<config name="ORW">
<component name="ORW">
<pv name="CWS-D02:WtrC-LIT-202:LevelTotal">
<description>High level in D02 waste water tanks</description>
<latching>true</latching>
<annunciating>true</annunciating>
<guidance>
<title>High level in waste water tanks</title>
<details>Check fill rate of tanks and evaluate if present fill rate can be sustained without flooding the tanks.
Send guard to lab area in D02. Search all rooms for leaks or running taps. These can be found on level 095, 100, 110 and 120
See also: FLOW CHART, WASTE WATER ESS-3863535
</details>
</guidance>
</pv>
<pv name="CWS-D02:WtrC-LIT-202:LevelChange">
<description>High filling rate in D02 waste water tanks</description>
<latching>true</latching>
<annunciating>true</annunciating>
<guidance>
<title>High filling rate in waste water tanks</title>
<details>Check fill rate of tanks and evaluate if present fill rate can be sustained without flooding the tanks.
Send guard to lab area in D02. Search all rooms for leaks or running taps. These can be found on level 095, 100, 110 and 120
See also: FLOW CHART, WASTE WATER ESS-3863535
</details>
</guidance>
</pv>
<pv name="CWS-D02:WtrC-LIT-205:LevelChange">
<description>High filling rate in D02 waste water tanks</description>
<latching>true</latching>
<annunciating>true</annunciating>
<guidance>
<title>High filling rate in waste water tanks</title>
<details>Check fill rate of tanks and evaluate if present fill rate can be sustained without flooding the tanks.
Send guard to lab area in D02. Search all rooms for leaks or running taps. These can be found on level 095, 100, 110 and 120
See also: FLOW CHART, WASTE WATER ESS-3863535
</details>
</guidance>
</pv>
<pv name="CWS-D02:WtrC-LSH-201:Closed">
<description>Tank in D02 basement full, flooding ongoing</description>
<latching>true</latching>
<annunciating>true</annunciating>
<guidance>
<title>Tank in D02 basement full, flooding ongoing</title>
<details>Send guard to lab area in D02. Search all rooms for leaks or running taps. These can be found on level 095, 100, 110 and 120.
If flooding can’t be prevented, call IOM mechanical on-call 046-8882002.
See also: FLOW CHART, WASTE WATER ESS-3863535
</details>
</guidance>
</pv>
<pv name="CWS-D02:WtrC-LSH-204:Closed">
<description>Tank in D02 basement full, flooding ongoing</description>
<latching>true</latching>
<annunciating>true</annunciating>
<guidance>
<title>Tank in D02 basement full, flooding ongoing</title>
<details>Send guard to lab area in D02. Search all rooms for leaks or running taps. These can be found on level 095, 100, 110 and 120.
If flooding can’t be prevented, call IOM mechanical on-call 046-8882002.
See also: FLOW CHART, WASTE WATER ESS-3863535
</details>
</guidance>
</pv>
<pv name="CWS-D02:WtrC-GQ-002:NOK">
<description>Tank in D02 basement full, flooding ongoing</description>
<latching>true</latching>
<annunciating>true</annunciating>
<guidance>
<title>Tank in D02 basement full, flooding ongoing</title>
<details>Send guard to lab area in D02. Search all rooms for leaks or running taps. These can be found on level 095, 100, 110 and 120.
If flooding can’t be prevented, call IOM mechanical on-call 046-8882002.
See also: FLOW CHART, WASTE WATER ESS-3863535
</details>
</guidance>
</pv>
<pv name="CWS-D04:WtrC-LIT-402:LevelTotal">
<description>High level in D04 waste water tanks</description>
<latching>true</latching>
<annunciating>true</annunciating>
<guidance>
<title>High level in waste water tanks</title>
<details>Check fill rate of tanks and evaluate if present fill rate can be sustained without flooding the tanks.
Send guard to lab area in D04. Search all rooms for leaks or running taps. These can be found on level 100, 110 and also the HVAC room and in D02.140.4015, D02.150.1014 and D02.150.4015 as well as the sink in D03
See also: FLOW CHART, WASTE WATER ESS-3723201
</details>
</guidance>
</pv>
<pv name="CWS-D04:WtrC-LIT-402:LevelChange">
<description>High filling rate in D04 waste water tanks</description>
<latching>true</latching>
<annunciating>true</annunciating>
<guidance>
<title>High filling rate in waste water tanks</title>
<details>Check fill rate of tanks and evaluate if present fill rate can be sustained without flooding the tanks.
Send guard to lab area in D04. Search all rooms for leaks or running taps. These can be found on level 100, 110 and also the HVAC room and in D02.140.4015, D02.150.1014 and D02.150.4015 as well as the sink in D03
See also: FLOW CHART, WASTE WATER ESS-3723201
</details>
</guidance>
</pv>
<pv name="CWS-D04:WtrC-LIT-405:LevelChange">
<description>High filling rate in D04 waste water tanks</description>
<latching>true</latching>
<annunciating>true</annunciating>
<guidance>
<title>High filling rate in waste water tanks</title>
<details>Check fill rate of tanks and evaluate if present fill rate can be sustained without flooding the tanks.
Send guard to lab area in D04. Search all rooms for leaks or running taps. These can be found on level 100, 110 and also the HVAC room and in D02.140.4015, D02.150.1014 and D02.150.4015 as well as the sink in D03
See also: FLOW CHART, WASTE WATER ESS-3723201
</details>
</guidance>
</pv>
<pv name="CWS-D04:WtrC-LSH-401:Closed">
<description>Tank in D04 basement full, flooding ongoing</description>
<latching>true</latching>
<annunciating>true</annunciating>
<guidance>
<title>Tank in D04 basement full, flooding ongoing</title>
<details>Send guard to lab area in D04. Search all rooms for leaks or running taps. These can be found on level 100, 110 and also the HVAC room and in D02.140.4015, D02.150.1014 and D02.150.4015 as well as the sink in D03
If flooding can’t be prevented, call IOM mechanical on-call 046-8882002.
See also: FLOW CHART, WASTE WATER ESS-3723201
</details>
</guidance>
</pv>
<pv name="CWS-D04:WtrC-LSH-404:Closed">
<description>Tank in D04 basement full, flooding ongoing</description>
<latching>true</latching>
<annunciating>true</annunciating>
<guidance>
<title>Tank in D04 basement full, flooding ongoing</title>
<details>Send guard to lab area in D04. Search all rooms for leaks or running taps. These can be found on level 100, 110 and also the HVAC room and in D02.140.4015, D02.150.1014 and D02.150.4015 as well as the sink in D03
If flooding can’t be prevented, call IOM mechanical on-call 046-8882002.
See also: FLOW CHART, WASTE WATER ESS-3723201
</details>
</guidance>
</pv>
<pv name="CWS-D04:WtrC-GQ-002:NOK">
<description>Tank in D04 basement full, flooding ongoing</description>
<latching>true</latching>
<annunciating>true</annunciating>
<guidance>
<title>Tank in D04 basement full, flooding ongoing</title>
<details>Send guard to lab area in D04. Search all rooms for leaks or running taps. These can be found on level 100, 110 and also the HVAC room and in D02.140.4015, D02.150.1014 and D02.150.4015 as well as the sink in D03
If flooding can’t be prevented, call IOM mechanical on-call 046-8882002.
See also: FLOW CHART, WASTE WATER ESS-3723201
</details>
</guidance>
</pv>
<pv name="CWS-D07:WtrC-LIT-702:Level">
<description>High level in D07 waste water tanks</description>
<latching>true</latching>
<annunciating>true</annunciating>
<guidance>
<title>High level in waste water tanks</title>
<details>Check fill rate of tanks and evaluate if present fill rate can be sustained without flooding the tanks.
Send guard to lab area in D01. Search all rooms for leaks or running taps. These can be found on level 100 in D01.5001
See also: FLOW CHART, WASTE WATER ESS-3476152
</details>
</guidance>
</pv>
<pv name="CWS-D07:WtrC-LIT-702:LevelChange">
<description>High filling rate in D07 waste water tanks</description>
<latching>true</latching>
<annunciating>true</annunciating>
<guidance>
<title>High filling rate in waste water tanks</title>
<details>Check fill rate of tanks and evaluate if present fill rate can be sustained without flooding the tanks.
Send guard to lab area in D01. Search all rooms for leaks or running taps. These can be found on level 100 in D01.5001
See also: FLOW CHART, WASTE WATER ESS-3476152
</details>
</guidance>
</pv>
<pv name="CWS-D07:WtrC-LSH-701:Closed">
<description>Tank in D07 basement full, flooding ongoing</description>
<latching>true</latching>
<annunciating>true</annunciating>
<guidance>
<title>Tank in D07 basement full, flooding ongoing</title>
<details>Send guard to lab area in D01. Search all rooms for leaks or running taps. These can be found on level 100 in D01.5001
If flooding can’t be prevented, call IOM mechanical on-call 046-8882002.
See also: FLOW CHART, WASTE WATER ESS-3476152
</details>
</guidance>
</pv>
<pv name="CWS-D07:WtrC-GQ-002:NOK">
<description>Tank in D07 basement full, flooding ongoing</description>
<latching>true</latching>
<annunciating>true</annunciating>
<guidance>
<title>Tank in D07 basement full, flooding ongoing</title>
<details>Send guard to lab area in D01. Search all rooms for leaks or running taps. These can be found on level 100 in D01.5001
If flooding can’t be prevented, call IOM mechanical on-call 046-8882002.
See also: FLOW CHART, WASTE WATER ESS-3476152
</details>
</guidance>
</pv>
<pv name="CWS-D08:WtrC-LIT-802:LevelTotal">
<description>High level in D08 waste water tanks</description>
<latching>true</latching>
<annunciating>true</annunciating>
<guidance>
<title>High level in waste water tanks</title>
<details>Check fill rate of tanks and evaluate if present fill rate can be sustained without flooding the tanks.
Send guard to lab area in D08. Search all rooms for leaks or running taps. These can be found on level 100, 110, 120 and the HVAC room
See also: FLOW CHART, WASTE WATER ESS-3778471
</details>
</guidance>
</pv>
<pv name="CWS-D08:WtrC-LIT-802:LevelChange">
<description>High filling rate in D08 waste water tanks</description>
<latching>true</latching>
<annunciating>true</annunciating>
<guidance>
<title>High filling rate in waste water tanks</title>
<details>Check fill rate of tanks and evaluate if present fill rate can be sustained without flooding the tanks.
Send guard to lab area in D08. Search all rooms for leaks or running taps. These can be found on level 100, 110, 120 and the HVAC room
See also: FLOW CHART, WASTE WATER ESS-3778471
</details>
</guidance>
</pv>
<pv name="CWS-D08:WtrC-LIT-805:LevelChange">
<description>High filling rate in D08 waste water tanks</description>
<latching>true</latching>
<annunciating>true</annunciating>
<guidance>
<title>High filling rate in waste water tanks</title>
<details>Check fill rate of tanks and evaluate if present fill rate can be sustained without flooding the tanks.
Send guard to lab area in D08. Search all rooms for leaks or running taps. These can be found on level 100, 110, 120 and the HVAC room
See also: FLOW CHART, WASTE WATER ESS-3778471
</details>
</guidance>
</pv>
<pv name="CWS-D08:WtrC-LIT-808:Level">
<description>High level in D08 waste water tanks</description>
<latching>true</latching>
<annunciating>true</annunciating>
<guidance>
<title>High level in waste water tanks</title>
<details>Check fill rate of tanks and evaluate if present fill rate can be sustained without flooding the tanks.
Send guard to lab area in D08. Search all rooms for leaks or running taps. These can be found on level 100, 110, 120 and the HVAC room
See also: FLOW CHART, WASTE WATER ESS-3778471
</details>
</guidance>
</pv>
<pv name="CWS-D08:WtrC-LIT-808:LevelChange">
<description>High filling rate in D08 waste water tanks</description>
<latching>true</latching>
<annunciating>true</annunciating>
<guidance>
<title>High filling rate in waste water tanks</title>
<details>Check fill rate of tanks and evaluate if present fill rate can be sustained without flooding the tanks.
Send guard to lab area in D08. Search all rooms for leaks or running taps. These can be found on level 100, 110, 120 and the HVAC room
See also: FLOW CHART, WASTE WATER ESS-3778471
</details>
</guidance>
</pv>
<pv name="CWS-D08:WtrC-LSH-801:Closed">
<description>Tank in D08 basement full, flooding ongoing</description>
<latching>true</latching>
<annunciating>true</annunciating>
<guidance>
<title>Tank in D08 basement full, flooding ongoing</title>
<details>Send guard to lab area in D08. Search all rooms for leaks or running taps. These can be found on level 100, 110, 120 and the HVAC room
If flooding can’t be prevented, call IOM mechanical on-call 046-8882002.
See also: FLOW CHART, WASTE WATER ESS-3778471
</details>
</guidance>
</pv>
<pv name="CWS-D08:WtrC-LSH-804:Closed">
<description>Tank in D08 basement full, flooding ongoing</description>
<latching>true</latching>
<annunciating>true</annunciating>
<guidance>
<title>Tank in D08 basement full, flooding ongoing</title>
<details>Send guard to lab area in D08. Search all rooms for leaks or running taps. These can be found on level 100, 110, 120 and the HVAC room
If flooding can’t be prevented, call IOM mechanical on-call 046-8882002.
See also: FLOW CHART, WASTE WATER ESS-3778471
</details>
</guidance>
</pv>
<pv name="CWS-D08:WtrC-GQ-002:NOK">
<description>Tank in D08 basement full, flooding ongoing</description>
<latching>true</latching>
<annunciating>true</annunciating>
<guidance>
<title>Tank in D08 basement full, flooding ongoing</title>
<details>Send guard to lab area in D08. Search all rooms for leaks or running taps. These can be found on level 100, 110, 120 and the HVAC room
If flooding can’t be prevented, call IOM mechanical on-call 046-8882002.
See also: FLOW CHART, WASTE WATER ESS-3778471
</details>
</guidance>
</pv>
<pv name="CWS-E03:WtrC-LIT-302:LevelTotal">
<description>High level in E03 waste water tanks</description>
<latching>true</latching>
<annunciating>true</annunciating>
<guidance>
<title>High level in waste water tanks</title>
<details>Check fill rate of tanks and evaluate if present fill rate can be sustained without flooding the tanks.
Send guard to lab area in E03. Search all rooms for leaks or running taps. These can be found on level 100, 110 and the HVAC room
See also: FLOW CHART, WASTE WATER ESS-1680626
</details>
</guidance>
</pv>
<pv name="CWS-E03:WtrC-LIT-302:LevelChange">
<description>High filling rate in E03 waste water tanks</description>
<latching>true</latching>
<annunciating>true</annunciating>
<guidance>
<title>High filling rate in waste water tanks</title>
<details>Check fill rate of tanks and evaluate if present fill rate can be sustained without flooding the tanks.
Send guard to lab area in E03. Search all rooms for leaks or running taps. These can be found on level 100, 110 and the HVAC room
See also: FLOW CHART, WASTE WATER ESS-1680626
</details>
</guidance>
</pv>
<pv name="CWS-E03:WtrC-LIT-305:LevelChange">
<description>High filling rate in E03 waste water tanks</description>
<latching>true</latching>
<annunciating>true</annunciating>
<guidance>
<title>High filling rate in waste water tanks</title>
<details>Check fill rate of tanks and evaluate if present fill rate can be sustained without flooding the tanks.
Send guard to lab area in E03. Search all rooms for leaks or running taps. These can be found on level 100, 110 and the HVAC room
See also: FLOW CHART, WASTE WATER ESS-1680626
</details>
</guidance>
</pv>
<pv name="CWS-E03:WtrC-LSH-301:Closed">
<description>Tank in E03 basement full, flooding ongoing</description>
<latching>true</latching>
<annunciating>true</annunciating>
<guidance>
<title>Tank in E03 basement full, flooding ongoing</title>
<details>Send guard to lab area in E03. Search all rooms for leaks or running taps. These can be found on level 100, 110 and the HVAC room
If flooding can’t be prevented, call IOM mechanical on-call 046-8882002.
See also: FLOW CHART, WASTE WATER ESS-1680626
</details>
</guidance>
</pv>
<pv name="CWS-E03:WtrC-LSH-304:Closed">
<description>Tank in E03 basement full, flooding ongoing</description>
<latching>true</latching>
<annunciating>true</annunciating>
<guidance>
<title>Tank in E03 basement full, flooding ongoing</title>
<details>Send guard to lab area in E03. Search all rooms for leaks or running taps. These can be found on level 100, 110 and the HVAC room
If flooding can’t be prevented, call IOM mechanical on-call 046-8882002.
See also: FLOW CHART, WASTE WATER ESS-1680626
</details>
</guidance>
</pv>
<pv name="CWS-E03:WtrC-GQ-002:NOK">
<description>Tank in E03 basement full, flooding ongoing</description>
<latching>true</latching>
<annunciating>true</annunciating>
<guidance>
<title>Tank in E03 basement full, flooding ongoing</title>
<details>Send guard to lab area in E03. Search all rooms for leaks or running taps. These can be found on level 100, 110 and the HVAC room
If flooding can’t be prevented, call IOM mechanical on-call 046-8882002.
See also: FLOW CHART, WASTE WATER ESS-1680626
</details>
</guidance>
</pv>
<pv name="CWS-E04:WtrC-LIT-402:LevelTotal">
<description>High level in E04 waste water tanks</description>
<latching>true</latching>
<annunciating>true</annunciating>
<guidance>
<title>High level in waste water tanks</title>
<details>Check fill rate of tanks and evaluate if present fill rate can be sustained without flooding the tanks.
Send guard to lab area in E04. Search all rooms for leaks or running taps. These can be found on level 100, 110 120 and the HVAC roomas well as the sink in E01
See also: FLOW CHART, WASTE WATER ESS-1716802
</details>
</guidance>
</pv>
<pv name="CWS-E04:WtrC-LIT-402:LevelChange">
<description>High filling rate in E04 waste water tanks</description>
<latching>true</latching>
<annunciating>true</annunciating>
<guidance>
<title>High filling rate in waste water tanks</title>
<details>Check fill rate of tanks and evaluate if present fill rate can be sustained without flooding the tanks.
Send guard to lab area in E04. Search all rooms for leaks or running taps. These can be found on level 100, 110 120 and the HVAC roomas well as the sink in E01
See also: FLOW CHART, WASTE WATER ESS-1716802
</details>
</guidance>
</pv>
<pv name="CWS-E04:WtrC-LIT-405:LevelChange">
<description>High filling rate in E04 waste water tanks</description>
<latching>true</latching>
<annunciating>true</annunciating>
<guidance>
<title>High filling rate in waste water tanks</title>
<details>Check fill rate of tanks and evaluate if present fill rate can be sustained without flooding the tanks.
Send guard to lab area in E04. Search all rooms for leaks or running taps. These can be found on level 100, 110 120 and the HVAC roomas well as the sink in E01
See also: FLOW CHART, WASTE WATER ESS-1716802
</details>
</guidance>
</pv>
<pv name="CWS-E04:WtrC-LSH-401:Closed">
<description>Tank in E04 basement full, flooding ongoing</description>
<latching>true</latching>
<annunciating>true</annunciating>
<guidance>
<title>Tank in E04 basement full, flooding ongoing</title>
<details>Send guard to lab area in E04. Search all rooms for leaks or running taps. These can be found on level 100, 110 120 and the HVAC roomas well as the sink in E01
If flooding can’t be prevented, call IOM mechanical on-call 046-8882002.
See also: FLOW CHART, WASTE WATER ESS-1716802
</details>
</guidance>
</pv>
<pv name="CWS-E04:WtrC-LSH-404:Closed">
<description>Tank in E04 basement full, flooding ongoing</description>
<latching>true</latching>
<annunciating>true</annunciating>
<guidance>
<title>Tank in E04 basement full, flooding ongoing</title>
<details>Send guard to lab area in E04. Search all rooms for leaks or running taps. These can be found on level 100, 110 120 and the HVAC roomas well as the sink in E01
If flooding can’t be prevented, call IOM mechanical on-call 046-8882002.
See also: FLOW CHART, WASTE WATER ESS-1716802
</details>
</guidance>
</pv>
<pv name="CWS-E04:WtrC-GQ-002:NOK">
<description>Tank in E04 basement full, flooding ongoing</description>
<latching>true</latching>
<annunciating>true</annunciating>
<guidance>
<title>Tank in E04 basement full, flooding ongoing</title>
<details>Send guard to lab area in E04. Search all rooms for leaks or running taps. These can be found on level 100, 110 120 and the HVAC roomas well as the sink in E01
If flooding can’t be prevented, call IOM mechanical on-call 046-8882002.
See also: FLOW CHART, WASTE WATER ESS-1716802
</details>
</guidance>
</pv>
</component>
</config>