91204:HI">
<description> TI-91204 compressor bearing temperature MRSS: Limit H </description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>Check for correct pressure ration.\nCheck the oil injection volume; correct if necessary</details>
</guidance>
</pv>
<pv name="CrS-ACCP:Cryo-TT-91204:HIHI">
<description> TI-91204 compressor bearing temperature MRSS: Limit HH </description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>Check for correct pressure ration.\nCheck the oil injection volume; correct if necessary</details>
</guidance>
</pv>
<pv name="CrS-ACCP:Cryo-TT-91204:Qbad">
<description> TI-91204 compressor bearing temperature MRSS: QBAD </description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>Check for correct pressure ration.\nCheck the oil injection volume; correct if necessary</details>
</guidance>
</pv>
<pv name="CrS-ACCP:Cryo-TT-91206:HI">
<description> TI-91206 compressor bearing temperature MRDS: Limit H </description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>Check for correct pressure ration.\nCheck the oil injection volume; correct if necessary</details>
</guidance>
</pv>
<pv name="CrS-ACCP:Cryo-TT-91206:HIHI">
<description> TI-91206 compressor bearing temperature MRDS: Limit HH </description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>Check for correct pressure ration.\nCheck the oil injection volume; correct if necessary</details>
</guidance>
</pv>
<pv name="CrS-ACCP:Cryo-TT-91206:Qbad">
<description> TI-91206 compressor bearing temperature MRDS: QBAD </description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>Check for correct pressure ration.\nCheck the oil injection volume; correct if necessary</details>
</guidance>
</pv>
<pv name="CrS-ACCP:Cryo-TT-91208:HI">
<description> TI-91208 compressor bearing temperature FRSS: Limit H </description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>Check operating data.\Check the lube oil temperature and pressure; correct if necessary</details>
</guidance>
</pv>
<pv name="CrS-ACCP:Cryo-TT-91208:HIHI">
<description> TI-91208 compressor bearing temperature FRSS: Limit HH </description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>Check operating data.\Check the lube oil temperature and pressure; correct if necessary</details>
</guidance>
</pv>
<pv name="CrS-ACCP:Cryo-TT-91208:Qbad">
<description> TI-91208 compressor bearing temperature FRSS: QBAD </description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>Check operating data.\Check the lube oil temperature and pressure; correct if necessary</details>
</guidance>
</pv>
<pv name="CrS-ACCP:Cryo-TT-91210:HI">
<description> TI-91210 compressor bearing temperature FRDS: Limit H </description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>Check operating data.\Check the lube oil temperature and pressure; correct if necessary</details>
</guidance>
</pv>
<pv name="CrS-ACCP:Cryo-TT-91210:HIHI">
<description> TI-91210 compressor bearing temperature FRDS: Limit HH </description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>Check operating data.\Check the lube oil temperature and pressure; correct if necessary</details>
</guidance>
</pv>
<pv name="CrS-ACCP:Cryo-TT-91210:Qbad">
<description> TI-91210 compressor bearing temperature FRDS: QBAD </description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>Check operating data.\Check the lube oil temperature and pressure; correct if necessary</details>
</guidance>
</pv>
<pv name="CrS-ACCP:Cryo-TT-91220:HI">
<description> TI-91220 winding temperature U: Limit H </description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>Check operating data..\nContact Aerzen support</details>
</guidance>
</pv>
<pv name="CrS-ACCP:Cryo-TT-91220:HIHI">
<description> TI-91220 winding temperature U: Limit HH </description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>Check operating data..\nContact Aerzen support</details>
</guidance>
</pv>
<pv name="CrS-ACCP:Cryo-TT-91220:Qbad">
<description> TI-91220 winding temperature U: QBAD </description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>Check operating data..\nContact Aerzen support</details>
</guidance>
</pv>
<pv name="CrS-ACCP:Cryo-TT-91222:HI">
<description> TI-91222 winding temperature V: Limit H </description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>Check operating data..\nContact Aerzen support</details>
</guidance>
</pv>
<pv name="CrS-ACCP:Cryo-TT-91222:HIHI">
<description> TI-91222 winding temperature V: Limit HH </description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>Check operating data..\nContact Aerzen support</details>
</guidance>
</pv>
<pv name="CrS-ACCP:Cryo-TT-91222:Qbad">
<description> TI-91222 winding temperature V: QBAD </description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>Check operating data..\nContact Aerzen support</details>
</guidance>
</pv>
<pv name="CrS-ACCP:Cryo-TT-91224:HI">
<description> TI-91224 winding temperature W: Limit H </description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>Check operating data..\nContact Aerzen support</details>
</guidance>
</pv>
<pv name="CrS-ACCP:Cryo-TT-91224:HIHI">
<description> TI-91224 winding temperature W: Limit HH </description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>Check operating data..\nContact Aerzen support</details>
</guidance>
</pv>
<pv name="CrS-ACCP:Cryo-TT-91224:Qbad">
<description> TI-91224 winding temperature W: QBAD </description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>Check operating data..\nContact Aerzen support</details>
</guidance>
</pv>
<pv name="CrS-ACCP:Cryo-TT-91226:HI">
<description> TI-91226 bearing temperature non driven end motor: Limit H </description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>Check operating data..\nContact Aerzen support</details>
</guidance>
</pv>
<pv name="CrS-ACCP:Cryo-TT-91226:HIHI">
<description> TI-91226 bearing temperature non driven end motor: Limit HH </description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>Check operating data..\nContact Aerzen support</details>
</guidance>
</pv>
<pv name="CrS-ACCP:Cryo-TT-91226:Qbad">
<description> TI-91226 bearing temperature non driven end motor: QBAD </description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>Check operating data..\nContact Aerzen support</details>
</guidance>
</pv>
<pv name="CrS-ACCP:Cryo-TT-91228:HI">
<description> TI-91228 bearing temperature driven end motor: Limit H </description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>Check operating data..\nContact Aerzen support</details>
</guidance>
</pv>
<pv name="CrS-ACCP:Cryo-TT-91228:HIHI">
<description> TI-91228 bearing temperature driven end motor: Limit HH </description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>Check operating data..\nContact Aerzen support</details>
</guidance>
</pv>
<pv name="CrS-ACCP:Cryo-TT-91228:Qbad">
<description> TI-91228 bearing temperature driven end motor: QBAD </description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>Check operating data..\nContact Aerzen support</details>
</guidance>
</pv>
<pv name="CrS-ACCP:Cryo-TT-97020:HIHI">
<description> TI-97020 oil temperature return mechanical seal: Limit HH </description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>Check operating data..\nContact Aerzen support</details>
</guidance>
</pv>
<pv name="CrS-ACCP:Cryo-TT-97020:LO">
<description> TI-97020 oil temperature return mechanical seal: Limit L </description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>Check operating data..\nContact Aerzen support</details>
</guidance>
</pv>
<pv name="CrS-ACCP:Cryo-TT-97020:Qbad">
<description> TI-97020 oil temperature return mechanical seal: QBAD </description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>Check operating data..\nContact Aerzen support</details>
</guidance>
</pv>
<pv name="CrS-ACCP:Cryo-TT-97030:HI">
<description> TI-97030 oil temperature oil supply: Limit H </description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>Check operating data..\nContact Aerzen support</details>
</guidance>
</pv>
<pv name="CrS-ACCP:Cryo-TT-97030:HIHI">
<description> TI-97030 oil temperature oil supply: Limit HH </description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>Check operating data..\nContact Aerzen support</details>
</guidance>
</pv>
<pv name="CrS-ACCP:Cryo-TT-97030:Qbad">
<description> TI-97030 oil temperature oil supply: QBAD </description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>Check operating data..\nContact Aerzen support</details>
</guidance>
</pv>
<pv name="CrS-ACCP:Cryo-TT-97036:Qbad">
<description> TI-97036 oil temperature outlet oil cooler: QBAD </description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>Check operating data..\nContact Aerzen support</details>
</guidance>
</pv>
<pv name="CrS-ACCP:Cryo-TT-97040:LO">
<description> TI-97040 oil temperature oil vessel: Limit L </description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>1. Check oil cooler output and adjust if necessary. 2. Replace oil pressure regulating valve.</details>
</guidance>
</pv>
<pv name="CrS-ACCP:Cryo-TT-97040:Qbad">
<description> TI-97040 oil temperature oil vessel: QBAD </description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>1. Check oil cooler output and adjust if necessary. 2. Replace oil pressure regulating valve.</details>
</guidance>
</pv>
<pv name="CrS-ACCP:Cryo-TT-97044:Qbad">
<description> TI-97044 oil temperature downstream oil pump: QBAD </description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>Check operating data..\nContact Aerzen support</details>
</guidance>
</pv>
<pv name="CrS-ACCP:Cryo-TT-98020:Qbad">
<description> TI-98020 cooling water temperature return gas cooler: QBAD </description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>Check operating data..\nContact Aerzen support</details>
</guidance>
</pv>
<pv name="CrS-ACCP:Cryo-TT-98022:Qbad">
<description> TI-98022 cooling water temperature return oil cooler: QBAD </description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>Check operating data..\nContact Aerzen support</details>
</guidance>
</pv>
<pv name="CrS-ACCP:Cryo-TT-98045:Qbad">
<description> TI-98045 cooling water temperature return motor: QBAD </description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>Check operating data..\nContact Aerzen support</details>
</guidance>
</pv>
<pv name="CrS-ACCP:Cryo-VMT-91200:HI">
<description> VMI-91200 compressor housing vibration FR DS 45ー: Limit H </description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>Check operating data.\nCheck the oil drainage; ensure unobstructed backflow.\nContact Aerzen support</details>
</guidance>
</pv>
<pv name="CrS-ACCP:Cryo-VMT-91200:HIHI">
<description> VMI-91200 compressor housing vibration FR DS 45ー: Limit HH </description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>Check operating data.\nCheck the oil drainage; ensure unobstructed backflow.\nContact Aerzen support</details>
</guidance>
</pv>
<pv name="CrS-ACCP:Cryo-VMT-91200:Qbad">
<description> VMI-91200 compressor housing vibration FR DS 45ー: QBAD </description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>Check operating data.\nCheck the oil drainage; ensure unobstructed backflow.\nContact Aerzen support</details>
</guidance>
</pv>
<pv name="CrS-ACCP:Cryo-VMT-91201:HI">
<description> VMI-91201 compressor housing vibration FR SS 45ー: Limit H </description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>Check operating data.\nCheck the oil drainage; ensure unobstructed backflow.\nContact Aerzen support</details>
</guidance>
</pv>
<pv name="CrS-ACCP:Cryo-VMT-91201:HIHI">
<description> VMI-91201 compressor housing vibration FR SS 45ー: Limit HH </description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>Check operating data.\nCheck the oil drainage; ensure unobstructed backflow.\nContact Aerzen support</details>
</guidance>
</pv>
<pv name="CrS-ACCP:Cryo-VMT-91201:Qbad">
<description> VMI-91201 compressor housing vibration FR DS 45ー: QBAD </description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>Check operating data.\nCheck the oil drainage; ensure unobstructed backflow.\nContact Aerzen support</details>
</guidance>
</pv>
</component>
</component>
<component name="PLC Communication">
<pv name="CrS-ACCP:SC-FSM-300:CommError">
......
This diff is collapsed.
......@@ -40203,6 +40203,15 @@
<details>Inform shift leader and contact MPS team.</details>
</guidance>
</pv>
<pv name="DTL-010Row:CnPw-U-005:FBISCrateStatus">
<description>Diagnostics surge protection FBIS crate Not Ok</description>
<latching>true</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Operator Action]</title>
<details>Inform shift leader and contact MPS team.</details>
</guidance>
</pv>
</component>
<component name="U09">
<pv name="MPSoS-PwrSup:Ctrl-PLC-09:Heartbeat_Stat">
......@@ -40861,7 +40870,7 @@
<details>Inform shift leader and contact MPS team.</details>
</guidance>
</pv>
<pv name="MPSoS:CnPw-U-001:MPSTrg-Temperature-RB">
<pv name="MPSoS:CnPw-U-001:MPSTrg-TempRB">
<description>Temperature Limit value reached for rack</description>
<latching>true</latching>
<annunciating>true</annunciating>
......@@ -40899,7 +40908,7 @@
<details>Inform shift leader and contact MPS team.</details>
</guidance>
</pv>
<pv name="MPSoS:CnPw-U-002:MPSTrg-Temperature-RB">
<pv name="MPSoS:CnPw-U-002:MPSTrg-TempRB">
<description>Temperature Limit value reached for rack</description>
<latching>true</latching>
<annunciating>true</annunciating>
......@@ -40937,7 +40946,7 @@
<details>Inform shift leader and contact MPS team.</details>
</guidance>
</pv>
<pv name="MPSoS:CnPw-U-003:MPSTrg-Temperature-RB">
<pv name="MPSoS:CnPw-U-003:MPSTrg-TempRB">
<description>Temperature Limit value reached for rack</description>
<latching>true</latching>
<annunciating>true</annunciating>
......@@ -40975,7 +40984,7 @@
<details>Inform shift leader and contact MPS team.</details>
</guidance>
</pv>
<pv name="MPSoS:CnPw-U-004:MPSTrg-Temperature-RB">
<pv name="MPSoS:CnPw-U-004:MPSTrg-TempRB">
<description>Temperature Limit value reached for rack</description>
<latching>true</latching>
<annunciating>true</annunciating>
This diff is collapsed.
This diff is collapsed.
This diff is collapsed.
......@@ -672,44 +672,6 @@
</guidance>
</pv>
</component>
<component name="HBL-030Row">
<pv name="HBL-030Row:WtrC-SmD-001:On">
<description>Smoke detector state 1 HBL-030Row</description>
<latching>true</latching>
<annunciating>true</annunciating>
<guidance>
<title>Guidance in case of alarm</title>
<details>Contact facility management</details>
</guidance>
</pv>
<pv name="HBL-030Row:WtrC-TT-001:Temp">
<description>Temperature sensor reading 1 HBL-030Row</description>
<latching>true</latching>
<annunciating>true</annunciating>
<guidance>
<title>Guidance in case of alarm</title>
<details>Contact facility management</details>
</guidance>
</pv>
<pv name="HBL-030Row:WtrC-SmD-002:On">
<description>Smoke detector state 2 HBL-030Row</description>
<latching>true</latching>
<annunciating>true</annunciating>
<guidance>
<title>Guidance in case of alarm</title>
<details>Contact facility management</details>
</guidance>
</pv>
<pv name="HBL-030Row:WtrC-TT-002:Temp">
<description>Temperature sensor reading 2 HBL-030Row</description>
<latching>true</latching>
<annunciating>true</annunciating>
<guidance>
<title>Guidance in case of alarm</title>
<details>Contact facility management</details>
</guidance>
</pv>
</component>
<component name="HBL-050Row">
<pv name="HBL-050Row:WtrC-SmD-001:On">
<description>Smoke detector state 1 HBL-050Row</description>
......
......@@ -1260,6 +1260,7 @@
<latching>false</latching>
<annunciating>false</annunciating>
</pv>
<!--
<pv name="ConVen-H09:HVAC-Ahu-100:Fault">
<description>HVAC alarm ConVen-H09:HVAC-Ahu-100:Fault</description>
<latching>false</latching>
......@@ -1310,5 +1311,6 @@
<latching>false</latching>
<annunciating>false</annunciating>
</pv>
-->
</component>
</config>
This diff is collapsed.
This diff is collapsed.
This diff is collapsed.
This diff is collapsed.
......@@ -22,7 +22,6 @@
</pv>
<pv name="DTL-020:PBI-FC-001:WtrFlowOK">
<description>Water flow interlock for the DTL2 FC (disabled during DTL4 commissioning)</description>
<enabled>false</enabled>
<latching>true</latching>
<annunciating>true</annunciating>
<guidance>
......@@ -70,7 +69,6 @@
</pv>
<pv name="DTL-020:PBI-FC-001:BodyTempOK">
<description>Water temperature on the DTL2 FC (disabled during DTL4 commissioning)</description>
<enabled>false</enabled>
<latching>true</latching>
<annunciating>true</annunciating>
<guidance>
......@@ -107,7 +105,6 @@
</pv>
<pv name="DTL-020:PBI-FC-001:LimSwPressedCount">
<description>Motion timer for the DTL2 FC (disabled during DTL4 commissioning)</description>
<enabled>false</enabled>
<latching>true</latching>
<guidance>
<title>DTL2 FC probably stuck</title>
......@@ -116,7 +113,6 @@
</pv>
<pv name="DTL-040:PBI-FC-001:LimSwPressedCount">
<description>Motion timer for the DTL4 FC (disabled during DTL4 commissioning)</description>
<enabled>false</enabled>
<latching>true</latching>
<guidance>
<title>DTL4 FC probably stuck</title>
......@@ -163,7 +159,6 @@
</pv>
<pv name="DTL-020:PBI-FC-001:Voltage-R">
<description>Voltage readback for the DTL2 FC (disabled during DTL4 commissioning)</description>
<enabled>false</enabled>
<latching>true</latching>
<annunciating>true</annunciating>
<guidance>
......@@ -173,7 +168,6 @@
</pv>
<pv name="DTL-020:PBI-FC-001:HVCurrent-R">
<description>Current readback for the DTL2 FC (disabled during DTL4 commissioning)</description>
<enabled>false</enabled>
<latching>true</latching>
<annunciating>true</annunciating>
<guidance>
......@@ -181,26 +175,6 @@
<details>Disable the repeller bias in the FC ME OPI. In the 'repeller bias' section, set the high voltage = 0 and the current limit = 0 ASAP</details>
</guidance>
</pv>
<pv name="DTL-040:PBI-FC-001:Voltage-R">
<description>Voltage readback for the DTL4 FC (placeholder - disabled)</description>
<enabled>false</enabled>
<latching>true</latching>
<annunciating>true</annunciating>
<guidance>
<title>Overvoltage on the DTL4 FC</title>
<details>Disable the repeller bias in the FC ME OPI. In the 'repeller bias' section, set the high voltage = 0 and the current limit = 0 ASAP</details>
</guidance>
</pv>
<pv name="DTL-040:PBI-FC-001:HVCurrent-R">
<description>Current readback for the DTL4 FC (placeholder - disabled)</description>
<enabled>false</enabled>
<latching>true</latching>
<annunciating>true</annunciating>
<guidance>
<title>Overcurrent on the DTL4 FC</title>
<details>Disable the repeller bias in the FC ME OPI. In the 'repeller bias' section, set the high voltage = 0 and the current limit = 0 ASAP</details>
</guidance>
</pv>
</component>
</component>
</config>
<?xml version="1.0" encoding="UTF-8" standalone="yes"?>
<config name="PBI">
<component name="PBI-IBS">
<component name="Water cooling">
<pv name="PBI-IBS01:Ctrl-ECAT-100:WaterFlowOk">
<description>Water flow interlock for the SPK IBS</description>
<latching>true</latching>
<annunciating>true</annunciating>
<guidance>
<title>Water flow interlock for the SPK IBS is NOT OK</title>
<details>Visually inspect the SPK IBS pipes for water supply and the overall skid status, contact RP if there is a water leak</details>
</guidance>
</pv>
<pv name="PBI-IBS02:Ctrl-ECAT-100:WaterFlowOk">
<description>Water flow interlock for the MBL IBS</description>
<enabled>false</enabled>
<latching>true</latching>
<annunciating>true</annunciating>
<guidance>
<title>Water flow interlock for the MBL IBS is NOT OK</title>
<details>Visually inspect the MBL IBS pipes for water supply and the overall skid status, contact RP if there is a water leak</details>
</guidance>
</pv>
</component>
<component name="Water temperature">
<pv name="PBI-IBS01:Ctrl-ECAT-100:WaterTempOk">
<description>Water temperature on the SPK IBS</description>
<latching>true</latching>
<annunciating>true</annunciating>
<guidance>
<title>Water termperature on the SPK IBS is too high or too low</title>
<details>Visually inspect the SPK IBS pipes for water supply and the overall skid status, contact RP if there is a water leak</details>
</guidance>
</pv>
<pv name="PBI-IBS02:Ctrl-ECAT-100:WaterTempOk">
<description>Water temperature on the SPK IBS</description>
<enabled>false</enabled>
<latching>true</latching>
<annunciating>true</annunciating>
<guidance>
<title>Water termperature on the MBL IBS is too high or too low</title>
<details>Visually inspect the MBL IBS pipes for water supply and the overall skid status, contact RP if there is a water leak</details>
</guidance>
</pv>
</component>
<component name="Motion">
<pv name="PBI-IBS01:Ctrl-ECAT-100:ActuatorTime">
<description>Motion timer for the SPK IBS</description>
<latching>true</latching>
<guidance>
<title>SPK IBS probably stuck</title>
<details>Do NOT try to move it, contact Beam Diagnosis</details>
</guidance>
</pv>
<pv name="PBI-IBS02:Ctrl-ECAT-100:ActuatorTime">
<description>Motion timer for the MBL IBS</description>
<enabled>false</enabled>
<latching>true</latching>
<guidance>
<title>MBL IBS probably stuck</title>
<details>Do NOT try to move it, contact Beam Diagnosis</details>
</guidance>
</pv>
</component>
</component>
</config>
......@@ -160,6 +160,11 @@
<latching>false</latching>
<annunciating>false</annunciating>
</pv>
<pv name="Tgt-MRCS:Ctrl-PLC-001:1054_YSV_001_WearMon">
<description>YSV 001 Valve wear monitoring alarm</description>
<latching>false</latching>
<annunciating>false</annunciating>
</pv>
</component>
<component name="1078">
<pv name="Tgt-Resn1078:Proc-PIT-101:Overrange">
......