...@@ -3861,9 +3861,18 @@ ...@@ -3861,9 +3861,18 @@
<annunciating>true</annunciating> <annunciating>true</annunciating>
<guidance> <guidance>
<title>[Cryo Operator Action]</title> <title>[Cryo Operator Action]</title>
<details>Check operating data..\nContac Aerzen support</details> <details>Check operating data..\nContact Aerzen support</details>
</guidance> </guidance>
</pv> </pv>
<pv name="CrS-ACCP:Cryo-C-91000:EmerStop">
<description>C91000 emergency stop BCP active</description>
<latching>true</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>Check operating data..\nContact Aerzen support</details>
</guidance>
</pv>
<pv name="CrS-ACCP:Cryo-PT-91004:Sta"> <pv name="CrS-ACCP:Cryo-PT-91004:Sta">
<description>BCP compressor discharge pressure high</description> <description>BCP compressor discharge pressure high</description>
<latching>true</latching> <latching>true</latching>
...@@ -3873,7 +3882,18 @@ ...@@ -3873,7 +3882,18 @@
<details>Check operating data.\nCheck the position of the output control gate; correct if necessary.</details> <details>Check operating data.\nCheck the position of the output control gate; correct if necessary.</details>
</guidance> </guidance>
</pv> </pv>
</component> </component>
<component name="BCP-Instrument-Air">
<pv name="CrS-ACCP:Cryo-PT-98005:Sta">
<description>BCP instrument air pressure low</description>
<latching>true</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>1. Check operating data.2. Contact Instrument Air supply.</details>
</guidance>
</pv>
</component>
<component name="BCP-Discharge-temperature"> <component name="BCP-Discharge-temperature">
<pv name="CrS-ACCP:Cryo-TT-91202:Sta"> <pv name="CrS-ACCP:Cryo-TT-91202:Sta">
<description>BCP discharge temperature high</description> <description>BCP discharge temperature high</description>
......