ICSHWI-11273: Logic updates to e-pickup
A lot of logic changes were requested by the system owner after using the system in test environments. Full description on the JIRA ticket ICSHWI-11273
Summary of requests for IOC:
- The bus V1 should be changed to monitor 9.5V
- Bus V2 monitors 15V
- Current Consumption measurement to be removed
- Change conversion factors of V1 and V2 to 11 (this is due to the resistor divider in the hardware)
- Rename "Test Monitoring" input indicator to "Fiber Test" and change the logic to display "Testing" when PV == 0
- Add a PV to monitor if the "Interlock = 0" and "Interlock = 1" signals are opposite values, raise alarm if not
- Change the "Interlock Status" PV value to "OK"/"NOK"