Forked from
Alarm Server / alarm-server-config
156 commits behind the upstream repository.
-
Antoni Simelio authoredAntoni Simelio authored
Code owners
Assign users and groups as approvers for specific file changes. Learn more.
LCR.xml 338.37 KiB
<?xml version="1.0" encoding="UTF-8" standalone="yes"?>
<config name="LCR">
<component name="ACCP">
<component name="ACCP Adsorber">
<pv name="CrS-ACCP:CRYO-A-31450:Sd">
<description>ACCP - 20K Adsorber general shutdown</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Operator Action]</title>
<details>Call Cryo on-call +46 46 888 31 66 Tell them that the ACCP 20K adsorber tripped.</details>
</guidance>
</pv>
</component>
<component name="ACCP Turbines">
<pv name="CrS-ACCP:CRYO-TStr-311x0:SdErrT31130">
<description>ACCP - (T-31130) Turbine 1 shutddown</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Operator Action]</title>
<details>Call Cryo on-call +46 46 888 31 66 Tell them that the ACCP Turbine 1 tripped</details>
</guidance>
</pv>
<pv name="CrS-ACCP:CRYO-TStr-311x0:SdErrT31150">
<description>ACCP - (T-31150) Turbine 2 Shutdown</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Operator Action]</title>
<details>Call Cryo on-call +46 46 888 31 66 Tell them that the ACCP Turbine 2 tripped</details>
</guidance>
</pv>
<pv name="CrS-ACCP:CRYO-TStr-313x0:SdErrT31330">
<description>ACCP - (T-31330) Turbine 3 Shutdown</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Operator Action]</title>
<details>Call Cryo on-call +46 46 888 31 66 Tell them that the ACCP turbine 3 tripped</details>
</guidance>
</pv>
<pv name="CrS-ACCP:CRYO-TStr-315x0:SdErrT31530">
<description>ACCP - (T-31530) Turbine 4 Shutdown</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Operator Action]</title>
<details>Call Cryo on-call +46 46 888 31 66 Tell them that the ACCP turbine 4 tripped</details>
</guidance>
</pv>
<pv name="CrS-ACCP:CRYO-TStr-315x0:SdErrT31550">
<description>ACCP - (T-31550) Turbine 5 Shutdown</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Operator Action]</title>
<details>Call Cryo on-call +46 46 888 31 66 Tell them that the ACCP turbine 5 tripped</details>
</guidance>
</pv>
<pv name="CrS-ACCP:CRYO-TStr-317x0:SdErrT31730">
<description>ACCP - (T-31730) Turbine 6 Shutdown</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Operator Action]</title>
<details>Call Cryo on-call +46 46 888 31 66 Tell them that the ACCP turbine 6 tripped</details>
</guidance>
</pv>
</component>
<component name="ACCP Cold Compressors">
<pv name="CrS-ACCP:CRYO-CC-34700:SdHard">
<description>ACCP - C-34700 Shutdown hard</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Operator Action]</title>
<details>Call Cryo on-call +46 46 888 31 66 Tell them that the ACCP Cold compressors tripped</details>
</guidance>
</pv>
<pv name="CrS-ACCP:CRYO-CC-34700:SdSoft">
<description>ACCP - C-34700 Shutdown soft</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Operator Action]</title>
<details>Call Cryo on-call +46 46 888 31 66 Tell them that the ACCP Cold compressors tripped</details>
</guidance>
</pv>
<pv name="CrS-ACCP:CRYO-CC-34800:SdHard">
<description>ACCP - C-34800 Shutdown hard</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Operator Action]</title>
<details>Call Cryo on-call +46 46 888 31 66 Tell them that the ACCP Cold compressors tripped</details>
</guidance>
</pv>
<pv name="CrS-ACCP:CRYO-CC-34800:SdSoft">
<description>ACCP - C-34800 Shutdown soft</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Operator Action]</title>
<details>Call Cryo on-call +46 46 888 31 66 Tell them that the ACCP Cold compressors tripped</details>
</guidance>
</pv>
<pv name="CrS-ACCP:CRYO-CC-34900:SdHard">
<description>ACCP - C-34900 Shutdown hard</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Operator Action]</title>
<details>Call Cryo on-call +46 46 888 31 66 Tell them that the ACCP Cold compressors tripped</details>
</guidance>
</pv>
<pv name="CrS-ACCP:CRYO-CC-34900:SdSoft">
<description>ACCP - C-34900 Shutdown soft</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Operator Action]</title>
<details>Call Cryo on-call +46 46 888 31 66 Tell them that the ACCP Cold compressors tripped</details>
</guidance>
</pv>
<pv name="CrS-ACCP:CRYO-CC-34x00:SdGenHard">
<description>ACCP - CC Hard shutdown</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Operator Action]</title>
<details>Call Cryo on-call +46 46 888 31 66 Tell them that the ACCP Cold compressors tripped</details>
</guidance>
</pv>
<pv name="CrS-ACCP:CRYO-CC-34x00:SdGen">
<description>ACCP - CC General shutdown</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Operator Action]</title>
<details>Call Cryo on-call +46 46 888 31 66 Tell them that the ACCP Cold compressors tripped</details>
</guidance>
</pv>
<pv name="CrS-ACCP:CRYO-CC-34x00:SdSurge">
<description>ACCP- CC Max surge oversteps reached.</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Operator Action]</title>
<details>Call Cryo on-call +46 46 888 31 66 Tell them that the ACCP Cold compressors tripped</details>
</guidance>
</pv>
</component>
<component name="ACCP Coldbox and He Guard">
<pv name="CrS-ACCP:CRYO-PT-39001:AHH">
<description>ACCP - Coldbox insulation vacuum too high</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Operator Action]</title>
<details>Call Cryo on-call +46 46 888 31 66 Tell them that ACCP Colbox have lost insulation vacuum.</details>
</guidance>
</pv>
<pv name="CrS-ACCP:CRYO-Cbox:SdEMSTP">
<description>ACCP Coldbox emergency stop</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Operator Action]</title>
<details>Call Cryo on-call +46 46 888 31 66 Tell them that ACCP Colbox have been emergency stoped.</details>
</guidance>
</pv>
<pv name="CrS-ACCP:CRYO-PT-31641:AHH">
<description>ACCP - TS Pressure to high</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Operator Action]</title>
<details>Call Cryo on-call +46 46 888 31 66 Tell them that ACCP Colbox have to high Termal Shield presssure.</details>
</guidance>
</pv>
</component>
<component name="ACCP WCS ORS, GMP and He Guard">
<pv name="CrS-ACCP:CRYO-PT-22601:AH">
<description>ACCP - Buffer tank (aux) pressure high</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Operator Action]</title>
<details>Call Cryo on-call +46 46 888 31 66 Tell them that ACCP buffers have too high pressure</details>
</guidance>
</pv>
<pv name="CrS-ACCP:CRYO-PT-22601:AL">
<description>ACCP - Buffer tank (aux) pressure low</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Operator Action]</title>
<details>Call Cryo on-call +46 46 888 31 66 Tell them that ACCP buffers have too low pressure</details>
</guidance>
</pv>
<pv name="CrS-ACCP:CRYO-PT-22600:AL">
<description>ACCP - Buffer tank (main) pressure low</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Operator Action]</title>
<details>Call Cryo on-call +46 46 888 31 66 Tell them that ACCP buffers have too low pressure</details>
</guidance>
</pv>
<pv name="CrS-ACCP:CRYO-PT-22600:AH">
<description>ACCP - Buffer tank (main) pressure high</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Operator Action]</title>
<details>Call Cryo on-call +46 46 888 31 66 Tell them that ACCP buffers have too high pressure</details>
</guidance>
</pv>
</component>
<component name="ACCP WCS Compressors">
<pv name="CrS-ACCP:CRYO-C-21000:EmStopHPActv">
<description>ACCP - C21000 emergency stop HP active</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Operator Action]</title>
<details>Call Cryo on-call +46 46 888 31 66 Tell them that ACCP HP compressor have been emergency stopped</details>
</guidance>
</pv>
<pv name="CrS-ACCP:CRYO-C-21000:GroupTrp">
<description>ACCP - C21000 Compressor trip</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Operator Action]</title>
<details>Call Cryo on-call +46 46 888 31 66 Tell them that ACCP HP compressor have tripped.</details>
</guidance>
</pv>
<pv name="CrS-ACCP:CRYO-C-21000:ComFail">
<description>ACCP - Trip - Communication fail</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Operator Action]</title>
<details>Call Cryo on-call +46 46 888 31 66 Tell them that ACCP HP Compressor have tripped due to communication loss</details>
</guidance>
</pv>
<pv name="CrS-ACCP:CRYO-C-23000:GroupTrp">
<description>ACCP - C23000 LP Compressor group trip</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Operator Action]</title>
<details>Call Cryo on-call +46 46 888 31 66 Tell them that ACCP LP Compressor have tripped</details>
</guidance>
</pv>
<pv name="CrS-ACCP:CRYO-C-23000:ComFail">
<description>ACCP - Trip - Communication fail</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Operator Action]</title>
<details>Call Cryo on-call +46 46 888 31 66 Tell them that ACCP LP Compressor have tripped</details>
</guidance>
</pv>
<pv name="CrS-ACCP:CRYO-C-24000:GroupTrp">
<description>ACCP - C24000 Compressor group trip SP</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Operator Action]</title>
<details>Call Cryo on-call +46 46 888 31 66 Tell them that ACCP SP Compressor have tripped</details>
</guidance>
</pv>
<pv name="CrS-ACCP:CRYO-C-24000:ComFail">
<description>ACCP - Trip - Communication fail</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Operator Action]</title>
<details>Call Cryo on-call +46 46 888 31 66 Tell them that ACCP SP Compressor have tripped due to communications loss.</details>
</guidance>
</pv>
<pv name="CrS-ACCP:CRYO-C-24000:EmStopActv">
<description>ACCP - Emergency Stop active SP+LP</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Operator Action]</title>
<details>Call Cryo on-call +46 46 888 31 66 Tell them that ACCP SP and LP compresors have been emergency stopped.</details>
</guidance>
</pv>
</component>
</component>
<component name="TICP">
<component name="TICP Coldbox">
<pv name="CrS-TICP:Cryo-Virt-MJFLT1:Major_Fault_013">
<description>TICP - Turbine trip</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Operator Action]</title>
<details>Call Cryo on-call +46 46 888 31 66 Tell them that TICP turbines have tripped</details>
</guidance>
</pv>
<pv name="CrS-TICP:Cryo-Virt-MJFLT1:Major_Fault_051">
<description>TICP - Coldbox instrument air loss</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Operator Action]</title>
<details>Call Cryo on-call +46 46 888 31 66 Tell them that TICP coldbox have lost instrument air</details>
</guidance>
</pv>
<pv name="CrS-TICP:Cryo-Virt-MJFLT1:Major_Fault_081">
<description>TICP - Coldbox communication loss Coldbox stopped-</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Operator Action]</title>
<details>Call Cryo on-call +46 46 888 31 66 Tell them that TICP coldbox have stopped due to communication failure.</details>
</guidance>
</pv>
<pv name="CrS-TICP:Cryo-Virt-MJFLT1:Major_Fault_080">
<description>TICP - Coldbox emergency stoped.</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Operator Action]</title>
<details>Call Cryo on-call +46 46 888 31 66 Tell them that TICP colbox have been emergency stopped</details>
</guidance>
</pv>
</component>
<component name="TICP recovery system">
<pv name="CrS-TICP:Cryo-Virt-MJFLT2:Major_Fault_001">
<description>TICP - Gasbag level high high</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Operator Action]</title>
<details>Call Cryo on-call +46 46 888 31 66 Tell them that Gasbag level is high</details>
</guidance>
</pv>
<pv name="CrS-TICP:Cryo-Virt-MJFLT2:Major_Fault_010">
<description>TICP - HP Compressor A failed to start</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Operator Action]</title>
<details>Call Cryo on-call +46 46 888 31 66 Tell them that Revocery compressor A have failed to start</details>
</guidance>
</pv>
<pv name="CrS-TICP:Cryo-Virt-MJFLT2:Major_Fault_011">
<description>TICP - HP Compressor B failed to start</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Operator Action]</title>
<details>Call Cryo on-call +46 46 888 31 66 Tell them that Revocery compressor A have failed to starB</details>
</guidance>
</pv>
</component>
<component name="TICP WCS">
<pv name="CrS-TICP:Cryo-Virt-MJFLT2:Major_Fault_025">
<description>TICP - Compressor station major fault</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Operator Action]</title>
<details>Call Cryo on-call +46 46 888 31 66 Tell them that TICP Kaeser compressor have tripped</details>
</guidance>
</pv>
<pv name="CrS-TICP:Cryo-Virt-MJFLT2:Major_Fault_028">
<description>TICP - Kaeser station major fault</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Operator Action]</title>
<details>Call Cryo on-call +46 46 888 31 66 Tell them that TICP Kaeser compressor have tripped</details>
</guidance>
</pv>
<pv name="CrS-TICP:Cryo-Virt-MJFLT2:Major_Fault_040">
<description>TICP WCS - Emergency stopped</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Operator Action]</title>
<details>Call Cryo on-call +46 46 888 31 66 Tell them that TICP WCS have been emergency stopped.</details>
</guidance>
</pv>
<pv name="CrS-TICP:Cryo-Virt-MJFLT2:Major_Fault_090">
<description>TICP PVPS - General fault</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Operator Action]</title>
<details>Call Cryo on-call +46 46 888 31 66 Tell them that TICP PVPS have tripped.</details>
</guidance>
</pv>
</component>
</component>
<component name="TMCP">
<component name="TMCP WSC">
<pv name="CrS-TMCP:Cryo-PI-217001:AHH">
<description>TMCP: HP pressure too high. Compressor trip.</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Operator Action]</title>
<details>Call Cryo on-call +46 46 888 31 66 Tell them that TMCP compressors tripped</details>
</guidance>
</pv>
<pv name="CrS-TMCP:Cryo-PI-23400:AHH">
<description>TMCP: LP pressure too high</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Operator Action]</title>
<details>Call Cryo on-call +46 46 888 31 66 Tell them that TMCP compressors tripped</details>
</guidance>
</pv>
<pv name="CrS-TMCP:Cryo-PI-21701:AL">
<description>TMCP: HP Buffer pressure too low.</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Operator Action]</title>
<details>Call Cryo on-call +46 46 888 31 66 Tell them that TMCP buffer pressure low</details>
</guidance>
</pv>
<pv name="CrS-TMCP:Cryo-PS-29070:AL">
<description>TMCP: Instrument air pressure low. (GMP)</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Operator Action]</title>
<details>Call Cryo on-call +46 46 888 31 66 Tell them that TMCP GMP lost instrument air</details>
</guidance>
</pv>
<pv name="CrS-TMCP:Cryo-PS-29090:AL">
<description>TMCP: Instrument air pressure low. </description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Operator Action]</title>
<details>Call Cryo on-call +46 46 888 31 66 Tell them that TMCP WCS lost instrument air</details>
</guidance>
</pv>
<pv name="CrS-TMCP:Cryo-PS-29183:ZAL">
<description>TMCP: Instrument air pressure low. (Compressor 1)</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Operator Action]</title>
<details>Call Cryo on-call +46 46 888 31 66 Tell them that TMCP Compressor 1 have lost instruemnt air</details>
</guidance>
</pv>
<pv name="CrS-TMCP:Cryo-PS-29283:ZAL">
<description>TMCP: Instrument air pressure low. (Compressor 2)</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Operator Action]</title>
<details>Call Cryo on-call +46 46 888 31 66 Tell them that TMCP Compressor 2 have lost instrument air</details>
</guidance>
</pv>
<pv name="CrS-TMCP:Cryo-C-21101:TrpComFail">
<description>Compressor and TMCP comms timeout</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Operator Action]</title>
<details>Call Cryo on-call +46 46 888 31 66 Tell them that TMCP WCS 1 has lost communication and tripped</details>
</guidance>
</pv>
<pv name="CrS-TMCP:Cryo-C-21201:TrpComFail">
<description>Compressor and TMCP comms timeout</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Operator Action]</title>
<details>Call Cryo on-call +46 46 888 31 66 Tell them that TMCP WCS 2 has lost communication and tripped</details>
</guidance>
</pv>
</component>
<component name="TMCP Coldbox General">
<pv name="CrS-TMCP:Cryo-PS-39050:SdInstrAirMiss">
<description>TMCP: Instrument air pressure low. (Coldbox)</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Operator Action]</title>
<details>Call Cryo on-call +46 46 888 31 66 Tell them that TMCP Coldbox have lost instrument air</details>
</guidance>
</pv>
<pv name="CrS-TMCP:Cryo-PI-39001:AH">
<description>TMCP: Coldbox insulations vacuum too high.</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Operator Action]</title>
<details>Call Cryo on-call +46 46 888 31 66 Tell them that TMCP Coldbox have lost insulation vacuum</details>
</guidance>
</pv>
</component>
<component name="TMCP Turbines">
<pv name="CrS-TMCP:Cryo-SI-31131:AHH">
<description>TMCP: T-31130 Overspeed trip</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Operator Action]</title>
<details>Call Cryo on-call +46 46 888 31 66 Tell them that TMCP Turbine 1 have tripped</details>
</guidance>
</pv>
<pv name="CrS-TMCP:Cryo-SI-31131:ALL">
<description>TMCP: T-31130 underspeed trip</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Operator Action]</title>
<details>Call Cryo on-call +46 46 888 31 66 Tell them that TMCP Turbine 1 have tripped</details>
</guidance>
</pv>
<pv name="CrS-TMCP:Cryo-TI-31131:AHH">
<description>TMCP: T-31130 brake temperature too high trip.</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Operator Action]</title>
<details>Call Cryo on-call +46 46 888 31 66 Tell them that TMCP Turbine 1 have tripped</details>
</guidance>
</pv>
<pv name="CrS-TMCP:Cryo-SI-31231:AHH">
<description>TMCP: T-31230 Overspeed trip</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Operator Action]</title>
<details>Call Cryo on-call +46 46 888 31 66 Tell them that TMCP Turbine 2 have tripped</details>
</guidance>
</pv>
<pv name="CrS-TMCP:Cryo-SI-31231:ALL">
<description>TMCP: T-31230 underspeed trip</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Operator Action]</title>
<details>Call Cryo on-call +46 46 888 31 66 Tell them that TMCP Turbine 2 have tripped</details>
</guidance>
</pv>
<pv name="CrS-TMCP:Cryo-TI-31231:AHH">
<description>TMCP: T-31230 brake temperature too high trip.</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Operator Action]</title>
<details>Call Cryo on-call +46 46 888 31 66 Tell them that TMCP Turbine 1 have tripped</details>
</guidance>
</pv>
<pv name="CrS-TMCP:Cryo-SI-31331:AHH">
<description>TMCP: T-31130 Overspeed trip</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Operator Action]</title>
<details>Call Cryo on-call +46 46 888 31 66 Tell them that TMCP Turbine 3 have tripped</details>
</guidance>
</pv>
<pv name="CrS-TMCP:Cryo-SI-31331:ALL">
<description>TMCP: T-31130 underspeed trip</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Operator Action]</title>
<details>Call Cryo on-call +46 46 888 31 66 Tell them that TMCP Turbine 3 have tripped</details>
</guidance>
</pv>
<pv name="CrS-TMCP:Cryo-TI-31331:AHH">
<description>TMCP: T-31130 brake temperature too high trip.</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Operator Action]</title>
<details>Call Cryo on-call +46 46 888 31 66 Tell them that TMCP Turbine 3 have tripped</details>
</guidance>
</pv>
</component>
</component>
<component name="Emergency Showers">
<component name="Emergency Showers ACH">
<pv name="CrS-PHS:Cryo-GS-001shw:Alarm">
<description>G04 ACH Hall emergency shower triggered</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Operator Action]</title>
<details>Go directly to G04 ACH (right hall) to check if anyone needs assistance</details>
</guidance>
</pv>
<pv name="CrS-PHS:Cryo-GS-001eye:Alarm">
<description>G04 ACH Hall eye shower triggered</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Operator Action]</title>
<details>Go directly to G04 ACH (right hall) to check if anyone needs assistance</details>
</guidance>
</pv>
</component>
<component name="Emergency Showers TCH">
<pv name="CrS-PHS:Cryo-GS-002shw:Alarm">
<description>G04 TCH Hall emergency shower triggered </description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Operator Action]</title>
<details>Go directly to G04 TCH (left hall) to check if anyone needs assistance</details>
</guidance>
</pv>
<pv name="CrS-PHS:Cryo-GS-002eye:Alarm">
<description>G04 TCH Hall eye shower triggered </description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Operator Action]</title>
<details>Go directly to G04 TCH (left hall) to check if anyone needs assistance</details>
</guidance>
</pv>
</component>
</component>
<component name="LINAC">
<component name="CTL">
<pv name="CrS-CTL::VacNotOK">
<description>CTL ISO Vacuum is bad</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>contact CRYO on-call, bad iso-vacuum in the CTL</details>
</guidance>
</pv>
</component>
<component name="SHL">
<pv name="CrS-SHC::GlobalAlarm">
<description>Global alarm on Safety Helium Collector</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>contact CRYO on-call, Global alarm in Safety Helium Collector (check status of valves)</details>
</guidance>
</pv>
</component>
<component name="End Box">
<pv name="Spk-000CDL:Cryo-LT-91:HIHI">
<description>LT-91 helium level extremely high</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>contact CRYO on-call and inform SCL on-call, Cryomodule liquid level too high (check the other gauge LT-92). </details>
</guidance>
</pv>
<pv name="Spk-000CDL:Cryo-LT-92:HIHI">
<description>LT-92 helium level extremely high</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>contact CRYO on-call and inform SCL on-call, Cryomodule liquid level too high (check the other gauge LT-91). </details>
</guidance>
</pv>
</component>
<component name="Cryomodules\SPK-010 Cryomodule">
<pv name="Spk-010Crm:Cryo-LT-001:HIHI">
<description>LT-001 helium level extremely high</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>contact CRYO on-call and inform SCL on-call, Cryomodule liquid level too high (check the other gauge LT-002). Close supply valve CV01, CV02</details>
</guidance>
</pv>
<pv name="Spk-010Crm:Cryo-LT-002:HIHI">
<description>LT-002 helium level extremely high</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>contact CRYO on-call and inform SCL on-call, Cryomodule liquid level too high (check the other gauge LT-001). Close supply valve CV01, CV02</details>
</guidance>
</pv>
<pv name="Spk-010Crm:Cryo-LT-001:HI">
<description>LT-001 helium level high</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>contact CRYO on-call and inform SCL on-call, Cryomodule liquid level high (check the other gauge LT-002). Check level regulation valve settings, if needed: adjust LMN_LO and if necessary: Close supply valve CV01, CV02</details>
</guidance>
</pv>
<pv name="Spk-010Crm:Cryo-LT-002:HI">
<description>LT-002 helium level high</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>contact CRYO on-call and inform SCL on-call, Cryomodule liquid level high (check the other gauge LT-002). Check level regulation valve settings, if needed: adjust LMN_LO and if necessary: Close supply valve CV01, CV02</details>
</guidance>
</pv>
<pv name="Spk-010Crm:Cryo-LT-001:LO">
<description>LT-001 helium level low</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>contact CRYO on-call and inform SCL on-call, Cryomodule liquid level low (check the other gauge LT-001). Check level regulation valve settings, if needed: adjust LMN_HI</details>
</guidance>
</pv>
<pv name="Spk-010Crm:Cryo-LT-002:LO">
<description>LT-002 helium level low</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>contact CRYO on-call and inform SCL on-call, Cryomodule liquid level low (check the other gauge LT-002). Check level regulation valvesettings, if needed: adjust LMN_HI</details>
</guidance>
</pv>
<pv name="Spk-010Crm:Cryo-LT-001:LOLO">
<description>LT-002 helium level extremely low</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>contact CRYO on-call and inform SCL on-call, Cryomodule liquid level too low (check the other gauge LT-001). Check level regulation valve settings, if needed: adjust LMN_HI</details>
</guidance>
</pv>
<pv name="Spk-010Crm:Cryo-LT-002:LOLO">
<description>LT-002 helium level extremely low</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>contact CRYO on-call and inform SCL on-call, Cryomodule liquid level too low (check the other gauge LT-002). Check level regulation valvesettings, if needed: adjust LMN_HI</details>
</guidance>
</pv>
<pv name="Spk-010Crm:Cryo-PT-003:HIHI">
<description>Cavity tanks pressure is too high (typical value is 31mbar in 2K mode and 1050mbar in 4K mode)</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>contact CRYO on-call and inform SCL on-call, Cryomodule bath pressure too high (check the other gauge PT002). Close supply valve CV01, CV02 if necessary</details>
</guidance>
</pv>
<pv name="Spk-010Crm:Cryo-PT-003:Cable_Error">
<description>Cavity tanks Pressure Sensor cables are disconnected</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>contact CRYO on-call and inform SCL on-call, Cryomodule pressure cable seems disconnected (value gets stuck), assign PT002 as measuring device on CV04 and CV-090 </details>
</guidance>
</pv>
<pv name="Spk-010Crm:Cryo-PT-002:HIHI">
<description>Cavity tanks pressure is too high (typical value is 31mbar in 2K mode and 1050mbar in 4K mode)</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>contact CRYO on-call and inform SCL on-call,, Cryomodule bath pressure too high (check the other gauge PT003). Close supply valve CV01, CV02 if necessary</details>
</guidance>
</pv>
<pv name="Spk-010Crm:Cryo-PT-002:Cable_Error">
<description>Cavity tanks Pressure Sensor cables are disconnected</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>contact CRYO on-call and inform SCL on-call, Cryomodule pressure cable seems disconnected (value gets stuck), assign PT003 as measuring device on CV04 and CV-090 </details>
</guidance>
</pv>
<pv name="Spk-010Crm:Cryo-TT-120:P_Limit_LO">
<description>Power coupler flange temperature low</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>contact CRYO on-call and inform SCL on-call, power coupler flange temperature is low, check heater output, if nominal then coupler flow needs to be adjusted (reduced)</details>
</guidance>
</pv>
<pv name="Spk-010Crm:Cryo-TT-120:P_Limit_LOLO">
<description>Power coupler flange temperature too low</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>contact CRYO on-call and inform SCL on-call, power coupler flange temperature is too low, check heater output, if nominal then coupler flow needs to be adjusted (reduced)</details>
</guidance>
</pv>
<pv name="Spk-010Crm:Cryo-TT-120:P_Limit_HIHI">
<description>Power coupler flange temperature too high</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>contact CRYO on-call and inform SCL on-call, power coupler flange temperature is too high, check heater output, if nominal then coupler flow needs to be adjusted (reduced)</details>
</guidance>
</pv>
<pv name="Spk-010Crm:Cryo-TT-220:P_Limit_LO">
<description>Power coupler flange temperature low</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>contact CRYO on-call and inform SCL on-call, power coupler flange temperature is low, check heater output, if nominal then coupler flow needs to be adjusted (reduced)</details>
</guidance>
</pv>
<pv name="Spk-010Crm:Cryo-TT-220:P_Limit_LOLO">
<description>Power coupler flange temperature too low</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>contact CRYO on-call and inform SCL on-call, power coupler flange temperature is too low, check heater output, if nominal then coupler flow needs to be adjusted (reduced)</details>
</guidance>
</pv>
<pv name="Spk-010Crm:Cryo-TT-220:P_Limit_HIHI">
<description>Power coupler flange temperature too high</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>contact CRYO on-call and inform SCL on-call, power coupler flange temperature is too high, check heater output, if nominal then coupler flow needs to be adjusted (reduced)</details>
</guidance>
</pv>
<pv name="Spk-010Crm:WtrC-FS-013:Flow_OK_WF">
<description>! Alarm when signal drops from 1 to zero. No Water Flow Antenna 1</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>contact CRYO on-call and inform SCL on-call, assure Flange temperature TT-120 is correct. Risk of Water freeze if no flow and temperature too low</details>
</guidance>
</pv>
<pv name="Spk-010Crm:WtrC-FS-014:Flow_OK_WF">
<description>! Alarm when signal drops from 1 to zero. No Water Flow Window 1</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>contact CRYO on-call and inform SCL on-call, assure Flange temperature TT-120 is correct. Risk of Water freeze if no flow and temperature too low</details>
</guidance>
</pv>
<pv name="Spk-010Crm:WtrC-FS-023:Flow_OK_WF">
<description>! Alarm when signal drops from 1 to zero. No Water Flow Antenna 2</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>contact CRYO on-call and inform SCL on-call, assure Flange temperature TT-120 is correct. Risk of Water freeze if no flow and temperature too low</details>
</guidance>
</pv>
<pv name="Spk-010Crm:WtrC-FS-024:Flow_OK_WF">
<description>! Alarm when signal drops from 1 to zero. No Water Flow Window 2</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>contact CRYO on-call and inform SCL on-call, assure Flange temperature TT-120 is correct. Risk of Water freeze if no flow and temperature too low</details>
</guidance>
</pv>
</component>
<component name="Cryomodules\SPK-020 Cryomodule">
<pv name="Spk-020Crm:Cryo-LT-001:HIHI">
<description>LT-001 helium level extremely high</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>contact CRYO on-call and inform SCL on-call, Cryomodule liquid level too high (check the other gauge LT-002). Close supply valve CV01, CV02</details>
</guidance>
</pv>
<pv name="Spk-020Crm:Cryo-LT-002:HIHI">
<description>LT-002 helium level extremely high</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>contact CRYO on-call and inform SCL on-call, Cryomodule liquid level too high (check the other gauge LT-001). Close supply valve CV01, CV02</details>
</guidance>
</pv>
<pv name="Spk-020Crm:Cryo-LT-001:HI">
<description>LT-001 helium level high</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>contact CRYO on-call and inform SCL on-call, Cryomodule liquid level high (check the other gauge LT-002). Check level regulation valve settings, if needed: adjust LMN_LO and if necessary: Close supply valve CV01, CV02</details>
</guidance>
</pv>
<pv name="Spk-020Crm:Cryo-LT-002:HI">
<description>LT-002 helium level high</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>contact CRYO on-call and inform SCL on-call, Cryomodule liquid level high (check the other gauge LT-002). Check level regulation valve settings, if needed: adjust LMN_LO and if necessary: Close supply valve CV01, CV02</details>
</guidance>
</pv>
<pv name="Spk-020Crm:Cryo-LT-001:LO">
<description>LT-001 helium level low</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>contact CRYO on-call and inform SCL on-call, Cryomodule liquid level low (check the other gauge LT-001). Check level regulation valve settings, if needed: adjust LMN_HI</details>
</guidance>
</pv>
<pv name="Spk-020Crm:Cryo-LT-002:LO">
<description>LT-002 helium level low</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>contact CRYO on-call and inform SCL on-call, Cryomodule liquid level low (check the other gauge LT-002). Check level regulation valvesettings, if needed: adjust LMN_HI</details>
</guidance>
</pv>
<pv name="Spk-020Crm:Cryo-LT-001:LOLO">
<description>LT-002 helium level extremely low</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>contact CRYO on-call and inform SCL on-call, Cryomodule liquid level too low (check the other gauge LT-001). Check level regulation valve settings, if needed: adjust LMN_HI</details>
</guidance>
</pv>
<pv name="Spk-020Crm:Cryo-LT-002:LOLO">
<description>LT-002 helium level extremely low</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>contact CRYO on-call and inform SCL on-call, Cryomodule liquid level too low (check the other gauge LT-002). Check level regulation valvesettings, if needed: adjust LMN_HI</details>
</guidance>
</pv>
<pv name="Spk-020Crm:Cryo-PT-003:HIHI">
<description>Cavity tanks pressure is too high (typical value is 31mbar in 2K mode and 1050mbar in 4K mode)</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>contact CRYO on-call and inform SCL on-call, Cryomodule bath pressure too high (check the other gauge PT002). Close supply valve CV01, CV02 if necessary</details>
</guidance>
</pv>
<pv name="Spk-020Crm:Cryo-PT-003:Cable_Error">
<description>Cavity tanks Pressure Sensor cables are disconnected</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>contact CRYO on-call and inform SCL on-call, Cryomodule pressure cable seems disconnected (value gets stuck), assign PT002 as measuring device on CV04 and CV-090 </details>
</guidance>
</pv>
<pv name="Spk-020Crm:Cryo-PT-002:HIHI">
<description>Cavity tanks pressure is too high (typical value is 31mbar in 2K mode and 1050mbar in 4K mode)</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>contact CRYO on-call and inform SCL on-call,, Cryomodule bath pressure too high (check the other gauge PT003). Close supply valve CV01, CV02 if necessary</details>
</guidance>
</pv>
<pv name="Spk-020Crm:Cryo-PT-002:Cable_Error">
<description>Cavity tanks Pressure Sensor cables are disconnected</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>contact CRYO on-call and inform SCL on-call, Cryomodule pressure cable seems disconnected (value gets stuck), assign PT003 as measuring device on CV04 and CV-090 </details>
</guidance>
</pv>
<pv name="Spk-020Crm:Cryo-TT-120:P_Limit_LO">
<description>Power coupler flange temperature low</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>contact CRYO on-call and inform SCL on-call, power coupler flange temperature is low, check heater output, if nominal then coupler flow needs to be adjusted (reduced)</details>
</guidance>
</pv>
<pv name="Spk-020Crm:Cryo-TT-120:P_Limit_LOLO">
<description>Power coupler flange temperature too low</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>contact CRYO on-call and inform SCL on-call, power coupler flange temperature is too low, check heater output, if nominal then coupler flow needs to be adjusted (reduced)</details>
</guidance>
</pv>
<pv name="Spk-020Crm:Cryo-TT-120:P_Limit_HIHI">
<description>Power coupler flange temperature too high</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>contact CRYO on-call and inform SCL on-call, power coupler flange temperature is too high, check heater output, if nominal then coupler flow needs to be adjusted (reduced)</details>
</guidance>
</pv>
<pv name="Spk-020Crm:Cryo-TT-220:P_Limit_LO">
<description>Power coupler flange temperature low</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>contact CRYO on-call and inform SCL on-call, power coupler flange temperature is low, check heater output, if nominal then coupler flow needs to be adjusted (reduced)</details>
</guidance>
</pv>
<pv name="Spk-020Crm:Cryo-TT-220:P_Limit_LOLO">
<description>Power coupler flange temperature too low</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>contact CRYO on-call and inform SCL on-call, power coupler flange temperature is too low, check heater output, if nominal then coupler flow needs to be adjusted (reduced)</details>
</guidance>
</pv>
<pv name="Spk-020Crm:Cryo-TT-220:P_Limit_HIHI">
<description>Power coupler flange temperature too high</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>contact CRYO on-call and inform SCL on-call, power coupler flange temperature is too high, check heater output, if nominal then coupler flow needs to be adjusted (reduced)</details>
</guidance>
</pv>
<pv name="Spk-020Crm:WtrC-FS-013:Flow_OK_WF">
<description>! Alarm when signal drops from 1 to zero. No Water Flow Antenna 1</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>contact CRYO on-call and inform SCL on-call, assure Flange temperature TT-120 is correct. Risk of Water freeze if no flow and temperature too low</details>
</guidance>
</pv>
<pv name="Spk-020Crm:WtrC-FS-014:Flow_OK_WF">
<description>! Alarm when signal drops from 1 to zero. No Water Flow Window 1</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>contact CRYO on-call and inform SCL on-call, assure Flange temperature TT-120 is correct. Risk of Water freeze if no flow and temperature too low</details>
</guidance>
</pv>
<pv name="Spk-020Crm:WtrC-FS-023:Flow_OK_WF">
<description>! Alarm when signal drops from 1 to zero. No Water Flow Antenna 2</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>contact CRYO on-call and inform SCL on-call, assure Flange temperature TT-120 is correct. Risk of Water freeze if no flow and temperature too low</details>
</guidance>
</pv>
<pv name="Spk-020Crm:WtrC-FS-024:Flow_OK_WF">
<description>! Alarm when signal drops from 1 to zero. No Water Flow Window 2</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>contact CRYO on-call and inform SCL on-call, assure Flange temperature TT-120 is correct. Risk of Water freeze if no flow and temperature too low</details>
</guidance>
</pv>
</component>
<component name="Cryomodules\SPK-030 Cryomodule">
<pv name="Spk-030Crm:Cryo-LT-001:HIHI">
<description>LT-001 helium level extremely high</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>contact CRYO on-call and inform SCL on-call, Cryomodule liquid level too high (check the other gauge LT-002). Close supply valve CV01, CV02</details>
</guidance>
</pv>
<pv name="Spk-030Crm:Cryo-LT-002:HIHI">
<description>LT-002 helium level extremely high</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>contact CRYO on-call and inform SCL on-call, Cryomodule liquid level too high (check the other gauge LT-001). Close supply valve CV01, CV02</details>
</guidance>
</pv>
<pv name="Spk-030Crm:Cryo-LT-001:HI">
<description>LT-001 helium level high</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>contact CRYO on-call and inform SCL on-call, Cryomodule liquid level high (check the other gauge LT-002). Check level regulation valve settings, if needed: adjust LMN_LO and if necessary: Close supply valve CV01, CV02</details>
</guidance>
</pv>
<pv name="Spk-030Crm:Cryo-LT-002:HI">
<description>LT-002 helium level high</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>contact CRYO on-call and inform SCL on-call, Cryomodule liquid level high (check the other gauge LT-002). Check level regulation valve settings, if needed: adjust LMN_LO and if necessary: Close supply valve CV01, CV02</details>
</guidance>
</pv>
<pv name="Spk-030Crm:Cryo-LT-001:LO">
<description>LT-001 helium level low</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>contact CRYO on-call and inform SCL on-call, Cryomodule liquid level low (check the other gauge LT-001). Check level regulation valve settings, if needed: adjust LMN_HI</details>
</guidance>
</pv>
<pv name="Spk-030Crm:Cryo-LT-002:LO">
<description>LT-002 helium level low</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>contact CRYO on-call and inform SCL on-call, Cryomodule liquid level low (check the other gauge LT-002). Check level regulation valvesettings, if needed: adjust LMN_HI</details>
</guidance>
</pv>
<pv name="Spk-030Crm:Cryo-LT-001:LOLO">
<description>LT-002 helium level extremely low</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>contact CRYO on-call and inform SCL on-call, Cryomodule liquid level too low (check the other gauge LT-001). Check level regulation valve settings, if needed: adjust LMN_HI</details>
</guidance>
</pv>
<pv name="Spk-030Crm:Cryo-LT-002:LOLO">
<description>LT-002 helium level extremely low</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>contact CRYO on-call and inform SCL on-call, Cryomodule liquid level too low (check the other gauge LT-002). Check level regulation valvesettings, if needed: adjust LMN_HI</details>
</guidance>
</pv>
<pv name="Spk-030Crm:Cryo-PT-003:HIHI">
<description>Cavity tanks pressure is too high (typical value is 31mbar in 2K mode and 1050mbar in 4K mode)</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>contact CRYO on-call and inform SCL on-call, Cryomodule bath pressure too high (check the other gauge PT002). Close supply valve CV01, CV02 if necessary</details>
</guidance>
</pv>
<pv name="Spk-030Crm:Cryo-PT-003:Cable_Error">
<description>Cavity tanks Pressure Sensor cables are disconnected</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>contact CRYO on-call and inform SCL on-call, Cryomodule pressure cable seems disconnected (value gets stuck), assign PT002 as measuring device on CV04 and CV-090 </details>
</guidance>
</pv>
<pv name="Spk-030Crm:Cryo-PT-002:HIHI">
<description>Cavity tanks pressure is too high (typical value is 31mbar in 2K mode and 1050mbar in 4K mode)</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>contact CRYO on-call and inform SCL on-call,, Cryomodule bath pressure too high (check the other gauge PT003). Close supply valve CV01, CV02 if necessary</details>
</guidance>
</pv>
<pv name="Spk-030Crm:Cryo-PT-002:Cable_Error">
<description>Cavity tanks Pressure Sensor cables are disconnected</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>contact CRYO on-call and inform SCL on-call, Cryomodule pressure cable seems disconnected (value gets stuck), assign PT003 as measuring device on CV04 and CV-090 </details>
</guidance>
</pv>
<pv name="Spk-030Crm:Cryo-TT-120:P_Limit_LO">
<description>Power coupler flange temperature low</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>contact CRYO on-call and inform SCL on-call, power coupler flange temperature is low, check heater output, if nominal then coupler flow needs to be adjusted (reduced)</details>
</guidance>
</pv>
<pv name="Spk-030Crm:Cryo-TT-120:P_Limit_LOLO">
<description>Power coupler flange temperature too low</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>contact CRYO on-call and inform SCL on-call, power coupler flange temperature is too low, check heater output, if nominal then coupler flow needs to be adjusted (reduced)</details>
</guidance>
</pv>
<pv name="Spk-030Crm:Cryo-TT-120:P_Limit_HIHI">
<description>Power coupler flange temperature too high</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>contact CRYO on-call and inform SCL on-call, power coupler flange temperature is too high, check heater output, if nominal then coupler flow needs to be adjusted (reduced)</details>
</guidance>
</pv>
<pv name="Spk-030Crm:Cryo-TT-220:P_Limit_LO">
<description>Power coupler flange temperature low</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>contact CRYO on-call and inform SCL on-call, power coupler flange temperature is low, check heater output, if nominal then coupler flow needs to be adjusted (reduced)</details>
</guidance>
</pv>
<pv name="Spk-030Crm:Cryo-TT-220:P_Limit_LOLO">
<description>Power coupler flange temperature too low</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>contact CRYO on-call and inform SCL on-call, power coupler flange temperature is too low, check heater output, if nominal then coupler flow needs to be adjusted (reduced)</details>
</guidance>
</pv>
<pv name="Spk-030Crm:Cryo-TT-220:P_Limit_HIHI">
<description>Power coupler flange temperature too high</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>contact CRYO on-call and inform SCL on-call, power coupler flange temperature is too high, check heater output, if nominal then coupler flow needs to be adjusted (reduced)</details>
</guidance>
</pv>
<pv name="Spk-030Crm:WtrC-FS-013:Flow_OK_WF">
<description>! Alarm when signal drops from 1 to zero. No Water Flow Antenna 1</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>contact CRYO on-call and inform SCL on-call, assure Flange temperature TT-120 is correct. Risk of Water freeze if no flow and temperature too low</details>
</guidance>
</pv>
<pv name="Spk-030Crm:WtrC-FS-014:Flow_OK_WF">
<description>! Alarm when signal drops from 1 to zero. No Water Flow Window 1</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>contact CRYO on-call and inform SCL on-call, assure Flange temperature TT-120 is correct. Risk of Water freeze if no flow and temperature too low</details>
</guidance>
</pv>
<pv name="Spk-030Crm:WtrC-FS-023:Flow_OK_WF">
<description>! Alarm when signal drops from 1 to zero. No Water Flow Antenna 2</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>contact CRYO on-call and inform SCL on-call, assure Flange temperature TT-120 is correct. Risk of Water freeze if no flow and temperature too low</details>
</guidance>
</pv>
<pv name="Spk-030Crm:WtrC-FS-024:Flow_OK_WF">
<description>! Alarm when signal drops from 1 to zero. No Water Flow Window 2</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>contact CRYO on-call and inform SCL on-call, assure Flange temperature TT-120 is correct. Risk of Water freeze if no flow and temperature too low</details>
</guidance>
</pv>
</component>
<component name="Cryomodules\SPK-040 Cryomodule">
<pv name="Spk-040Crm:Cryo-LT-001:HIHI">
<description>LT-001 helium level extremely high</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>contact CRYO on-call and inform SCL on-call, Cryomodule liquid level too high (check the other gauge LT-002). Close supply valve CV01, CV02</details>
</guidance>
</pv>
<pv name="Spk-040Crm:Cryo-LT-002:HIHI">
<description>LT-002 helium level extremely high</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>contact CRYO on-call and inform SCL on-call, Cryomodule liquid level too high (check the other gauge LT-001). Close supply valve CV01, CV02</details>
</guidance>
</pv>
<pv name="Spk-040Crm:Cryo-LT-001:HI">
<description>LT-001 helium level high</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>contact CRYO on-call and inform SCL on-call, Cryomodule liquid level high (check the other gauge LT-002). Check level regulation valve settings, if needed: adjust LMN_LO and if necessary: Close supply valve CV01, CV02</details>
</guidance>
</pv>
<pv name="Spk-040Crm:Cryo-LT-002:HI">
<description>LT-002 helium level high</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>contact CRYO on-call and inform SCL on-call, Cryomodule liquid level high (check the other gauge LT-002). Check level regulation valve settings, if needed: adjust LMN_LO and if necessary: Close supply valve CV01, CV02</details>
</guidance>
</pv>
<pv name="Spk-040Crm:Cryo-LT-001:LO">
<description>LT-001 helium level low</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>contact CRYO on-call and inform SCL on-call, Cryomodule liquid level low (check the other gauge LT-001). Check level regulation valve settings, if needed: adjust LMN_HI</details>
</guidance>
</pv>
<pv name="Spk-040Crm:Cryo-LT-002:LO">
<description>LT-002 helium level low</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>contact CRYO on-call and inform SCL on-call, Cryomodule liquid level low (check the other gauge LT-002). Check level regulation valvesettings, if needed: adjust LMN_HI</details>
</guidance>
</pv>
<pv name="Spk-040Crm:Cryo-LT-001:LOLO">
<description>LT-002 helium level extremely low</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>contact CRYO on-call and inform SCL on-call, Cryomodule liquid level too low (check the other gauge LT-001). Check level regulation valve settings, if needed: adjust LMN_HI</details>
</guidance>
</pv>
<pv name="Spk-040Crm:Cryo-LT-002:LOLO">
<description>LT-002 helium level extremely low</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>contact CRYO on-call and inform SCL on-call, Cryomodule liquid level too low (check the other gauge LT-002). Check level regulation valvesettings, if needed: adjust LMN_HI</details>
</guidance>
</pv>
<pv name="Spk-040Crm:Cryo-PT-003:HIHI">
<description>Cavity tanks pressure is too high (typical value is 31mbar in 2K mode and 1050mbar in 4K mode)</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>contact CRYO on-call and inform SCL on-call, Cryomodule bath pressure too high (check the other gauge PT002). Close supply valve CV01, CV02 if necessary</details>
</guidance>
</pv>
<pv name="Spk-040Crm:Cryo-PT-003:Cable_Error">
<description>Cavity tanks Pressure Sensor cables are disconnected</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>contact CRYO on-call and inform SCL on-call, Cryomodule pressure cable seems disconnected (value gets stuck), assign PT002 as measuring device on CV04 and CV-090 </details>
</guidance>
</pv>
<pv name="Spk-040Crm:Cryo-PT-002:HIHI">
<description>Cavity tanks pressure is too high (typical value is 31mbar in 2K mode and 1050mbar in 4K mode)</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>contact CRYO on-call and inform SCL on-call,, Cryomodule bath pressure too high (check the other gauge PT003). Close supply valve CV01, CV02 if necessary</details>
</guidance>
</pv>
<pv name="Spk-040Crm:Cryo-PT-002:Cable_Error">
<description>Cavity tanks Pressure Sensor cables are disconnected</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>contact CRYO on-call and inform SCL on-call, Cryomodule pressure cable seems disconnected (value gets stuck), assign PT003 as measuring device on CV04 and CV-090 </details>
</guidance>
</pv>
<pv name="Spk-040Crm:Cryo-TT-120:P_Limit_LO">
<description>Power coupler flange temperature low</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>contact CRYO on-call and inform SCL on-call, power coupler flange temperature is low, check heater output, if nominal then coupler flow needs to be adjusted (reduced)</details>
</guidance>
</pv>
<pv name="Spk-040Crm:Cryo-TT-120:P_Limit_LOLO">
<description>Power coupler flange temperature too low</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>contact CRYO on-call and inform SCL on-call, power coupler flange temperature is too low, check heater output, if nominal then coupler flow needs to be adjusted (reduced)</details>
</guidance>
</pv>
<pv name="Spk-040Crm:Cryo-TT-120:P_Limit_HIHI">
<description>Power coupler flange temperature too high</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>contact CRYO on-call and inform SCL on-call, power coupler flange temperature is too high, check heater output, if nominal then coupler flow needs to be adjusted (reduced)</details>
</guidance>
</pv>
<pv name="Spk-040Crm:Cryo-TT-220:P_Limit_LO">
<description>Power coupler flange temperature low</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>contact CRYO on-call and inform SCL on-call, power coupler flange temperature is low, check heater output, if nominal then coupler flow needs to be adjusted (reduced)</details>
</guidance>
</pv>
<pv name="Spk-040Crm:Cryo-TT-220:P_Limit_LOLO">
<description>Power coupler flange temperature too low</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>contact CRYO on-call and inform SCL on-call, power coupler flange temperature is too low, check heater output, if nominal then coupler flow needs to be adjusted (reduced)</details>
</guidance>
</pv>
<pv name="Spk-040Crm:Cryo-TT-220:P_Limit_HIHI">
<description>Power coupler flange temperature too high</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>contact CRYO on-call and inform SCL on-call, power coupler flange temperature is too high, check heater output, if nominal then coupler flow needs to be adjusted (reduced)</details>
</guidance>
</pv>
<pv name="Spk-040Crm:WtrC-FS-013:Flow_OK_WF">
<description>! Alarm when signal drops from 1 to zero. No Water Flow Antenna 1</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>contact CRYO on-call and inform SCL on-call, assure Flange temperature TT-120 is correct. Risk of Water freeze if no flow and temperature too low</details>
</guidance>
</pv>
<pv name="Spk-040Crm:WtrC-FS-014:Flow_OK_WF">
<description>! Alarm when signal drops from 1 to zero. No Water Flow Window 1</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>contact CRYO on-call and inform SCL on-call, assure Flange temperature TT-120 is correct. Risk of Water freeze if no flow and temperature too low</details>
</guidance>
</pv>
<pv name="Spk-040Crm:WtrC-FS-023:Flow_OK_WF">
<description>! Alarm when signal drops from 1 to zero. No Water Flow Antenna 2</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>contact CRYO on-call and inform SCL on-call, assure Flange temperature TT-120 is correct. Risk of Water freeze if no flow and temperature too low</details>
</guidance>
</pv>
<pv name="Spk-040Crm:WtrC-FS-024:Flow_OK_WF">
<description>! Alarm when signal drops from 1 to zero. No Water Flow Window 2</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>contact CRYO on-call and inform SCL on-call, assure Flange temperature TT-120 is correct. Risk of Water freeze if no flow and temperature too low</details>
</guidance>
</pv>
</component>
<component name="Cryomodules\SPK-050 Cryomodule">
<pv name="Spk-050Crm:Cryo-LT-001:HIHI">
<description>LT-001 helium level extremely high</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>contact CRYO on-call and inform SCL on-call, Cryomodule liquid level too high (check the other gauge LT-002). Close supply valve CV01, CV02</details>
</guidance>
</pv>
<pv name="Spk-050Crm:Cryo-LT-002:HIHI">
<description>LT-002 helium level extremely high</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>contact CRYO on-call and inform SCL on-call, Cryomodule liquid level too high (check the other gauge LT-001). Close supply valve CV01, CV02</details>
</guidance>
</pv>
<pv name="Spk-050Crm:Cryo-LT-001:HI">
<description>LT-001 helium level high</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>contact CRYO on-call and inform SCL on-call, Cryomodule liquid level high (check the other gauge LT-002). Check level regulation valve settings, if needed: adjust LMN_LO and if necessary: Close supply valve CV01, CV02</details>
</guidance>
</pv>
<pv name="Spk-050Crm:Cryo-LT-002:HI">
<description>LT-002 helium level high</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>contact CRYO on-call and inform SCL on-call, Cryomodule liquid level high (check the other gauge LT-002). Check level regulation valve settings, if needed: adjust LMN_LO and if necessary: Close supply valve CV01, CV02</details>
</guidance>
</pv>
<pv name="Spk-050Crm:Cryo-LT-001:LO">
<description>LT-001 helium level low</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>contact CRYO on-call and inform SCL on-call, Cryomodule liquid level low (check the other gauge LT-001). Check level regulation valve settings, if needed: adjust LMN_HI</details>
</guidance>
</pv>
<pv name="Spk-050Crm:Cryo-LT-002:LO">
<description>LT-002 helium level low</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>contact CRYO on-call and inform SCL on-call, Cryomodule liquid level low (check the other gauge LT-002). Check level regulation valvesettings, if needed: adjust LMN_HI</details>
</guidance>
</pv>
<pv name="Spk-050Crm:Cryo-LT-001:LOLO">
<description>LT-002 helium level extremely low</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>contact CRYO on-call and inform SCL on-call, Cryomodule liquid level too low (check the other gauge LT-001). Check level regulation valve settings, if needed: adjust LMN_HI</details>
</guidance>
</pv>
<pv name="Spk-050Crm:Cryo-LT-002:LOLO">
<description>LT-002 helium level extremely low</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>contact CRYO on-call and inform SCL on-call, Cryomodule liquid level too low (check the other gauge LT-002). Check level regulation valvesettings, if needed: adjust LMN_HI</details>
</guidance>
</pv>
<pv name="Spk-050Crm:Cryo-PT-003:HIHI">
<description>Cavity tanks pressure is too high (typical value is 31mbar in 2K mode and 1050mbar in 4K mode)</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>contact CRYO on-call and inform SCL on-call, Cryomodule bath pressure too high (check the other gauge PT002). Close supply valve CV01, CV02 if necessary</details>
</guidance>
</pv>
<pv name="Spk-050Crm:Cryo-PT-003:Cable_Error">
<description>Cavity tanks Pressure Sensor cables are disconnected</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>contact CRYO on-call and inform SCL on-call, Cryomodule pressure cable seems disconnected (value gets stuck), assign PT002 as measuring device on CV04 and CV-090 </details>
</guidance>
</pv>
<pv name="Spk-050Crm:Cryo-PT-002:HIHI">
<description>Cavity tanks pressure is too high (typical value is 31mbar in 2K mode and 1050mbar in 4K mode)</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>contact CRYO on-call and inform SCL on-call,, Cryomodule bath pressure too high (check the other gauge PT003). Close supply valve CV01, CV02 if necessary</details>
</guidance>
</pv>
<pv name="Spk-050Crm:Cryo-PT-002:Cable_Error">
<description>Cavity tanks Pressure Sensor cables are disconnected</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>contact CRYO on-call and inform SCL on-call, Cryomodule pressure cable seems disconnected (value gets stuck), assign PT003 as measuring device on CV04 and CV-090 </details>
</guidance>
</pv>
<pv name="Spk-050Crm:Cryo-TT-120:P_Limit_LO">
<description>Power coupler flange temperature low</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>contact CRYO on-call and inform SCL on-call, power coupler flange temperature is low, check heater output, if nominal then coupler flow needs to be adjusted (reduced)</details>
</guidance>
</pv>
<pv name="Spk-050Crm:Cryo-TT-120:P_Limit_LOLO">
<description>Power coupler flange temperature too low</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>contact CRYO on-call and inform SCL on-call, power coupler flange temperature is too low, check heater output, if nominal then coupler flow needs to be adjusted (reduced)</details>
</guidance>
</pv>
<pv name="Spk-050Crm:Cryo-TT-120:P_Limit_HIHI">
<description>Power coupler flange temperature too high</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>contact CRYO on-call and inform SCL on-call, power coupler flange temperature is too high, check heater output, if nominal then coupler flow needs to be adjusted (reduced)</details>
</guidance>
</pv>
<pv name="Spk-050Crm:Cryo-TT-220:P_Limit_LO">
<description>Power coupler flange temperature low</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>contact CRYO on-call and inform SCL on-call, power coupler flange temperature is low, check heater output, if nominal then coupler flow needs to be adjusted (reduced)</details>
</guidance>
</pv>
<pv name="Spk-050Crm:Cryo-TT-220:P_Limit_LOLO">
<description>Power coupler flange temperature too low</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>contact CRYO on-call and inform SCL on-call, power coupler flange temperature is too low, check heater output, if nominal then coupler flow needs to be adjusted (reduced)</details>
</guidance>
</pv>
<pv name="Spk-050Crm:Cryo-TT-220:P_Limit_HIHI">
<description>Power coupler flange temperature too high</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>contact CRYO on-call and inform SCL on-call, power coupler flange temperature is too high, check heater output, if nominal then coupler flow needs to be adjusted (reduced)</details>
</guidance>
</pv>
<pv name="Spk-050Crm:WtrC-FS-013:Flow_OK_WF">
<description>! Alarm when signal drops from 1 to zero. No Water Flow Antenna 1</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>contact CRYO on-call and inform SCL on-call, assure Flange temperature TT-120 is correct. Risk of Water freeze if no flow and temperature too low</details>
</guidance>
</pv>
<pv name="Spk-050Crm:WtrC-FS-014:Flow_OK_WF">
<description>! Alarm when signal drops from 1 to zero. No Water Flow Window 1</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>contact CRYO on-call and inform SCL on-call, assure Flange temperature TT-120 is correct. Risk of Water freeze if no flow and temperature too low</details>
</guidance>
</pv>
<pv name="Spk-050Crm:WtrC-FS-023:Flow_OK_WF">
<description>! Alarm when signal drops from 1 to zero. No Water Flow Antenna 2</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>contact CRYO on-call and inform SCL on-call, assure Flange temperature TT-120 is correct. Risk of Water freeze if no flow and temperature too low</details>
</guidance>
</pv>
<pv name="Spk-050Crm:WtrC-FS-024:Flow_OK_WF">
<description>! Alarm when signal drops from 1 to zero. No Water Flow Window 2</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>contact CRYO on-call and inform SCL on-call, assure Flange temperature TT-120 is correct. Risk of Water freeze if no flow and temperature too low</details>
</guidance>
</pv>
</component>
<component name="Cryomodules\SPK-060 Cryomodule">
<pv name="Spk-060Crm:Cryo-LT-001:HIHI">
<description>LT-001 helium level extremely high</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>contact CRYO on-call and inform SCL on-call, Cryomodule liquid level too high (check the other gauge LT-002). Close supply valve CV01, CV02</details>
</guidance>
</pv>
<pv name="Spk-060Crm:Cryo-LT-002:HIHI">
<description>LT-002 helium level extremely high</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>contact CRYO on-call and inform SCL on-call, Cryomodule liquid level too high (check the other gauge LT-001). Close supply valve CV01, CV02</details>
</guidance>
</pv>
<pv name="Spk-060Crm:Cryo-LT-001:HI">
<description>LT-001 helium level high</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>contact CRYO on-call and inform SCL on-call, Cryomodule liquid level high (check the other gauge LT-002). Check level regulation valve settings, if needed: adjust LMN_LO and if necessary: Close supply valve CV01, CV02</details>
</guidance>
</pv>
<pv name="Spk-060Crm:Cryo-LT-002:HI">
<description>LT-002 helium level high</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>contact CRYO on-call and inform SCL on-call, Cryomodule liquid level high (check the other gauge LT-002). Check level regulation valve settings, if needed: adjust LMN_LO and if necessary: Close supply valve CV01, CV02</details>
</guidance>
</pv>
<pv name="Spk-060Crm:Cryo-LT-001:LO">
<description>LT-001 helium level low</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>contact CRYO on-call and inform SCL on-call, Cryomodule liquid level low (check the other gauge LT-001). Check level regulation valve settings, if needed: adjust LMN_HI</details>
</guidance>
</pv>
<pv name="Spk-060Crm:Cryo-LT-002:LO">
<description>LT-002 helium level low</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>contact CRYO on-call and inform SCL on-call, Cryomodule liquid level low (check the other gauge LT-002). Check level regulation valvesettings, if needed: adjust LMN_HI</details>
</guidance>
</pv>
<pv name="Spk-060Crm:Cryo-LT-001:LOLO">
<description>LT-002 helium level extremely low</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>contact CRYO on-call and inform SCL on-call, Cryomodule liquid level too low (check the other gauge LT-001). Check level regulation valve settings, if needed: adjust LMN_HI</details>
</guidance>
</pv>
<pv name="Spk-060Crm:Cryo-LT-002:LOLO">
<description>LT-002 helium level extremely low</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>contact CRYO on-call and inform SCL on-call, Cryomodule liquid level too low (check the other gauge LT-002). Check level regulation valvesettings, if needed: adjust LMN_HI</details>
</guidance>
</pv>
<pv name="Spk-060Crm:Cryo-PT-003:HIHI">
<description>Cavity tanks pressure is too high (typical value is 31mbar in 2K mode and 1050mbar in 4K mode)</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>contact CRYO on-call and inform SCL on-call, Cryomodule bath pressure too high (check the other gauge PT002). Close supply valve CV01, CV02 if necessary</details>
</guidance>
</pv>
<pv name="Spk-060Crm:Cryo-PT-003:Cable_Error">
<description>Cavity tanks Pressure Sensor cables are disconnected</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>contact CRYO on-call and inform SCL on-call, Cryomodule pressure cable seems disconnected (value gets stuck), assign PT002 as measuring device on CV04 and CV-090 </details>
</guidance>
</pv>
<pv name="Spk-060Crm:Cryo-PT-002:HIHI">
<description>Cavity tanks pressure is too high (typical value is 31mbar in 2K mode and 1050mbar in 4K mode)</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>contact CRYO on-call and inform SCL on-call,, Cryomodule bath pressure too high (check the other gauge PT003). Close supply valve CV01, CV02 if necessary</details>
</guidance>
</pv>
<pv name="Spk-060Crm:Cryo-PT-002:Cable_Error">
<description>Cavity tanks Pressure Sensor cables are disconnected</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>contact CRYO on-call and inform SCL on-call, Cryomodule pressure cable seems disconnected (value gets stuck), assign PT003 as measuring device on CV04 and CV-090 </details>
</guidance>
</pv>
<pv name="Spk-060Crm:Cryo-TT-120:P_Limit_LO">
<description>Power coupler flange temperature low</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>contact CRYO on-call and inform SCL on-call, power coupler flange temperature is low, check heater output, if nominal then coupler flow needs to be adjusted (reduced)</details>
</guidance>
</pv>
<pv name="Spk-060Crm:Cryo-TT-120:P_Limit_LOLO">
<description>Power coupler flange temperature too low</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>contact CRYO on-call and inform SCL on-call, power coupler flange temperature is too low, check heater output, if nominal then coupler flow needs to be adjusted (reduced)</details>
</guidance>
</pv>
<pv name="Spk-060Crm:Cryo-TT-120:P_Limit_HIHI">
<description>Power coupler flange temperature too high</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>contact CRYO on-call and inform SCL on-call, power coupler flange temperature is too high, check heater output, if nominal then coupler flow needs to be adjusted (reduced)</details>
</guidance>
</pv>
<pv name="Spk-060Crm:Cryo-TT-220:P_Limit_LO">
<description>Power coupler flange temperature low</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>contact CRYO on-call and inform SCL on-call, power coupler flange temperature is low, check heater output, if nominal then coupler flow needs to be adjusted (reduced)</details>
</guidance>
</pv>
<pv name="Spk-060Crm:Cryo-TT-220:P_Limit_LOLO">
<description>Power coupler flange temperature too low</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>contact CRYO on-call and inform SCL on-call, power coupler flange temperature is too low, check heater output, if nominal then coupler flow needs to be adjusted (reduced)</details>
</guidance>
</pv>
<pv name="Spk-060Crm:Cryo-TT-220:P_Limit_HIHI">
<description>Power coupler flange temperature too high</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>contact CRYO on-call and inform SCL on-call, power coupler flange temperature is too high, check heater output, if nominal then coupler flow needs to be adjusted (reduced)</details>
</guidance>
</pv>
<pv name="Spk-060Crm:WtrC-FS-013:Flow_OK_WF">
<description>! Alarm when signal drops from 1 to zero. No Water Flow Antenna 1</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>contact CRYO on-call and inform SCL on-call, assure Flange temperature TT-120 is correct. Risk of Water freeze if no flow and temperature too low</details>
</guidance>
</pv>
<pv name="Spk-060Crm:WtrC-FS-014:Flow_OK_WF">
<description>! Alarm when signal drops from 1 to zero. No Water Flow Window 1</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>contact CRYO on-call and inform SCL on-call, assure Flange temperature TT-120 is correct. Risk of Water freeze if no flow and temperature too low</details>
</guidance>
</pv>
<pv name="Spk-060Crm:WtrC-FS-023:Flow_OK_WF">
<description>! Alarm when signal drops from 1 to zero. No Water Flow Antenna 2</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>contact CRYO on-call and inform SCL on-call, assure Flange temperature TT-120 is correct. Risk of Water freeze if no flow and temperature too low</details>
</guidance>
</pv>
<pv name="Spk-060Crm:WtrC-FS-024:Flow_OK_WF">
<description>! Alarm when signal drops from 1 to zero. No Water Flow Window 2</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>contact CRYO on-call and inform SCL on-call, assure Flange temperature TT-120 is correct. Risk of Water freeze if no flow and temperature too low</details>
</guidance>
</pv>
</component>
<component name="Cryomodules\SPK-070 Cryomodule">
<pv name="Spk-070Crm:Cryo-LT-001:HIHI">
<description>LT-001 helium level extremely high</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>contact CRYO on-call and inform SCL on-call, Cryomodule liquid level too high (check the other gauge LT-002). Close supply valve CV01, CV02</details>
</guidance>
</pv>
<pv name="Spk-070Crm:Cryo-LT-002:HIHI">
<description>LT-002 helium level extremely high</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>contact CRYO on-call and inform SCL on-call, Cryomodule liquid level too high (check the other gauge LT-001). Close supply valve CV01, CV02</details>
</guidance>
</pv>
<pv name="Spk-070Crm:Cryo-LT-001:HI">
<description>LT-001 helium level high</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>contact CRYO on-call and inform SCL on-call, Cryomodule liquid level high (check the other gauge LT-002). Check level regulation valve settings, if needed: adjust LMN_LO and if necessary: Close supply valve CV01, CV02</details>
</guidance>
</pv>
<pv name="Spk-070Crm:Cryo-LT-002:HI">
<description>LT-002 helium level high</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>contact CRYO on-call and inform SCL on-call, Cryomodule liquid level high (check the other gauge LT-002). Check level regulation valve settings, if needed: adjust LMN_LO and if necessary: Close supply valve CV01, CV02</details>
</guidance>
</pv>
<pv name="Spk-070Crm:Cryo-LT-001:LO">
<description>LT-001 helium level low</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>contact CRYO on-call and inform SCL on-call, Cryomodule liquid level low (check the other gauge LT-001). Check level regulation valve settings, if needed: adjust LMN_HI</details>
</guidance>
</pv>
<pv name="Spk-070Crm:Cryo-LT-002:LO">
<description>LT-002 helium level low</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>contact CRYO on-call and inform SCL on-call, Cryomodule liquid level low (check the other gauge LT-002). Check level regulation valvesettings, if needed: adjust LMN_HI</details>
</guidance>
</pv>
<pv name="Spk-070Crm:Cryo-LT-001:LOLO">
<description>LT-002 helium level extremely low</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>contact CRYO on-call and inform SCL on-call, Cryomodule liquid level too low (check the other gauge LT-001). Check level regulation valve settings, if needed: adjust LMN_HI</details>
</guidance>
</pv>
<pv name="Spk-070Crm:Cryo-LT-002:LOLO">
<description>LT-002 helium level extremely low</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>contact CRYO on-call and inform SCL on-call, Cryomodule liquid level too low (check the other gauge LT-002). Check level regulation valvesettings, if needed: adjust LMN_HI</details>
</guidance>
</pv>
<pv name="Spk-070Crm:Cryo-PT-003:HIHI">
<description>Cavity tanks pressure is too high (typical value is 31mbar in 2K mode and 1050mbar in 4K mode)</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>contact CRYO on-call and inform SCL on-call, Cryomodule bath pressure too high (check the other gauge PT002). Close supply valve CV01, CV02 if necessary</details>
</guidance>
</pv>
<pv name="Spk-070Crm:Cryo-PT-003:Cable_Error">
<description>Cavity tanks Pressure Sensor cables are disconnected</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>contact CRYO on-call and inform SCL on-call, Cryomodule pressure cable seems disconnected (value gets stuck), assign PT002 as measuring device on CV04 and CV-090 </details>
</guidance>
</pv>
<pv name="Spk-070Crm:Cryo-PT-002:HIHI">
<description>Cavity tanks pressure is too high (typical value is 31mbar in 2K mode and 1050mbar in 4K mode)</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>contact CRYO on-call and inform SCL on-call,, Cryomodule bath pressure too high (check the other gauge PT003). Close supply valve CV01, CV02 if necessary</details>
</guidance>
</pv>
<pv name="Spk-070Crm:Cryo-PT-002:Cable_Error">
<description>Cavity tanks Pressure Sensor cables are disconnected</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>contact CRYO on-call and inform SCL on-call, Cryomodule pressure cable seems disconnected (value gets stuck), assign PT003 as measuring device on CV04 and CV-090 </details>
</guidance>
</pv>
<pv name="Spk-070Crm:Cryo-TT-120:P_Limit_LO">
<description>Power coupler flange temperature low</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>contact CRYO on-call and inform SCL on-call, power coupler flange temperature is low, check heater output, if nominal then coupler flow needs to be adjusted (reduced)</details>
</guidance>
</pv>
<pv name="Spk-070Crm:Cryo-TT-120:P_Limit_LOLO">
<description>Power coupler flange temperature too low</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>contact CRYO on-call and inform SCL on-call, power coupler flange temperature is too low, check heater output, if nominal then coupler flow needs to be adjusted (reduced)</details>
</guidance>
</pv>
<pv name="Spk-070Crm:Cryo-TT-120:P_Limit_HIHI">
<description>Power coupler flange temperature too high</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>contact CRYO on-call and inform SCL on-call, power coupler flange temperature is too high, check heater output, if nominal then coupler flow needs to be adjusted (reduced)</details>
</guidance>
</pv>
<pv name="Spk-070Crm:Cryo-TT-220:P_Limit_LO">
<description>Power coupler flange temperature low</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>contact CRYO on-call and inform SCL on-call, power coupler flange temperature is low, check heater output, if nominal then coupler flow needs to be adjusted (reduced)</details>
</guidance>
</pv>
<pv name="Spk-070Crm:Cryo-TT-220:P_Limit_LOLO">
<description>Power coupler flange temperature too low</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>contact CRYO on-call and inform SCL on-call, power coupler flange temperature is too low, check heater output, if nominal then coupler flow needs to be adjusted (reduced)</details>
</guidance>
</pv>
<pv name="Spk-070Crm:Cryo-TT-220:P_Limit_HIHI">
<description>Power coupler flange temperature too high</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>contact CRYO on-call and inform SCL on-call, power coupler flange temperature is too high, check heater output, if nominal then coupler flow needs to be adjusted (reduced)</details>
</guidance>
</pv>
<pv name="Spk-070Crm:WtrC-FS-013:Flow_OK_WF">
<description>! Alarm when signal drops from 1 to zero. No Water Flow Antenna 1</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>contact CRYO on-call and inform SCL on-call, assure Flange temperature TT-120 is correct. Risk of Water freeze if no flow and temperature too low</details>
</guidance>
</pv>
<pv name="Spk-070Crm:WtrC-FS-014:Flow_OK_WF">
<description>! Alarm when signal drops from 1 to zero. No Water Flow Window 1</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>contact CRYO on-call and inform SCL on-call, assure Flange temperature TT-120 is correct. Risk of Water freeze if no flow and temperature too low</details>
</guidance>
</pv>
<pv name="Spk-070Crm:WtrC-FS-023:Flow_OK_WF">
<description>! Alarm when signal drops from 1 to zero. No Water Flow Antenna 2</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>contact CRYO on-call and inform SCL on-call, assure Flange temperature TT-120 is correct. Risk of Water freeze if no flow and temperature too low</details>
</guidance>
</pv>
<pv name="Spk-070Crm:WtrC-FS-024:Flow_OK_WF">
<description>! Alarm when signal drops from 1 to zero. No Water Flow Window 2</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>contact CRYO on-call and inform SCL on-call, assure Flange temperature TT-120 is correct. Risk of Water freeze if no flow and temperature too low</details>
</guidance>
</pv>
</component>
<component name="Cryomodules\SPK-080 Cryomodule">
<pv name="Spk-080Crm:Cryo-LT-001:HIHI">
<description>LT-001 helium level extremely high</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>contact CRYO on-call and inform SCL on-call, Cryomodule liquid level too high (check the other gauge LT-002). Close supply valve CV01, CV02</details>
</guidance>
</pv>
<pv name="Spk-080Crm:Cryo-LT-002:HIHI">
<description>LT-002 helium level extremely high</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>contact CRYO on-call and inform SCL on-call, Cryomodule liquid level too high (check the other gauge LT-001). Close supply valve CV01, CV02</details>
</guidance>
</pv>
<pv name="Spk-080Crm:Cryo-LT-001:HI">
<description>LT-001 helium level high</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>contact CRYO on-call and inform SCL on-call, Cryomodule liquid level high (check the other gauge LT-002). Check level regulation valve settings, if needed: adjust LMN_LO and if necessary: Close supply valve CV01, CV02</details>
</guidance>
</pv>
<pv name="Spk-080Crm:Cryo-LT-002:HI">
<description>LT-002 helium level high</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>contact CRYO on-call and inform SCL on-call, Cryomodule liquid level high (check the other gauge LT-002). Check level regulation valve settings, if needed: adjust LMN_LO and if necessary: Close supply valve CV01, CV02</details>
</guidance>
</pv>
<pv name="Spk-080Crm:Cryo-LT-001:LO">
<description>LT-001 helium level low</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>contact CRYO on-call and inform SCL on-call, Cryomodule liquid level low (check the other gauge LT-001). Check level regulation valve settings, if needed: adjust LMN_HI</details>
</guidance>
</pv>
<pv name="Spk-080Crm:Cryo-LT-002:LO">
<description>LT-002 helium level low</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>contact CRYO on-call and inform SCL on-call, Cryomodule liquid level low (check the other gauge LT-002). Check level regulation valvesettings, if needed: adjust LMN_HI</details>
</guidance>
</pv>
<pv name="Spk-080Crm:Cryo-LT-001:LOLO">
<description>LT-002 helium level extremely low</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>contact CRYO on-call and inform SCL on-call, Cryomodule liquid level too low (check the other gauge LT-001). Check level regulation valve settings, if needed: adjust LMN_HI</details>
</guidance>
</pv>
<pv name="Spk-080Crm:Cryo-LT-002:LOLO">
<description>LT-002 helium level extremely low</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>contact CRYO on-call and inform SCL on-call, Cryomodule liquid level too low (check the other gauge LT-002). Check level regulation valvesettings, if needed: adjust LMN_HI</details>
</guidance>
</pv>
<pv name="Spk-080Crm:Cryo-PT-003:HIHI">
<description>Cavity tanks pressure is too high (typical value is 31mbar in 2K mode and 1050mbar in 4K mode)</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>contact CRYO on-call and inform SCL on-call, Cryomodule bath pressure too high (check the other gauge PT002). Close supply valve CV01, CV02 if necessary</details>
</guidance>
</pv>
<pv name="Spk-080Crm:Cryo-PT-003:Cable_Error">
<description>Cavity tanks Pressure Sensor cables are disconnected</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>contact CRYO on-call and inform SCL on-call, Cryomodule pressure cable seems disconnected (value gets stuck), assign PT002 as measuring device on CV04 and CV-090 </details>
</guidance>
</pv>
<pv name="Spk-080Crm:Cryo-PT-002:HIHI">
<description>Cavity tanks pressure is too high (typical value is 31mbar in 2K mode and 1050mbar in 4K mode)</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>contact CRYO on-call and inform SCL on-call,, Cryomodule bath pressure too high (check the other gauge PT003). Close supply valve CV01, CV02 if necessary</details>
</guidance>
</pv>
<pv name="Spk-080Crm:Cryo-PT-002:Cable_Error">
<description>Cavity tanks Pressure Sensor cables are disconnected</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>contact CRYO on-call and inform SCL on-call, Cryomodule pressure cable seems disconnected (value gets stuck), assign PT003 as measuring device on CV04 and CV-090 </details>
</guidance>
</pv>
<pv name="Spk-080Crm:Cryo-TT-120:P_Limit_LO">
<description>Power coupler flange temperature low</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>contact CRYO on-call and inform SCL on-call, power coupler flange temperature is low, check heater output, if nominal then coupler flow needs to be adjusted (reduced)</details>
</guidance>
</pv>
<pv name="Spk-080Crm:Cryo-TT-120:P_Limit_LOLO">
<description>Power coupler flange temperature too low</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>contact CRYO on-call and inform SCL on-call, power coupler flange temperature is too low, check heater output, if nominal then coupler flow needs to be adjusted (reduced)</details>
</guidance>
</pv>
<pv name="Spk-080Crm:Cryo-TT-120:P_Limit_HIHI">
<description>Power coupler flange temperature too high</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>contact CRYO on-call and inform SCL on-call, power coupler flange temperature is too high, check heater output, if nominal then coupler flow needs to be adjusted (reduced)</details>
</guidance>
</pv>
<pv name="Spk-080Crm:Cryo-TT-220:P_Limit_LO">
<description>Power coupler flange temperature low</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>contact CRYO on-call and inform SCL on-call, power coupler flange temperature is low, check heater output, if nominal then coupler flow needs to be adjusted (reduced)</details>
</guidance>
</pv>
<pv name="Spk-080Crm:Cryo-TT-220:P_Limit_LOLO">
<description>Power coupler flange temperature too low</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>contact CRYO on-call and inform SCL on-call, power coupler flange temperature is too low, check heater output, if nominal then coupler flow needs to be adjusted (reduced)</details>
</guidance>
</pv>
<pv name="Spk-080Crm:Cryo-TT-220:P_Limit_HIHI">
<description>Power coupler flange temperature too high</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>contact CRYO on-call and inform SCL on-call, power coupler flange temperature is too high, check heater output, if nominal then coupler flow needs to be adjusted (reduced)</details>
</guidance>
</pv>
<pv name="Spk-080Crm:WtrC-FS-013:Flow_OK_WF">
<description>! Alarm when signal drops from 1 to zero. No Water Flow Antenna 1</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>contact CRYO on-call and inform SCL on-call, assure Flange temperature TT-120 is correct. Risk of Water freeze if no flow and temperature too low</details>
</guidance>
</pv>
<pv name="Spk-080Crm:WtrC-FS-014:Flow_OK_WF">
<description>! Alarm when signal drops from 1 to zero. No Water Flow Window 1</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>contact CRYO on-call and inform SCL on-call, assure Flange temperature TT-120 is correct. Risk of Water freeze if no flow and temperature too low</details>
</guidance>
</pv>
<pv name="Spk-080Crm:WtrC-FS-023:Flow_OK_WF">
<description>! Alarm when signal drops from 1 to zero. No Water Flow Antenna 2</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>contact CRYO on-call and inform SCL on-call, assure Flange temperature TT-120 is correct. Risk of Water freeze if no flow and temperature too low</details>
</guidance>
</pv>
<pv name="Spk-080Crm:WtrC-FS-024:Flow_OK_WF">
<description>! Alarm when signal drops from 1 to zero. No Water Flow Window 2</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>contact CRYO on-call and inform SCL on-call, assure Flange temperature TT-120 is correct. Risk of Water freeze if no flow and temperature too low</details>
</guidance>
</pv>
</component>
<component name="Cryomodules\SPK-090 Cryomodule">
<pv name="Spk-090Crm:Cryo-LT-001:HIHI">
<description>LT-001 helium level extremely high</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>contact CRYO on-call and inform SCL on-call, Cryomodule liquid level too high (check the other gauge LT-002). Close supply valve CV01, CV02</details>
</guidance>
</pv>
<pv name="Spk-090Crm:Cryo-LT-002:HIHI">
<description>LT-002 helium level extremely high</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>contact CRYO on-call and inform SCL on-call, Cryomodule liquid level too high (check the other gauge LT-001). Close supply valve CV01, CV02</details>
</guidance>
</pv>
<pv name="Spk-090Crm:Cryo-LT-001:HI">
<description>LT-001 helium level high</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>contact CRYO on-call and inform SCL on-call, Cryomodule liquid level high (check the other gauge LT-002). Check level regulation valve settings, if needed: adjust LMN_LO and if necessary: Close supply valve CV01, CV02</details>
</guidance>
</pv>
<pv name="Spk-090Crm:Cryo-LT-002:HI">
<description>LT-002 helium level high</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>contact CRYO on-call and inform SCL on-call, Cryomodule liquid level high (check the other gauge LT-002). Check level regulation valve settings, if needed: adjust LMN_LO and if necessary: Close supply valve CV01, CV02</details>
</guidance>
</pv>
<pv name="Spk-090Crm:Cryo-LT-001:LO">
<description>LT-001 helium level low</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>contact CRYO on-call and inform SCL on-call, Cryomodule liquid level low (check the other gauge LT-001). Check level regulation valve settings, if needed: adjust LMN_HI</details>
</guidance>
</pv>
<pv name="Spk-090Crm:Cryo-LT-002:LO">
<description>LT-002 helium level low</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>contact CRYO on-call and inform SCL on-call, Cryomodule liquid level low (check the other gauge LT-002). Check level regulation valvesettings, if needed: adjust LMN_HI</details>
</guidance>
</pv>
<pv name="Spk-090Crm:Cryo-LT-001:LOLO">
<description>LT-002 helium level extremely low</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>contact CRYO on-call and inform SCL on-call, Cryomodule liquid level too low (check the other gauge LT-001). Check level regulation valve settings, if needed: adjust LMN_HI</details>
</guidance>
</pv>
<pv name="Spk-090Crm:Cryo-LT-002:LOLO">
<description>LT-002 helium level extremely low</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>contact CRYO on-call and inform SCL on-call, Cryomodule liquid level too low (check the other gauge LT-002). Check level regulation valvesettings, if needed: adjust LMN_HI</details>
</guidance>
</pv>
<pv name="Spk-090Crm:Cryo-PT-003:HIHI">
<description>Cavity tanks pressure is too high (typical value is 31mbar in 2K mode and 1050mbar in 4K mode)</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>contact CRYO on-call and inform SCL on-call, Cryomodule bath pressure too high (check the other gauge PT002). Close supply valve CV01, CV02 if necessary</details>
</guidance>
</pv>
<pv name="Spk-090Crm:Cryo-PT-003:Cable_Error">
<description>Cavity tanks Pressure Sensor cables are disconnected</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>contact CRYO on-call and inform SCL on-call, Cryomodule pressure cable seems disconnected (value gets stuck), assign PT002 as measuring device on CV04 and CV-090 </details>
</guidance>
</pv>
<pv name="Spk-090Crm:Cryo-PT-002:HIHI">
<description>Cavity tanks pressure is too high (typical value is 31mbar in 2K mode and 1050mbar in 4K mode)</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>contact CRYO on-call and inform SCL on-call,, Cryomodule bath pressure too high (check the other gauge PT003). Close supply valve CV01, CV02 if necessary</details>
</guidance>
</pv>
<pv name="Spk-090Crm:Cryo-PT-002:Cable_Error">
<description>Cavity tanks Pressure Sensor cables are disconnected</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>contact CRYO on-call and inform SCL on-call, Cryomodule pressure cable seems disconnected (value gets stuck), assign PT003 as measuring device on CV04 and CV-090 </details>
</guidance>
</pv>
<pv name="Spk-090Crm:Cryo-TT-120:P_Limit_LO">
<description>Power coupler flange temperature low</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>contact CRYO on-call and inform SCL on-call, power coupler flange temperature is low, check heater output, if nominal then coupler flow needs to be adjusted (reduced)</details>
</guidance>
</pv>
<pv name="Spk-090Crm:Cryo-TT-120:P_Limit_LOLO">
<description>Power coupler flange temperature too low</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>contact CRYO on-call and inform SCL on-call, power coupler flange temperature is too low, check heater output, if nominal then coupler flow needs to be adjusted (reduced)</details>
</guidance>
</pv>
<pv name="Spk-090Crm:Cryo-TT-120:P_Limit_HIHI">
<description>Power coupler flange temperature too high</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>contact CRYO on-call and inform SCL on-call, power coupler flange temperature is too high, check heater output, if nominal then coupler flow needs to be adjusted (reduced)</details>
</guidance>
</pv>
<pv name="Spk-090Crm:Cryo-TT-220:P_Limit_LO">
<description>Power coupler flange temperature low</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>contact CRYO on-call and inform SCL on-call, power coupler flange temperature is low, check heater output, if nominal then coupler flow needs to be adjusted (reduced)</details>
</guidance>
</pv>
<pv name="Spk-090Crm:Cryo-TT-220:P_Limit_LOLO">
<description>Power coupler flange temperature too low</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>contact CRYO on-call and inform SCL on-call, power coupler flange temperature is too low, check heater output, if nominal then coupler flow needs to be adjusted (reduced)</details>
</guidance>
</pv>
<pv name="Spk-090Crm:Cryo-TT-220:P_Limit_HIHI">
<description>Power coupler flange temperature too high</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>contact CRYO on-call and inform SCL on-call, power coupler flange temperature is too high, check heater output, if nominal then coupler flow needs to be adjusted (reduced)</details>
</guidance>
</pv>
<pv name="Spk-090Crm:WtrC-FS-013:Flow_OK_WF">
<description>! Alarm when signal drops from 1 to zero. No Water Flow Antenna 1</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>contact CRYO on-call and inform SCL on-call, assure Flange temperature TT-120 is correct. Risk of Water freeze if no flow and temperature too low</details>
</guidance>
</pv>
<pv name="Spk-090Crm:WtrC-FS-014:Flow_OK_WF">
<description>! Alarm when signal drops from 1 to zero. No Water Flow Window 1</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>contact CRYO on-call and inform SCL on-call, assure Flange temperature TT-120 is correct. Risk of Water freeze if no flow and temperature too low</details>
</guidance>
</pv>
<pv name="Spk-090Crm:WtrC-FS-023:Flow_OK_WF">
<description>! Alarm when signal drops from 1 to zero. No Water Flow Antenna 2</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>contact CRYO on-call and inform SCL on-call, assure Flange temperature TT-120 is correct. Risk of Water freeze if no flow and temperature too low</details>
</guidance>
</pv>
<pv name="Spk-090Crm:WtrC-FS-024:Flow_OK_WF">
<description>! Alarm when signal drops from 1 to zero. No Water Flow Window 2</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>contact CRYO on-call and inform SCL on-call, assure Flange temperature TT-120 is correct. Risk of Water freeze if no flow and temperature too low</details>
</guidance>
</pv>
</component>
<component name="Cryomodules\SPK-100 Cryomodule">
<pv name="Spk-100Crm:Cryo-LT-001:HIHI">
<description>LT-001 helium level extremely high</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>contact CRYO on-call and inform SCL on-call, Cryomodule liquid level too high (check the other gauge LT-002). Close supply valve CV01, CV02</details>
</guidance>
</pv>
<pv name="Spk-100Crm:Cryo-LT-002:HIHI">
<description>LT-002 helium level extremely high</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>contact CRYO on-call and inform SCL on-call, Cryomodule liquid level too high (check the other gauge LT-001). Close supply valve CV01, CV02</details>
</guidance>
</pv>
<pv name="Spk-100Crm:Cryo-LT-001:HI">
<description>LT-001 helium level high</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>contact CRYO on-call and inform SCL on-call, Cryomodule liquid level high (check the other gauge LT-002). Check level regulation valve settings, if needed: adjust LMN_LO and if necessary: Close supply valve CV01, CV02</details>
</guidance>
</pv>
<pv name="Spk-100Crm:Cryo-LT-002:HI">
<description>LT-002 helium level high</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>contact CRYO on-call and inform SCL on-call, Cryomodule liquid level high (check the other gauge LT-002). Check level regulation valve settings, if needed: adjust LMN_LO and if necessary: Close supply valve CV01, CV02</details>
</guidance>
</pv>
<pv name="Spk-100Crm:Cryo-LT-001:LO">
<description>LT-001 helium level low</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>contact CRYO on-call and inform SCL on-call, Cryomodule liquid level low (check the other gauge LT-001). Check level regulation valve settings, if needed: adjust LMN_HI</details>
</guidance>
</pv>
<pv name="Spk-100Crm:Cryo-LT-002:LO">
<description>LT-002 helium level low</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>contact CRYO on-call and inform SCL on-call, Cryomodule liquid level low (check the other gauge LT-002). Check level regulation valvesettings, if needed: adjust LMN_HI</details>
</guidance>
</pv>
<pv name="Spk-100Crm:Cryo-LT-001:LOLO">
<description>LT-002 helium level extremely low</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>contact CRYO on-call and inform SCL on-call, Cryomodule liquid level too low (check the other gauge LT-001). Check level regulation valve settings, if needed: adjust LMN_HI</details>
</guidance>
</pv>
<pv name="Spk-100Crm:Cryo-LT-002:LOLO">
<description>LT-002 helium level extremely low</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>contact CRYO on-call and inform SCL on-call, Cryomodule liquid level too low (check the other gauge LT-002). Check level regulation valvesettings, if needed: adjust LMN_HI</details>
</guidance>
</pv>
<pv name="Spk-100Crm:Cryo-PT-003:HIHI">
<description>Cavity tanks pressure is too high (typical value is 31mbar in 2K mode and 1050mbar in 4K mode)</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>contact CRYO on-call and inform SCL on-call, Cryomodule bath pressure too high (check the other gauge PT002). Close supply valve CV01, CV02 if necessary</details>
</guidance>
</pv>
<pv name="Spk-100Crm:Cryo-PT-003:Cable_Error">
<description>Cavity tanks Pressure Sensor cables are disconnected</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>contact CRYO on-call and inform SCL on-call, Cryomodule pressure cable seems disconnected (value gets stuck), assign PT002 as measuring device on CV04 and CV-090 </details>
</guidance>
</pv>
<pv name="Spk-100Crm:Cryo-PT-002:HIHI">
<description>Cavity tanks pressure is too high (typical value is 31mbar in 2K mode and 1050mbar in 4K mode)</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>contact CRYO on-call and inform SCL on-call,, Cryomodule bath pressure too high (check the other gauge PT003). Close supply valve CV01, CV02 if necessary</details>
</guidance>
</pv>
<pv name="Spk-100Crm:Cryo-PT-002:Cable_Error">
<description>Cavity tanks Pressure Sensor cables are disconnected</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>contact CRYO on-call and inform SCL on-call, Cryomodule pressure cable seems disconnected (value gets stuck), assign PT003 as measuring device on CV04 and CV-090 </details>
</guidance>
</pv>
<pv name="Spk-100Crm:Cryo-TT-120:P_Limit_LO">
<description>Power coupler flange temperature low</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>contact CRYO on-call and inform SCL on-call, power coupler flange temperature is low, check heater output, if nominal then coupler flow needs to be adjusted (reduced)</details>
</guidance>
</pv>
<pv name="Spk-100Crm:Cryo-TT-120:P_Limit_LOLO">
<description>Power coupler flange temperature too low</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>contact CRYO on-call and inform SCL on-call, power coupler flange temperature is too low, check heater output, if nominal then coupler flow needs to be adjusted (reduced)</details>
</guidance>
</pv>
<pv name="Spk-100Crm:Cryo-TT-120:P_Limit_HIHI">
<description>Power coupler flange temperature too high</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>contact CRYO on-call and inform SCL on-call, power coupler flange temperature is too high, check heater output, if nominal then coupler flow needs to be adjusted (reduced)</details>
</guidance>
</pv>
<pv name="Spk-100Crm:Cryo-TT-220:P_Limit_LO">
<description>Power coupler flange temperature low</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>contact CRYO on-call and inform SCL on-call, power coupler flange temperature is low, check heater output, if nominal then coupler flow needs to be adjusted (reduced)</details>
</guidance>
</pv>
<pv name="Spk-100Crm:Cryo-TT-220:P_Limit_LOLO">
<description>Power coupler flange temperature too low</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>contact CRYO on-call and inform SCL on-call, power coupler flange temperature is too low, check heater output, if nominal then coupler flow needs to be adjusted (reduced)</details>
</guidance>
</pv>
<pv name="Spk-100Crm:Cryo-TT-220:P_Limit_HIHI">
<description>Power coupler flange temperature too high</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>contact CRYO on-call and inform SCL on-call, power coupler flange temperature is too high, check heater output, if nominal then coupler flow needs to be adjusted (reduced)</details>
</guidance>
</pv>
<pv name="Spk-100Crm:WtrC-FS-013:Flow_OK_WF">
<description>! Alarm when signal drops from 1 to zero. No Water Flow Antenna 1</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>contact CRYO on-call and inform SCL on-call, assure Flange temperature TT-120 is correct. Risk of Water freeze if no flow and temperature too low</details>
</guidance>
</pv>
<pv name="Spk-100Crm:WtrC-FS-014:Flow_OK_WF">
<description>! Alarm when signal drops from 1 to zero. No Water Flow Window 1</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>contact CRYO on-call and inform SCL on-call, assure Flange temperature TT-120 is correct. Risk of Water freeze if no flow and temperature too low</details>
</guidance>
</pv>
<pv name="Spk-100Crm:WtrC-FS-023:Flow_OK_WF">
<description>! Alarm when signal drops from 1 to zero. No Water Flow Antenna 2</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>contact CRYO on-call and inform SCL on-call, assure Flange temperature TT-120 is correct. Risk of Water freeze if no flow and temperature too low</details>
</guidance>
</pv>
<pv name="Spk-100Crm:WtrC-FS-024:Flow_OK_WF">
<description>! Alarm when signal drops from 1 to zero. No Water Flow Window 2</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>contact CRYO on-call and inform SCL on-call, assure Flange temperature TT-120 is correct. Risk of Water freeze if no flow and temperature too low</details>
</guidance>
</pv>
</component>
<component name="Cryomodules\SPK-110 Cryomodule">
<pv name="Spk-110Crm:Cryo-LT-001:HIHI">
<description>LT-001 helium level extremely high</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>contact CRYO on-call and inform SCL on-call, Cryomodule liquid level too high (check the other gauge LT-002). Close supply valve CV01, CV02</details>
</guidance>
</pv>
<pv name="Spk-110Crm:Cryo-LT-002:HIHI">
<description>LT-002 helium level extremely high</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>contact CRYO on-call and inform SCL on-call, Cryomodule liquid level too high (check the other gauge LT-001). Close supply valve CV01, CV02</details>
</guidance>
</pv>
<pv name="Spk-110Crm:Cryo-LT-001:HI">
<description>LT-001 helium level high</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>contact CRYO on-call and inform SCL on-call, Cryomodule liquid level high (check the other gauge LT-002). Check level regulation valve settings, if needed: adjust LMN_LO and if necessary: Close supply valve CV01, CV02</details>
</guidance>
</pv>
<pv name="Spk-110Crm:Cryo-LT-002:HI">
<description>LT-002 helium level high</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>contact CRYO on-call and inform SCL on-call, Cryomodule liquid level high (check the other gauge LT-002). Check level regulation valve settings, if needed: adjust LMN_LO and if necessary: Close supply valve CV01, CV02</details>
</guidance>
</pv>
<pv name="Spk-110Crm:Cryo-LT-001:LO">
<description>LT-001 helium level low</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>contact CRYO on-call and inform SCL on-call, Cryomodule liquid level low (check the other gauge LT-001). Check level regulation valve settings, if needed: adjust LMN_HI</details>
</guidance>
</pv>
<pv name="Spk-110Crm:Cryo-LT-002:LO">
<description>LT-002 helium level low</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>contact CRYO on-call and inform SCL on-call, Cryomodule liquid level low (check the other gauge LT-002). Check level regulation valvesettings, if needed: adjust LMN_HI</details>
</guidance>
</pv>
<pv name="Spk-110Crm:Cryo-LT-001:LOLO">
<description>LT-002 helium level extremely low</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>contact CRYO on-call and inform SCL on-call, Cryomodule liquid level too low (check the other gauge LT-001). Check level regulation valve settings, if needed: adjust LMN_HI</details>
</guidance>
</pv>
<pv name="Spk-110Crm:Cryo-LT-002:LOLO">
<description>LT-002 helium level extremely low</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>contact CRYO on-call and inform SCL on-call, Cryomodule liquid level too low (check the other gauge LT-002). Check level regulation valvesettings, if needed: adjust LMN_HI</details>
</guidance>
</pv>
<pv name="Spk-110Crm:Cryo-PT-003:HIHI">
<description>Cavity tanks pressure is too high (typical value is 31mbar in 2K mode and 1050mbar in 4K mode)</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>contact CRYO on-call and inform SCL on-call, Cryomodule bath pressure too high (check the other gauge PT002). Close supply valve CV01, CV02 if necessary</details>
</guidance>
</pv>
<pv name="Spk-110Crm:Cryo-PT-003:Cable_Error">
<description>Cavity tanks Pressure Sensor cables are disconnected</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>contact CRYO on-call and inform SCL on-call, Cryomodule pressure cable seems disconnected (value gets stuck), assign PT002 as measuring device on CV04 and CV-090 </details>
</guidance>
</pv>
<pv name="Spk-110Crm:Cryo-PT-002:HIHI">
<description>Cavity tanks pressure is too high (typical value is 31mbar in 2K mode and 1050mbar in 4K mode)</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>contact CRYO on-call and inform SCL on-call,, Cryomodule bath pressure too high (check the other gauge PT003). Close supply valve CV01, CV02 if necessary</details>
</guidance>
</pv>
<pv name="Spk-110Crm:Cryo-PT-002:Cable_Error">
<description>Cavity tanks Pressure Sensor cables are disconnected</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>contact CRYO on-call and inform SCL on-call, Cryomodule pressure cable seems disconnected (value gets stuck), assign PT003 as measuring device on CV04 and CV-090 </details>
</guidance>
</pv>
<pv name="Spk-110Crm:Cryo-TT-120:P_Limit_LO">
<description>Power coupler flange temperature low</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>contact CRYO on-call and inform SCL on-call, power coupler flange temperature is low, check heater output, if nominal then coupler flow needs to be adjusted (reduced)</details>
</guidance>
</pv>
<pv name="Spk-110Crm:Cryo-TT-120:P_Limit_LOLO">
<description>Power coupler flange temperature too low</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>contact CRYO on-call and inform SCL on-call, power coupler flange temperature is too low, check heater output, if nominal then coupler flow needs to be adjusted (reduced)</details>
</guidance>
</pv>
<pv name="Spk-110Crm:Cryo-TT-120:P_Limit_HIHI">
<description>Power coupler flange temperature too high</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>contact CRYO on-call and inform SCL on-call, power coupler flange temperature is too high, check heater output, if nominal then coupler flow needs to be adjusted (reduced)</details>
</guidance>
</pv>
<pv name="Spk-110Crm:Cryo-TT-220:P_Limit_LO">
<description>Power coupler flange temperature low</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>contact CRYO on-call and inform SCL on-call, power coupler flange temperature is low, check heater output, if nominal then coupler flow needs to be adjusted (reduced)</details>
</guidance>
</pv>
<pv name="Spk-110Crm:Cryo-TT-220:P_Limit_LOLO">
<description>Power coupler flange temperature too low</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>contact CRYO on-call and inform SCL on-call, power coupler flange temperature is too low, check heater output, if nominal then coupler flow needs to be adjusted (reduced)</details>
</guidance>
</pv>
<pv name="Spk-110Crm:Cryo-TT-220:P_Limit_HIHI">
<description>Power coupler flange temperature too high</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>contact CRYO on-call and inform SCL on-call, power coupler flange temperature is too high, check heater output, if nominal then coupler flow needs to be adjusted (reduced)</details>
</guidance>
</pv>
<pv name="Spk-110Crm:WtrC-FS-013:Flow_OK_WF">
<description>! Alarm when signal drops from 1 to zero. No Water Flow Antenna 1</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>contact CRYO on-call and inform SCL on-call, assure Flange temperature TT-120 is correct. Risk of Water freeze if no flow and temperature too low</details>
</guidance>
</pv>
<pv name="Spk-110Crm:WtrC-FS-014:Flow_OK_WF">
<description>! Alarm when signal drops from 1 to zero. No Water Flow Window 1</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>contact CRYO on-call and inform SCL on-call, assure Flange temperature TT-120 is correct. Risk of Water freeze if no flow and temperature too low</details>
</guidance>
</pv>
<pv name="Spk-110Crm:WtrC-FS-023:Flow_OK_WF">
<description>! Alarm when signal drops from 1 to zero. No Water Flow Antenna 2</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>contact CRYO on-call and inform SCL on-call, assure Flange temperature TT-120 is correct. Risk of Water freeze if no flow and temperature too low</details>
</guidance>
</pv>
<pv name="Spk-110Crm:WtrC-FS-024:Flow_OK_WF">
<description>! Alarm when signal drops from 1 to zero. No Water Flow Window 2</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>contact CRYO on-call and inform SCL on-call, assure Flange temperature TT-120 is correct. Risk of Water freeze if no flow and temperature too low</details>
</guidance>
</pv>
</component>
<component name="Cryomodules\SPK-120 Cryomodule">
<pv name="Spk-120Crm:Cryo-LT-001:HIHI">
<description>LT-001 helium level extremely high</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>contact CRYO on-call and inform SCL on-call, Cryomodule liquid level too high (check the other gauge LT-002). Close supply valve CV01, CV02</details>
</guidance>
</pv>
<pv name="Spk-120Crm:Cryo-LT-002:HIHI">
<description>LT-002 helium level extremely high</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>contact CRYO on-call and inform SCL on-call, Cryomodule liquid level too high (check the other gauge LT-001). Close supply valve CV01, CV02</details>
</guidance>
</pv>
<pv name="Spk-120Crm:Cryo-LT-001:HI">
<description>LT-001 helium level high</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>contact CRYO on-call and inform SCL on-call, Cryomodule liquid level high (check the other gauge LT-002). Check level regulation valve settings, if needed: adjust LMN_LO and if necessary: Close supply valve CV01, CV02</details>
</guidance>
</pv>
<pv name="Spk-120Crm:Cryo-LT-002:HI">
<description>LT-002 helium level high</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>contact CRYO on-call and inform SCL on-call, Cryomodule liquid level high (check the other gauge LT-002). Check level regulation valve settings, if needed: adjust LMN_LO and if necessary: Close supply valve CV01, CV02</details>
</guidance>
</pv>
<pv name="Spk-120Crm:Cryo-LT-001:LO">
<description>LT-001 helium level low</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>contact CRYO on-call and inform SCL on-call, Cryomodule liquid level low (check the other gauge LT-001). Check level regulation valve settings, if needed: adjust LMN_HI</details>
</guidance>
</pv>
<pv name="Spk-120Crm:Cryo-LT-002:LO">
<description>LT-002 helium level low</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>contact CRYO on-call and inform SCL on-call, Cryomodule liquid level low (check the other gauge LT-002). Check level regulation valvesettings, if needed: adjust LMN_HI</details>
</guidance>
</pv>
<pv name="Spk-120Crm:Cryo-LT-001:LOLO">
<description>LT-002 helium level extremely low</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>contact CRYO on-call and inform SCL on-call, Cryomodule liquid level too low (check the other gauge LT-001). Check level regulation valve settings, if needed: adjust LMN_HI</details>
</guidance>
</pv>
<pv name="Spk-120Crm:Cryo-LT-002:LOLO">
<description>LT-002 helium level extremely low</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>contact CRYO on-call and inform SCL on-call, Cryomodule liquid level too low (check the other gauge LT-002). Check level regulation valvesettings, if needed: adjust LMN_HI</details>
</guidance>
</pv>
<pv name="Spk-120Crm:Cryo-PT-003:HIHI">
<description>Cavity tanks pressure is too high (typical value is 31mbar in 2K mode and 1050mbar in 4K mode)</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>contact CRYO on-call and inform SCL on-call, Cryomodule bath pressure too high (check the other gauge PT002). Close supply valve CV01, CV02 if necessary</details>
</guidance>
</pv>
<pv name="Spk-120Crm:Cryo-PT-003:Cable_Error">
<description>Cavity tanks Pressure Sensor cables are disconnected</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>contact CRYO on-call and inform SCL on-call, Cryomodule pressure cable seems disconnected (value gets stuck), assign PT002 as measuring device on CV04 and CV-090 </details>
</guidance>
</pv>
<pv name="Spk-120Crm:Cryo-PT-002:HIHI">
<description>Cavity tanks pressure is too high (typical value is 31mbar in 2K mode and 1050mbar in 4K mode)</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>contact CRYO on-call and inform SCL on-call,, Cryomodule bath pressure too high (check the other gauge PT003). Close supply valve CV01, CV02 if necessary</details>
</guidance>
</pv>
<pv name="Spk-120Crm:Cryo-PT-002:Cable_Error">
<description>Cavity tanks Pressure Sensor cables are disconnected</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>contact CRYO on-call and inform SCL on-call, Cryomodule pressure cable seems disconnected (value gets stuck), assign PT003 as measuring device on CV04 and CV-090 </details>
</guidance>
</pv>
<pv name="Spk-120Crm:Cryo-TT-120:P_Limit_LO">
<description>Power coupler flange temperature low</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>contact CRYO on-call and inform SCL on-call, power coupler flange temperature is low, check heater output, if nominal then coupler flow needs to be adjusted (reduced)</details>
</guidance>
</pv>
<pv name="Spk-120Crm:Cryo-TT-120:P_Limit_LOLO">
<description>Power coupler flange temperature too low</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>contact CRYO on-call and inform SCL on-call, power coupler flange temperature is too low, check heater output, if nominal then coupler flow needs to be adjusted (reduced)</details>
</guidance>
</pv>
<pv name="Spk-120Crm:Cryo-TT-120:P_Limit_HIHI">
<description>Power coupler flange temperature too high</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>contact CRYO on-call and inform SCL on-call, power coupler flange temperature is too high, check heater output, if nominal then coupler flow needs to be adjusted (reduced)</details>
</guidance>
</pv>
<pv name="Spk-120Crm:Cryo-TT-220:P_Limit_LO">
<description>Power coupler flange temperature low</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>contact CRYO on-call and inform SCL on-call, power coupler flange temperature is low, check heater output, if nominal then coupler flow needs to be adjusted (reduced)</details>
</guidance>
</pv>
<pv name="Spk-120Crm:Cryo-TT-220:P_Limit_LOLO">
<description>Power coupler flange temperature too low</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>contact CRYO on-call and inform SCL on-call, power coupler flange temperature is too low, check heater output, if nominal then coupler flow needs to be adjusted (reduced)</details>
</guidance>
</pv>
<pv name="Spk-120Crm:Cryo-TT-220:P_Limit_HIHI">
<description>Power coupler flange temperature too high</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>contact CRYO on-call and inform SCL on-call, power coupler flange temperature is too high, check heater output, if nominal then coupler flow needs to be adjusted (reduced)</details>
</guidance>
</pv>
<pv name="Spk-120Crm:WtrC-FS-013:Flow_OK_WF">
<description>! Alarm when signal drops from 1 to zero. No Water Flow Antenna 1</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>contact CRYO on-call and inform SCL on-call, assure Flange temperature TT-120 is correct. Risk of Water freeze if no flow and temperature too low</details>
</guidance>
</pv>
<pv name="Spk-120Crm:WtrC-FS-014:Flow_OK_WF">
<description>! Alarm when signal drops from 1 to zero. No Water Flow Window 1</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>contact CRYO on-call and inform SCL on-call, assure Flange temperature TT-120 is correct. Risk of Water freeze if no flow and temperature too low</details>
</guidance>
</pv>
<pv name="Spk-120Crm:WtrC-FS-023:Flow_OK_WF">
<description>! Alarm when signal drops from 1 to zero. No Water Flow Antenna 2</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>contact CRYO on-call and inform SCL on-call, assure Flange temperature TT-120 is correct. Risk of Water freeze if no flow and temperature too low</details>
</guidance>
</pv>
<pv name="Spk-120Crm:WtrC-FS-024:Flow_OK_WF">
<description>! Alarm when signal drops from 1 to zero. No Water Flow Window 2</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>contact CRYO on-call and inform SCL on-call, assure Flange temperature TT-120 is correct. Risk of Water freeze if no flow and temperature too low</details>
</guidance>
</pv>
</component>
<component name="Cryomodules\SPK-130 Cryomodule">
<pv name="Spk-130Crm:Cryo-LT-001:HIHI">
<description>LT-001 helium level extremely high</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>contact CRYO on-call and inform SCL on-call, Cryomodule liquid level too high (check the other gauge LT-002). Close supply valve CV01, CV02</details>
</guidance>
</pv>
<pv name="Spk-130Crm:Cryo-LT-002:HIHI">
<description>LT-002 helium level extremely high</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>contact CRYO on-call and inform SCL on-call, Cryomodule liquid level too high (check the other gauge LT-001). Close supply valve CV01, CV02</details>
</guidance>
</pv>
<pv name="Spk-130Crm:Cryo-LT-001:HI">
<description>LT-001 helium level high</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>contact CRYO on-call and inform SCL on-call, Cryomodule liquid level high (check the other gauge LT-002). Check level regulation valve settings, if needed: adjust LMN_LO and if necessary: Close supply valve CV01, CV02</details>
</guidance>
</pv>
<pv name="Spk-130Crm:Cryo-LT-002:HI">
<description>LT-002 helium level high</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>contact CRYO on-call and inform SCL on-call, Cryomodule liquid level high (check the other gauge LT-002). Check level regulation valve settings, if needed: adjust LMN_LO and if necessary: Close supply valve CV01, CV02</details>
</guidance>
</pv>
<pv name="Spk-130Crm:Cryo-LT-001:LO">
<description>LT-001 helium level low</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>contact CRYO on-call and inform SCL on-call, Cryomodule liquid level low (check the other gauge LT-001). Check level regulation valve settings, if needed: adjust LMN_HI</details>
</guidance>
</pv>
<pv name="Spk-130Crm:Cryo-LT-002:LO">
<description>LT-002 helium level low</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>contact CRYO on-call and inform SCL on-call, Cryomodule liquid level low (check the other gauge LT-002). Check level regulation valvesettings, if needed: adjust LMN_HI</details>
</guidance>
</pv>
<pv name="Spk-130Crm:Cryo-LT-001:LOLO">
<description>LT-002 helium level extremely low</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>contact CRYO on-call and inform SCL on-call, Cryomodule liquid level too low (check the other gauge LT-001). Check level regulation valve settings, if needed: adjust LMN_HI</details>
</guidance>
</pv>
<pv name="Spk-130Crm:Cryo-LT-002:LOLO">
<description>LT-002 helium level extremely low</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>contact CRYO on-call and inform SCL on-call, Cryomodule liquid level too low (check the other gauge LT-002). Check level regulation valvesettings, if needed: adjust LMN_HI</details>
</guidance>
</pv>
<pv name="Spk-130Crm:Cryo-PT-003:HIHI">
<description>Cavity tanks pressure is too high (typical value is 31mbar in 2K mode and 1050mbar in 4K mode)</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>contact CRYO on-call and inform SCL on-call, Cryomodule bath pressure too high (check the other gauge PT002). Close supply valve CV01, CV02 if necessary</details>
</guidance>
</pv>
<pv name="Spk-130Crm:Cryo-PT-003:Cable_Error">
<description>Cavity tanks Pressure Sensor cables are disconnected</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>contact CRYO on-call and inform SCL on-call, Cryomodule pressure cable seems disconnected (value gets stuck), assign PT002 as measuring device on CV04 and CV-090 </details>
</guidance>
</pv>
<pv name="Spk-130Crm:Cryo-PT-002:HIHI">
<description>Cavity tanks pressure is too high (typical value is 31mbar in 2K mode and 1050mbar in 4K mode)</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>contact CRYO on-call and inform SCL on-call,, Cryomodule bath pressure too high (check the other gauge PT003). Close supply valve CV01, CV02 if necessary</details>
</guidance>
</pv>
<pv name="Spk-130Crm:Cryo-PT-002:Cable_Error">
<description>Cavity tanks Pressure Sensor cables are disconnected</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>contact CRYO on-call and inform SCL on-call, Cryomodule pressure cable seems disconnected (value gets stuck), assign PT003 as measuring device on CV04 and CV-090 </details>
</guidance>
</pv>
<pv name="Spk-130Crm:Cryo-TT-120:P_Limit_LO">
<description>Power coupler flange temperature low</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>contact CRYO on-call and inform SCL on-call, power coupler flange temperature is low, check heater output, if nominal then coupler flow needs to be adjusted (reduced)</details>
</guidance>
</pv>
<pv name="Spk-130Crm:Cryo-TT-120:P_Limit_LOLO">
<description>Power coupler flange temperature too low</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>contact CRYO on-call and inform SCL on-call, power coupler flange temperature is too low, check heater output, if nominal then coupler flow needs to be adjusted (reduced)</details>
</guidance>
</pv>
<pv name="Spk-130Crm:Cryo-TT-120:P_Limit_HIHI">
<description>Power coupler flange temperature too high</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>contact CRYO on-call and inform SCL on-call, power coupler flange temperature is too high, check heater output, if nominal then coupler flow needs to be adjusted (increased)</details>
</guidance>
</pv>
<pv name="Spk-130Crm:Cryo-TT-220:P_Limit_LO">
<description>Power coupler flange temperature low</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>contact CRYO on-call and inform SCL on-call, power coupler flange temperature is low, check heater output, if nominal then coupler flow needs to be adjusted (reduced)</details>
</guidance>
</pv>
<pv name="Spk-130Crm:Cryo-TT-220:P_Limit_LOLO">
<description>Power coupler flange temperature too low</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>contact CRYO on-call and inform SCL on-call, power coupler flange temperature is too low, check heater output, if nominal then coupler flow needs to be adjusted (reduced)</details>
</guidance>
</pv>
<pv name="Spk-130Crm:Cryo-TT-220:P_Limit_HIHI">
<description>Power coupler flange temperature too high</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>contact CRYO on-call and inform SCL on-call, power coupler flange temperature is too high, check heater output, if nominal then coupler flow needs to be adjusted (increased)</details>
</guidance>
</pv>
<pv name="Spk-130Crm:WtrC-FS-013:Flow_OK_WF">
<description>! Alarm when signal drops from 1 to zero. No Water Flow Antenna 1</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>contact CRYO on-call and inform SCL on-call, assure Flange temperature TT-120 is correct. Risk of Water freeze if no flow and temperature too low</details>
</guidance>
</pv>
<pv name="Spk-130Crm:WtrC-FS-014:Flow_OK_WF">
<description>! Alarm when signal drops from 1 to zero. No Water Flow Window 1</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>contact CRYO on-call and inform SCL on-call, assure Flange temperature TT-120 is correct. Risk of Water freeze if no flow and temperature too low</details>
</guidance>
</pv>
<pv name="Spk-130Crm:WtrC-FS-023:Flow_OK_WF">
<description>! Alarm when signal drops from 1 to zero. No Water Flow Antenna 2</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>contact CRYO on-call and inform SCL on-call, assure Flange temperature TT-120 is correct. Risk of Water freeze if no flow and temperature too low</details>
</guidance>
</pv>
<pv name="Spk-130Crm:WtrC-FS-024:Flow_OK_WF">
<description>! Alarm when signal drops from 1 to zero. No Water Flow Window 2</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>contact CRYO on-call and inform SCL on-call, assure Flange temperature TT-120 is correct. Risk of Water freeze if no flow and temperature too low</details>
</guidance>
</pv>
</component>
<component name="Cryomodules\MBL-010 Cryomodule">
<pv name="MBL-010Crm:Cryo-LT-001:HIHI">
<description>LT-001 helium level extremely high</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>contact CRYO on-call and inform SCL on-call, Cryomodule liquid level too high (check the other gauge LT-002). Close supply valve CV01, CV02</details>
</guidance>
</pv>
<pv name="MBL-010Crm:Cryo-LT-002:HIHI">
<description>LT-002 helium level extremely high</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>contact CRYO on-call and inform SCL on-call, Cryomodule liquid level too high (check the other gauge LT-001). Close supply valve CV01, CV02</details>
</guidance>
</pv>
<pv name="MBL-010Crm:Cryo-LT-001:HI">
<description>LT-001 helium level high</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>contact CRYO on-call and inform SCL on-call, Cryomodule liquid level high (check the other gauge LT-002). Check level regulation valve settings, if needed: adjust LMN_LO and if necessary: Close supply valve CV01, CV02</details>
</guidance>
</pv>
<pv name="MBL-010Crm:Cryo-LT-002:HI">
<description>LT-002 helium level high</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>contact CRYO on-call and inform SCL on-call, Cryomodule liquid level high (check the other gauge LT-002). Check level regulation valve settings, if needed: adjust LMN_LO and if necessary: Close supply valve CV01, CV02</details>
</guidance>
</pv>
<pv name="MBL-010Crm:Cryo-LT-001:LO">
<description>LT-001 helium level low</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>contact CRYO on-call and inform SCL on-call, Cryomodule liquid level low (check the other gauge LT-001). Check level regulation valve settings, if needed: adjust LMN_HI</details>
</guidance>
</pv>
<pv name="MBL-010Crm:Cryo-LT-002:LO">
<description>LT-002 helium level low</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>contact CRYO on-call and inform SCL on-call, Cryomodule liquid level low (check the other gauge LT-002). Check level regulation valvesettings, if needed: adjust LMN_HI</details>
</guidance>
</pv>
<pv name="MBL-010Crm:Cryo-LT-001:LOLO">
<description>LT-002 helium level extremely low</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>contact CRYO on-call and inform SCL on-call, Cryomodule liquid level too low (check the other gauge LT-001). Check level regulation valve settings, if needed: adjust LMN_HI</details>
</guidance>
</pv>
<pv name="MBL-010Crm:Cryo-LT-002:LOLO">
<description>LT-002 helium level extremely low</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>contact CRYO on-call and inform SCL on-call, Cryomodule liquid level too low (check the other gauge LT-002). Check level regulation valvesettings, if needed: adjust LMN_HI</details>
</guidance>
</pv>
<pv name="MBL-010Crm:Cryo-PT-003:HIHI">
<description>Cavity tanks pressure is too high (typical value is 31mbar in 2K mode and 1050mbar in 4K mode)</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>contact CRYO on-call and inform SCL on-call, Cryomodule bath pressure too high (check the other gauge PT002). Close supply valve CV01, CV02 if necessary</details>
</guidance>
</pv>
<pv name="MBL-010Crm:Cryo-PT-003:Cable_Error">
<description>Cavity tanks Pressure Sensor cables are disconnected</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>contact CRYO on-call and inform SCL on-call, Cryomodule pressure cable seems disconnected (value gets stuck), assign PT002 as measuring device on CV04 and CV-090 </details>
</guidance>
</pv>
<pv name="MBL-010Crm:Cryo-PT-004:HIHI">
<description>Cavity tanks pressure is too high (typical value is 31mbar in 2K mode and 1050mbar in 4K mode)</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>contact CRYO on-call and inform SCL on-call,, Cryomodule bath pressure too high (check the other gauge PT003). Close supply valve CV01, CV02 if necessary</details>
</guidance>
</pv>
<pv name="MBL-010Crm:Cryo-PT-004:Cable_Error">
<description>Cavity tanks Pressure Sensor cables are disconnected</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>contact CRYO on-call and inform SCL on-call, Cryomodule pressure cable seems disconnected (value gets stuck), assign PT003 as measuring device on CV04 and CV-090 </details>
</guidance>
</pv>
<pv name="MBL-010Crm:Cryo-TT-014:P_Limit_HIHI">
<description>Power coupler flange temperature too high</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>contact CRYO on-call and inform SCL on-call, power coupler flange temperature is too high, check heater output, if nominal then coupler flow needs to be adjusted (increased)</details>
</guidance>
</pv>
<pv name="MBL-010Crm:Cryo-TT-014:P_Limit_LO">
<description>Power coupler flange temperature too low</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>contact CRYO on-call and inform SCL on-call, power coupler flange temperature is too low, check heater output, if nominal then coupler flow needs to be adjusted (reduced)</details>
</guidance>
</pv>
<pv name="MBL-010Crm:Cryo-TT-014:P_Limit_LOLO">
<description>Power coupler flange temperature too low</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>contact CRYO on-call and inform SCL on-call, power coupler flange temperature is too low, check heater output, if nominal then coupler flow needs to be adjusted (reduced)</details>
</guidance>
</pv>
<pv name="MBL-010Crm:Cryo-TT-024:P_Limit_HIHI">
<description>Power coupler flange temperature low</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>contact CRYO on-call and inform SCL on-call, power coupler flange temperature is too high, check heater output, if nominal then coupler flow needs to be adjusted (increased)</details>
</guidance>
</pv>
<pv name="MBL-010Crm:Cryo-TT-024:P_Limit_LO">
<description>Power coupler flange temperature too low</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>contact CRYO on-call and inform SCL on-call, power coupler flange temperature is too low, check heater output, if nominal then coupler flow needs to be adjusted (reduced)</details>
</guidance>
</pv>
<pv name="MBL-010Crm:Cryo-TT-024:P_Limit_LOLO">
<description>Power coupler flange temperature too high</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>contact CRYO on-call and inform SCL on-call, power coupler flange temperature is too low, check heater output, if nominal then coupler flow needs to be adjusted (reduced)</details>
</guidance>
</pv>
<pv name="MBL-010Crm:Cryo-TT-034:P_Limit_HIHI">
<description>Power coupler flange temperature low</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>contact CRYO on-call and inform SCL on-call, power coupler flange temperature is too high, check heater output, if nominal then coupler flow needs to be adjusted (increased)</details>
</guidance>
</pv>
<pv name="MBL-010Crm:Cryo-TT-034:P_Limit_LO">
<description>Power coupler flange temperature too low</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>contact CRYO on-call and inform SCL on-call, power coupler flange temperature is too low, check heater output, if nominal then coupler flow needs to be adjusted (reduced)</details>
</guidance>
</pv>
<pv name="MBL-010Crm:Cryo-TT-034:P_Limit_LOLO">
<description>Power coupler flange temperature too high</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>contact CRYO on-call and inform SCL on-call, power coupler flange temperature is too low, check heater output, if nominal then coupler flow needs to be adjusted (reduced)</details>
</guidance>
</pv>
<pv name="MBL-010Crm:Cryo-TT-044:P_Limit_HIHI">
<description>Power coupler flange temperature low</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>contact CRYO on-call and inform SCL on-call, power coupler flange temperature is too high, check heater output, if nominal then coupler flow needs to be adjusted (increased)</details>
</guidance>
</pv>
<pv name="MBL-010Crm:Cryo-TT-044:P_Limit_LO">
<description>Power coupler flange temperature too low</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>contact CRYO on-call and inform SCL on-call, power coupler flange temperature is too low, check heater output, if nominal then coupler flow needs to be adjusted (reduced)</details>
</guidance>
</pv>
<pv name="MBL-010Crm:Cryo-TT-043:P_Limit_LOLO">
<description>Power coupler flange temperature too high</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>contact CRYO on-call and inform SCL on-call, power coupler flange temperature is too low, check heater output, if nominal then coupler flow needs to be adjusted (reduced)</details>
</guidance>
</pv>
<pv name="MBL-010Crm:WtrC-FS-012:Flow_OK_WF">
<description>! Alarm when signal drops from 1 to zero. No Water Flow Antenna 1</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>contact CRYO on-call and inform SCL on-call, assure Flange temperature TT-014 is correct. Risk of Water freeze if no flow and temperature too low</details>
</guidance>
</pv>
<pv name="MBL-010Crm:WtrC-FS-022:Flow_OK_WF">
<description>! Alarm when signal drops from 1 to zero. No Water Flow Antenna 2</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>contact CRYO on-call and inform SCL on-call, assure Flange temperature TT-024 is correct. Risk of Water freeze if no flow and temperature too low</details>
</guidance>
</pv>
<pv name="MBL-010Crm:WtrC-FS-032:Flow_OK_WF">
<description>! Alarm when signal drops from 1 to zero. No Water Flow Antenna 3</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>contact CRYO on-call and inform SCL on-call, assure Flange temperature TT-034 is correct. Risk of Water freeze if no flow and temperature too low</details>
</guidance>
</pv>
<pv name="MBL-010Crm:WtrC-FS-042:Flow_OK_WF">
<description>! Alarm when signal drops from 1 to zero. No Water Flow Antenna 4</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>contact CRYO on-call and inform SCL on-call, assure Flange temperature TT-044 is correct. Risk of Water freeze if no flow and temperature too low</details>
</guidance>
</pv>
</component>
<component name="Cryomodules\MBL-020 Cryomodule">
<pv name="MBL-020Crm:Cryo-LT-001:HIHI">
<description>LT-001 helium level extremely high</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>contact CRYO on-call and inform SCL on-call, Cryomodule liquid level too high (check the other gauge LT-002). Close supply valve CV01, CV02</details>
</guidance>
</pv>
<pv name="MBL-020Crm:Cryo-LT-002:HIHI">
<description>LT-002 helium level extremely high</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>contact CRYO on-call and inform SCL on-call, Cryomodule liquid level too high (check the other gauge LT-001). Close supply valve CV01, CV02</details>
</guidance>
</pv>
<pv name="MBL-020Crm:Cryo-LT-001:HI">
<description>LT-001 helium level high</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>contact CRYO on-call and inform SCL on-call, Cryomodule liquid level high (check the other gauge LT-002). Check level regulation valve settings, if needed: adjust LMN_LO and if necessary: Close supply valve CV01, CV02</details>
</guidance>
</pv>
<pv name="MBL-020Crm:Cryo-LT-002:HI">
<description>LT-002 helium level high</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>contact CRYO on-call and inform SCL on-call, Cryomodule liquid level high (check the other gauge LT-002). Check level regulation valve settings, if needed: adjust LMN_LO and if necessary: Close supply valve CV01, CV02</details>
</guidance>
</pv>
<pv name="MBL-020Crm:Cryo-LT-001:LO">
<description>LT-001 helium level low</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>contact CRYO on-call and inform SCL on-call, Cryomodule liquid level low (check the other gauge LT-001). Check level regulation valve settings, if needed: adjust LMN_HI</details>
</guidance>
</pv>
<pv name="MBL-020Crm:Cryo-LT-002:LO">
<description>LT-002 helium level low</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>contact CRYO on-call and inform SCL on-call, Cryomodule liquid level low (check the other gauge LT-002). Check level regulation valvesettings, if needed: adjust LMN_HI</details>
</guidance>
</pv>
<pv name="MBL-020Crm:Cryo-LT-001:LOLO">
<description>LT-002 helium level extremely low</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>contact CRYO on-call and inform SCL on-call, Cryomodule liquid level too low (check the other gauge LT-001). Check level regulation valve settings, if needed: adjust LMN_HI</details>
</guidance>
</pv>
<pv name="MBL-020Crm:Cryo-LT-002:LOLO">
<description>LT-002 helium level extremely low</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>contact CRYO on-call and inform SCL on-call, Cryomodule liquid level too low (check the other gauge LT-002). Check level regulation valvesettings, if needed: adjust LMN_HI</details>
</guidance>
</pv>
<pv name="MBL-020Crm:Cryo-PT-003:HIHI">
<description>Cavity tanks pressure is too high (typical value is 31mbar in 2K mode and 1050mbar in 4K mode)</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>contact CRYO on-call and inform SCL on-call, Cryomodule bath pressure too high (check the other gauge PT002). Close supply valve CV01, CV02 if necessary</details>
</guidance>
</pv>
<pv name="MBL-020Crm:Cryo-PT-003:Cable_Error">
<description>Cavity tanks Pressure Sensor cables are disconnected</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>contact CRYO on-call and inform SCL on-call, Cryomodule pressure cable seems disconnected (value gets stuck), assign PT002 as measuring device on CV04 and CV-090 </details>
</guidance>
</pv>
<pv name="MBL-020Crm:Cryo-PT-004:HIHI">
<description>Cavity tanks pressure is too high (typical value is 31mbar in 2K mode and 1050mbar in 4K mode)</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>contact CRYO on-call and inform SCL on-call,, Cryomodule bath pressure too high (check the other gauge PT003). Close supply valve CV01, CV02 if necessary</details>
</guidance>
</pv>
<pv name="MBL-020Crm:Cryo-PT-004:Cable_Error">
<description>Cavity tanks Pressure Sensor cables are disconnected</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>contact CRYO on-call and inform SCL on-call, Cryomodule pressure cable seems disconnected (value gets stuck), assign PT003 as measuring device on CV04 and CV-090 </details>
</guidance>
</pv>
<pv name="MBL-020Crm:Cryo-TT-014:P_Limit_HIHI">
<description>Power coupler flange temperature too high</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>contact CRYO on-call and inform SCL on-call, power coupler flange temperature is too high, check heater output, if nominal then coupler flow needs to be adjusted (increased)</details>
</guidance>
</pv>
<pv name="MBL-020Crm:Cryo-TT-014:P_Limit_LO">
<description>Power coupler flange temperature too low</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>contact CRYO on-call and inform SCL on-call, power coupler flange temperature is too low, check heater output, if nominal then coupler flow needs to be adjusted (reduced)</details>
</guidance>
</pv>
<pv name="MBL-020Crm:Cryo-TT-014:P_Limit_LOLO">
<description>Power coupler flange temperature too low</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>contact CRYO on-call and inform SCL on-call, power coupler flange temperature is too low, check heater output, if nominal then coupler flow needs to be adjusted (reduced)</details>
</guidance>
</pv>
<pv name="MBL-020Crm:Cryo-TT-024:P_Limit_HIHI">
<description>Power coupler flange temperature low</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>contact CRYO on-call and inform SCL on-call, power coupler flange temperature is too high, check heater output, if nominal then coupler flow needs to be adjusted (increased)</details>
</guidance>
</pv>
<pv name="MBL-020Crm:Cryo-TT-024:P_Limit_LO">
<description>Power coupler flange temperature too low</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>contact CRYO on-call and inform SCL on-call, power coupler flange temperature is too low, check heater output, if nominal then coupler flow needs to be adjusted (reduced)</details>
</guidance>
</pv>
<pv name="MBL-020Crm:Cryo-TT-024:P_Limit_LOLO">
<description>Power coupler flange temperature too high</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>contact CRYO on-call and inform SCL on-call, power coupler flange temperature is too low, check heater output, if nominal then coupler flow needs to be adjusted (reduced)</details>
</guidance>
</pv>
<pv name="MBL-020Crm:Cryo-TT-034:P_Limit_HIHI">
<description>Power coupler flange temperature low</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>contact CRYO on-call and inform SCL on-call, power coupler flange temperature is too high, check heater output, if nominal then coupler flow needs to be adjusted (increased)</details>
</guidance>
</pv>
<pv name="MBL-020Crm:Cryo-TT-034:P_Limit_LO">
<description>Power coupler flange temperature too low</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>contact CRYO on-call and inform SCL on-call, power coupler flange temperature is too low, check heater output, if nominal then coupler flow needs to be adjusted (reduced)</details>
</guidance>
</pv>
<pv name="MBL-020Crm:Cryo-TT-034:P_Limit_LOLO">
<description>Power coupler flange temperature too high</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>contact CRYO on-call and inform SCL on-call, power coupler flange temperature is too low, check heater output, if nominal then coupler flow needs to be adjusted (reduced)</details>
</guidance>
</pv>
<pv name="MBL-020Crm:Cryo-TT-044:P_Limit_HIHI">
<description>Power coupler flange temperature low</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>contact CRYO on-call and inform SCL on-call, power coupler flange temperature is too high, check heater output, if nominal then coupler flow needs to be adjusted (increased)</details>
</guidance>
</pv>
<pv name="MBL-020Crm:Cryo-TT-044:P_Limit_LO">
<description>Power coupler flange temperature too low</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>contact CRYO on-call and inform SCL on-call, power coupler flange temperature is too low, check heater output, if nominal then coupler flow needs to be adjusted (reduced)</details>
</guidance>
</pv>
<pv name="MBL-020Crm:Cryo-TT-043:P_Limit_LOLO">
<description>Power coupler flange temperature too high</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>contact CRYO on-call and inform SCL on-call, power coupler flange temperature is too low, check heater output, if nominal then coupler flow needs to be adjusted (reduced)</details>
</guidance>
</pv>
<pv name="MBL-020Crm:WtrC-FS-012:Flow_OK_WF">
<description>! Alarm when signal drops from 1 to zero. No Water Flow Antenna 1</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>contact CRYO on-call and inform SCL on-call, assure Flange temperature TT-014 is correct. Risk of Water freeze if no flow and temperature too low</details>
</guidance>
</pv>
<pv name="MBL-020Crm:WtrC-FS-022:Flow_OK_WF">
<description>! Alarm when signal drops from 1 to zero. No Water Flow Antenna 2</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>contact CRYO on-call and inform SCL on-call, assure Flange temperature TT-024 is correct. Risk of Water freeze if no flow and temperature too low</details>
</guidance>
</pv>
<pv name="MBL-020Crm:WtrC-FS-032:Flow_OK_WF">
<description>! Alarm when signal drops from 1 to zero. No Water Flow Antenna 3</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>contact CRYO on-call and inform SCL on-call, assure Flange temperature TT-034 is correct. Risk of Water freeze if no flow and temperature too low</details>
</guidance>
</pv>
<pv name="MBL-020Crm:WtrC-FS-042:Flow_OK_WF">
<description>! Alarm when signal drops from 1 to zero. No Water Flow Antenna 4</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>contact CRYO on-call and inform SCL on-call, assure Flange temperature TT-044 is correct. Risk of Water freeze if no flow and temperature too low</details>
</guidance>
</pv>
</component>
<component name="Cryomodules\MBL-030 Cryomodule">
<pv name="MBL-030Crm:Cryo-LT-001:HIHI">
<description>LT-001 helium level extremely high</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>contact CRYO on-call and inform SCL on-call, Cryomodule liquid level too high (check the other gauge LT-002). Close supply valve CV01, CV02</details>
</guidance>
</pv>
<pv name="MBL-030Crm:Cryo-LT-002:HIHI">
<description>LT-002 helium level extremely high</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>contact CRYO on-call and inform SCL on-call, Cryomodule liquid level too high (check the other gauge LT-001). Close supply valve CV01, CV02</details>
</guidance>
</pv>
<pv name="MBL-030Crm:Cryo-LT-001:HI">
<description>LT-001 helium level high</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>contact CRYO on-call and inform SCL on-call, Cryomodule liquid level high (check the other gauge LT-002). Check level regulation valve settings, if needed: adjust LMN_LO and if necessary: Close supply valve CV01, CV02</details>
</guidance>
</pv>
<pv name="MBL-030Crm:Cryo-LT-002:HI">
<description>LT-002 helium level high</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>contact CRYO on-call and inform SCL on-call, Cryomodule liquid level high (check the other gauge LT-002). Check level regulation valve settings, if needed: adjust LMN_LO and if necessary: Close supply valve CV01, CV02</details>
</guidance>
</pv>
<pv name="MBL-030Crm:Cryo-LT-001:LO">
<description>LT-001 helium level low</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>contact CRYO on-call and inform SCL on-call, Cryomodule liquid level low (check the other gauge LT-001). Check level regulation valve settings, if needed: adjust LMN_HI</details>
</guidance>
</pv>
<pv name="MBL-030Crm:Cryo-LT-002:LO">
<description>LT-002 helium level low</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>contact CRYO on-call and inform SCL on-call, Cryomodule liquid level low (check the other gauge LT-002). Check level regulation valvesettings, if needed: adjust LMN_HI</details>
</guidance>
</pv>
<pv name="MBL-030Crm:Cryo-LT-001:LOLO">
<description>LT-002 helium level extremely low</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>contact CRYO on-call and inform SCL on-call, Cryomodule liquid level too low (check the other gauge LT-001). Check level regulation valve settings, if needed: adjust LMN_HI</details>
</guidance>
</pv>
<pv name="MBL-030Crm:Cryo-LT-002:LOLO">
<description>LT-002 helium level extremely low</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>contact CRYO on-call and inform SCL on-call, Cryomodule liquid level too low (check the other gauge LT-002). Check level regulation valvesettings, if needed: adjust LMN_HI</details>
</guidance>
</pv>
<pv name="MBL-030Crm:Cryo-PT-003:HIHI">
<description>Cavity tanks pressure is too high (typical value is 31mbar in 2K mode and 1050mbar in 4K mode)</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>contact CRYO on-call and inform SCL on-call, Cryomodule bath pressure too high (check the other gauge PT002). Close supply valve CV01, CV02 if necessary</details>
</guidance>
</pv>
<pv name="MBL-030Crm:Cryo-PT-003:Cable_Error">
<description>Cavity tanks Pressure Sensor cables are disconnected</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>contact CRYO on-call and inform SCL on-call, Cryomodule pressure cable seems disconnected (value gets stuck), assign PT002 as measuring device on CV04 and CV-090 </details>
</guidance>
</pv>
<pv name="MBL-030Crm:Cryo-PT-004:HIHI">
<description>Cavity tanks pressure is too high (typical value is 31mbar in 2K mode and 1050mbar in 4K mode)</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>contact CRYO on-call and inform SCL on-call,, Cryomodule bath pressure too high (check the other gauge PT003). Close supply valve CV01, CV02 if necessary</details>
</guidance>
</pv>
<pv name="MBL-030Crm:Cryo-PT-004:Cable_Error">
<description>Cavity tanks Pressure Sensor cables are disconnected</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>contact CRYO on-call and inform SCL on-call, Cryomodule pressure cable seems disconnected (value gets stuck), assign PT003 as measuring device on CV04 and CV-090 </details>
</guidance>
</pv>
<pv name="MBL-030Crm:Cryo-TT-014:P_Limit_HIHI">
<description>Power coupler flange temperature too high</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>contact CRYO on-call and inform SCL on-call, power coupler flange temperature is too high, check heater output, if nominal then coupler flow needs to be adjusted (increased)</details>
</guidance>
</pv>
<pv name="MBL-030Crm:Cryo-TT-014:P_Limit_LO">
<description>Power coupler flange temperature too low</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>contact CRYO on-call and inform SCL on-call, power coupler flange temperature is too low, check heater output, if nominal then coupler flow needs to be adjusted (reduced)</details>
</guidance>
</pv>
<pv name="MBL-030Crm:Cryo-TT-014:P_Limit_LOLO">
<description>Power coupler flange temperature too low</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>contact CRYO on-call and inform SCL on-call, power coupler flange temperature is too low, check heater output, if nominal then coupler flow needs to be adjusted (reduced)</details>
</guidance>
</pv>
<pv name="MBL-030Crm:Cryo-TT-024:P_Limit_HIHI">
<description>Power coupler flange temperature low</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>contact CRYO on-call and inform SCL on-call, power coupler flange temperature is too high, check heater output, if nominal then coupler flow needs to be adjusted (increased)</details>
</guidance>
</pv>
<pv name="MBL-030Crm:Cryo-TT-024:P_Limit_LO">
<description>Power coupler flange temperature too low</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>contact CRYO on-call and inform SCL on-call, power coupler flange temperature is too low, check heater output, if nominal then coupler flow needs to be adjusted (reduced)</details>
</guidance>
</pv>
<pv name="MBL-030Crm:Cryo-TT-024:P_Limit_LOLO">
<description>Power coupler flange temperature too high</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>contact CRYO on-call and inform SCL on-call, power coupler flange temperature is too low, check heater output, if nominal then coupler flow needs to be adjusted (reduced)</details>
</guidance>
</pv>
<pv name="MBL-030Crm:Cryo-TT-034:P_Limit_HIHI">
<description>Power coupler flange temperature low</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>contact CRYO on-call and inform SCL on-call, power coupler flange temperature is too high, check heater output, if nominal then coupler flow needs to be adjusted (increased)</details>
</guidance>
</pv>
<pv name="MBL-030Crm:Cryo-TT-034:P_Limit_LO">
<description>Power coupler flange temperature too low</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>contact CRYO on-call and inform SCL on-call, power coupler flange temperature is too low, check heater output, if nominal then coupler flow needs to be adjusted (reduced)</details>
</guidance>
</pv>
<pv name="MBL-030Crm:Cryo-TT-034:P_Limit_LOLO">
<description>Power coupler flange temperature too high</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>contact CRYO on-call and inform SCL on-call, power coupler flange temperature is too low, check heater output, if nominal then coupler flow needs to be adjusted (reduced)</details>
</guidance>
</pv>
<pv name="MBL-030Crm:Cryo-TT-044:P_Limit_HIHI">
<description>Power coupler flange temperature low</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>contact CRYO on-call and inform SCL on-call, power coupler flange temperature is too high, check heater output, if nominal then coupler flow needs to be adjusted (increased)</details>
</guidance>
</pv>
<pv name="MBL-030Crm:Cryo-TT-044:P_Limit_LO">
<description>Power coupler flange temperature too low</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>contact CRYO on-call and inform SCL on-call, power coupler flange temperature is too low, check heater output, if nominal then coupler flow needs to be adjusted (reduced)</details>
</guidance>
</pv>
<pv name="MBL-030Crm:Cryo-TT-043:P_Limit_LOLO">
<description>Power coupler flange temperature too high</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>contact CRYO on-call and inform SCL on-call, power coupler flange temperature is too low, check heater output, if nominal then coupler flow needs to be adjusted (reduced)</details>
</guidance>
</pv>
<pv name="MBL-030Crm:WtrC-FS-012:Flow_OK_WF">
<description>! Alarm when signal drops from 1 to zero. No Water Flow Antenna 1</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>contact CRYO on-call and inform SCL on-call, assure Flange temperature TT-014 is correct. Risk of Water freeze if no flow and temperature too low</details>
</guidance>
</pv>
<pv name="MBL-030Crm:WtrC-FS-022:Flow_OK_WF">
<description>! Alarm when signal drops from 1 to zero. No Water Flow Antenna 2</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>contact CRYO on-call and inform SCL on-call, assure Flange temperature TT-024 is correct. Risk of Water freeze if no flow and temperature too low</details>
</guidance>
</pv>
<pv name="MBL-030Crm:WtrC-FS-032:Flow_OK_WF">
<description>! Alarm when signal drops from 1 to zero. No Water Flow Antenna 3</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>contact CRYO on-call and inform SCL on-call, assure Flange temperature TT-034 is correct. Risk of Water freeze if no flow and temperature too low</details>
</guidance>
</pv>
<pv name="MBL-030Crm:WtrC-FS-042:Flow_OK_WF">
<description>! Alarm when signal drops from 1 to zero. No Water Flow Antenna 4</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>contact CRYO on-call and inform SCL on-call, assure Flange temperature TT-044 is correct. Risk of Water freeze if no flow and temperature too low</details>
</guidance>
</pv>
</component>
<component name="Cryomodules\MBL-040 Cryomodule">
<pv name="MBL-040Crm:Cryo-LT-001:HIHI">
<description>LT-001 helium level extremely high</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>contact CRYO on-call and inform SCL on-call, Cryomodule liquid level too high (check the other gauge LT-002). Close supply valve CV01, CV02</details>
</guidance>
</pv>
<pv name="MBL-040Crm:Cryo-LT-002:HIHI">
<description>LT-002 helium level extremely high</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>contact CRYO on-call and inform SCL on-call, Cryomodule liquid level too high (check the other gauge LT-001). Close supply valve CV01, CV02</details>
</guidance>
</pv>
<pv name="MBL-040Crm:Cryo-LT-001:HI">
<description>LT-001 helium level high</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>contact CRYO on-call and inform SCL on-call, Cryomodule liquid level high (check the other gauge LT-002). Check level regulation valve settings, if needed: adjust LMN_LO and if necessary: Close supply valve CV01, CV02</details>
</guidance>
</pv>
<pv name="MBL-040Crm:Cryo-LT-002:HI">
<description>LT-002 helium level high</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>contact CRYO on-call and inform SCL on-call, Cryomodule liquid level high (check the other gauge LT-002). Check level regulation valve settings, if needed: adjust LMN_LO and if necessary: Close supply valve CV01, CV02</details>
</guidance>
</pv>
<pv name="MBL-040Crm:Cryo-LT-001:LO">
<description>LT-001 helium level low</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>contact CRYO on-call and inform SCL on-call, Cryomodule liquid level low (check the other gauge LT-001). Check level regulation valve settings, if needed: adjust LMN_HI</details>
</guidance>
</pv>
<pv name="MBL-040Crm:Cryo-LT-002:LO">
<description>LT-002 helium level low</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>contact CRYO on-call and inform SCL on-call, Cryomodule liquid level low (check the other gauge LT-002). Check level regulation valvesettings, if needed: adjust LMN_HI</details>
</guidance>
</pv>
<pv name="MBL-040Crm:Cryo-LT-001:LOLO">
<description>LT-002 helium level extremely low</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>contact CRYO on-call and inform SCL on-call, Cryomodule liquid level too low (check the other gauge LT-001). Check level regulation valve settings, if needed: adjust LMN_HI</details>
</guidance>
</pv>
<pv name="MBL-040Crm:Cryo-LT-002:LOLO">
<description>LT-002 helium level extremely low</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>contact CRYO on-call and inform SCL on-call, Cryomodule liquid level too low (check the other gauge LT-002). Check level regulation valvesettings, if needed: adjust LMN_HI</details>
</guidance>
</pv>
<pv name="MBL-040Crm:Cryo-PT-003:HIHI">
<description>Cavity tanks pressure is too high (typical value is 31mbar in 2K mode and 1050mbar in 4K mode)</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>contact CRYO on-call and inform SCL on-call, Cryomodule bath pressure too high (check the other gauge PT002). Close supply valve CV01, CV02 if necessary</details>
</guidance>
</pv>
<pv name="MBL-040Crm:Cryo-PT-003:Cable_Error">
<description>Cavity tanks Pressure Sensor cables are disconnected</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>contact CRYO on-call and inform SCL on-call, Cryomodule pressure cable seems disconnected (value gets stuck), assign PT002 as measuring device on CV04 and CV-090 </details>
</guidance>
</pv>
<pv name="MBL-040Crm:Cryo-PT-004:HIHI">
<description>Cavity tanks pressure is too high (typical value is 31mbar in 2K mode and 1050mbar in 4K mode)</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>contact CRYO on-call and inform SCL on-call,, Cryomodule bath pressure too high (check the other gauge PT003). Close supply valve CV01, CV02 if necessary</details>
</guidance>
</pv>
<pv name="MBL-040Crm:Cryo-PT-004:Cable_Error">
<description>Cavity tanks Pressure Sensor cables are disconnected</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>contact CRYO on-call and inform SCL on-call, Cryomodule pressure cable seems disconnected (value gets stuck), assign PT003 as measuring device on CV04 and CV-090 </details>
</guidance>
</pv>
<pv name="MBL-040Crm:Cryo-TT-014:P_Limit_HIHI">
<description>Power coupler flange temperature too high</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>contact CRYO on-call and inform SCL on-call, power coupler flange temperature is too high, check heater output, if nominal then coupler flow needs to be adjusted (increased)</details>
</guidance>
</pv>
<pv name="MBL-040Crm:Cryo-TT-014:P_Limit_LO">
<description>Power coupler flange temperature too low</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>contact CRYO on-call and inform SCL on-call, power coupler flange temperature is too low, check heater output, if nominal then coupler flow needs to be adjusted (reduced)</details>
</guidance>
</pv>
<pv name="MBL-040Crm:Cryo-TT-014:P_Limit_LOLO">
<description>Power coupler flange temperature too low</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>contact CRYO on-call and inform SCL on-call, power coupler flange temperature is too low, check heater output, if nominal then coupler flow needs to be adjusted (reduced)</details>
</guidance>
</pv>
<pv name="MBL-040Crm:Cryo-TT-024:P_Limit_HIHI">
<description>Power coupler flange temperature low</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>contact CRYO on-call and inform SCL on-call, power coupler flange temperature is too high, check heater output, if nominal then coupler flow needs to be adjusted (increased)</details>
</guidance>
</pv>
<pv name="MBL-040Crm:Cryo-TT-024:P_Limit_LO">
<description>Power coupler flange temperature too low</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>contact CRYO on-call and inform SCL on-call, power coupler flange temperature is too low, check heater output, if nominal then coupler flow needs to be adjusted (reduced)</details>
</guidance>
</pv>
<pv name="MBL-040Crm:Cryo-TT-024:P_Limit_LOLO">
<description>Power coupler flange temperature too high</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>contact CRYO on-call and inform SCL on-call, power coupler flange temperature is too low, check heater output, if nominal then coupler flow needs to be adjusted (reduced)</details>
</guidance>
</pv>
<pv name="MBL-040Crm:Cryo-TT-034:P_Limit_HIHI">
<description>Power coupler flange temperature low</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>contact CRYO on-call and inform SCL on-call, power coupler flange temperature is too high, check heater output, if nominal then coupler flow needs to be adjusted (increased)</details>
</guidance>
</pv>
<pv name="MBL-040Crm:Cryo-TT-034:P_Limit_LO">
<description>Power coupler flange temperature too low</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>contact CRYO on-call and inform SCL on-call, power coupler flange temperature is too low, check heater output, if nominal then coupler flow needs to be adjusted (reduced)</details>
</guidance>
</pv>
<pv name="MBL-040Crm:Cryo-TT-034:P_Limit_LOLO">
<description>Power coupler flange temperature too high</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>contact CRYO on-call and inform SCL on-call, power coupler flange temperature is too low, check heater output, if nominal then coupler flow needs to be adjusted (reduced)</details>
</guidance>
</pv>
<pv name="MBL-040Crm:Cryo-TT-044:P_Limit_HIHI">
<description>Power coupler flange temperature low</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>contact CRYO on-call and inform SCL on-call, power coupler flange temperature is too high, check heater output, if nominal then coupler flow needs to be adjusted (increased)</details>
</guidance>
</pv>
<pv name="MBL-040Crm:Cryo-TT-044:P_Limit_LO">
<description>Power coupler flange temperature too low</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>contact CRYO on-call and inform SCL on-call, power coupler flange temperature is too low, check heater output, if nominal then coupler flow needs to be adjusted (reduced)</details>
</guidance>
</pv>
<pv name="MBL-040Crm:Cryo-TT-043:P_Limit_LOLO">
<description>Power coupler flange temperature too high</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>contact CRYO on-call and inform SCL on-call, power coupler flange temperature is too low, check heater output, if nominal then coupler flow needs to be adjusted (reduced)</details>
</guidance>
</pv>
<pv name="MBL-040Crm:WtrC-FS-012:Flow_OK_WF">
<description>! Alarm when signal drops from 1 to zero. No Water Flow Antenna 1</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>contact CRYO on-call and inform SCL on-call, assure Flange temperature TT-014 is correct. Risk of Water freeze if no flow and temperature too low</details>
</guidance>
</pv>
<pv name="MBL-040Crm:WtrC-FS-022:Flow_OK_WF">
<description>! Alarm when signal drops from 1 to zero. No Water Flow Antenna 2</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>contact CRYO on-call and inform SCL on-call, assure Flange temperature TT-024 is correct. Risk of Water freeze if no flow and temperature too low</details>
</guidance>
</pv>
<pv name="MBL-040Crm:WtrC-FS-032:Flow_OK_WF">
<description>! Alarm when signal drops from 1 to zero. No Water Flow Antenna 3</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>contact CRYO on-call and inform SCL on-call, assure Flange temperature TT-034 is correct. Risk of Water freeze if no flow and temperature too low</details>
</guidance>
</pv>
<pv name="MBL-040Crm:WtrC-FS-042:Flow_OK_WF">
<description>! Alarm when signal drops from 1 to zero. No Water Flow Antenna 4</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>contact CRYO on-call and inform SCL on-call, assure Flange temperature TT-044 is correct. Risk of Water freeze if no flow and temperature too low</details>
</guidance>
</pv>
</component>
<component name="Cryomodules\MBL-050 Cryomodule">
<pv name="MBL-050Crm:Cryo-LT-001:HIHI">
<description>LT-001 helium level extremely high</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>contact CRYO on-call and inform SCL on-call, Cryomodule liquid level too high (check the other gauge LT-002). Close supply valve CV01, CV02</details>
</guidance>
</pv>
<pv name="MBL-050Crm:Cryo-LT-002:HIHI">
<description>LT-002 helium level extremely high</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>contact CRYO on-call and inform SCL on-call, Cryomodule liquid level too high (check the other gauge LT-001). Close supply valve CV01, CV02</details>
</guidance>
</pv>
<pv name="MBL-050Crm:Cryo-LT-001:HI">
<description>LT-001 helium level high</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>contact CRYO on-call and inform SCL on-call, Cryomodule liquid level high (check the other gauge LT-002). Check level regulation valve settings, if needed: adjust LMN_LO and if necessary: Close supply valve CV01, CV02</details>
</guidance>
</pv>
<pv name="MBL-050Crm:Cryo-LT-002:HI">
<description>LT-002 helium level high</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>contact CRYO on-call and inform SCL on-call, Cryomodule liquid level high (check the other gauge LT-002). Check level regulation valve settings, if needed: adjust LMN_LO and if necessary: Close supply valve CV01, CV02</details>
</guidance>
</pv>
<pv name="MBL-050Crm:Cryo-LT-001:LO">
<description>LT-001 helium level low</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>contact CRYO on-call and inform SCL on-call, Cryomodule liquid level low (check the other gauge LT-001). Check level regulation valve settings, if needed: adjust LMN_HI</details>
</guidance>
</pv>
<pv name="MBL-050Crm:Cryo-LT-002:LO">
<description>LT-002 helium level low</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>contact CRYO on-call and inform SCL on-call, Cryomodule liquid level low (check the other gauge LT-002). Check level regulation valvesettings, if needed: adjust LMN_HI</details>
</guidance>
</pv>
<pv name="MBL-050Crm:Cryo-LT-001:LOLO">
<description>LT-002 helium level extremely low</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>contact CRYO on-call and inform SCL on-call, Cryomodule liquid level too low (check the other gauge LT-001). Check level regulation valve settings, if needed: adjust LMN_HI</details>
</guidance>
</pv>
<pv name="MBL-050Crm:Cryo-LT-002:LOLO">
<description>LT-002 helium level extremely low</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>contact CRYO on-call and inform SCL on-call, Cryomodule liquid level too low (check the other gauge LT-002). Check level regulation valvesettings, if needed: adjust LMN_HI</details>
</guidance>
</pv>
<pv name="MBL-050Crm:Cryo-PT-003:HIHI">
<description>Cavity tanks pressure is too high (typical value is 31mbar in 2K mode and 1050mbar in 4K mode)</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>contact CRYO on-call and inform SCL on-call, Cryomodule bath pressure too high (check the other gauge PT002). Close supply valve CV01, CV02 if necessary</details>
</guidance>
</pv>
<pv name="MBL-050Crm:Cryo-PT-003:Cable_Error">
<description>Cavity tanks Pressure Sensor cables are disconnected</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>contact CRYO on-call and inform SCL on-call, Cryomodule pressure cable seems disconnected (value gets stuck), assign PT002 as measuring device on CV04 and CV-090 </details>
</guidance>
</pv>
<pv name="MBL-050Crm:Cryo-PT-004:HIHI">
<description>Cavity tanks pressure is too high (typical value is 31mbar in 2K mode and 1050mbar in 4K mode)</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>contact CRYO on-call and inform SCL on-call,, Cryomodule bath pressure too high (check the other gauge PT003). Close supply valve CV01, CV02 if necessary</details>
</guidance>
</pv>
<pv name="MBL-050Crm:Cryo-PT-004:Cable_Error">
<description>Cavity tanks Pressure Sensor cables are disconnected</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>contact CRYO on-call and inform SCL on-call, Cryomodule pressure cable seems disconnected (value gets stuck), assign PT003 as measuring device on CV04 and CV-090 </details>
</guidance>
</pv>
<pv name="MBL-050Crm:Cryo-TT-014:P_Limit_HIHI">
<description>Power coupler flange temperature too high</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>contact CRYO on-call and inform SCL on-call, power coupler flange temperature is too high, check heater output, if nominal then coupler flow needs to be adjusted (increased)</details>
</guidance>
</pv>
<pv name="MBL-050Crm:Cryo-TT-014:P_Limit_LO">
<description>Power coupler flange temperature too low</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>contact CRYO on-call and inform SCL on-call, power coupler flange temperature is too low, check heater output, if nominal then coupler flow needs to be adjusted (reduced)</details>
</guidance>
</pv>
<pv name="MBL-050Crm:Cryo-TT-014:P_Limit_LOLO">
<description>Power coupler flange temperature too low</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>contact CRYO on-call and inform SCL on-call, power coupler flange temperature is too low, check heater output, if nominal then coupler flow needs to be adjusted (reduced)</details>
</guidance>
</pv>
<pv name="MBL-050Crm:Cryo-TT-024:P_Limit_HIHI">
<description>Power coupler flange temperature low</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>contact CRYO on-call and inform SCL on-call, power coupler flange temperature is too high, check heater output, if nominal then coupler flow needs to be adjusted (increased)</details>
</guidance>
</pv>
<pv name="MBL-050Crm:Cryo-TT-024:P_Limit_LO">
<description>Power coupler flange temperature too low</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>contact CRYO on-call and inform SCL on-call, power coupler flange temperature is too low, check heater output, if nominal then coupler flow needs to be adjusted (reduced)</details>
</guidance>
</pv>
<pv name="MBL-050Crm:Cryo-TT-024:P_Limit_LOLO">
<description>Power coupler flange temperature too high</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>contact CRYO on-call and inform SCL on-call, power coupler flange temperature is too low, check heater output, if nominal then coupler flow needs to be adjusted (reduced)</details>
</guidance>
</pv>
<pv name="MBL-050Crm:Cryo-TT-034:P_Limit_HIHI">
<description>Power coupler flange temperature low</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>contact CRYO on-call and inform SCL on-call, power coupler flange temperature is too high, check heater output, if nominal then coupler flow needs to be adjusted (increased)</details>
</guidance>
</pv>
<pv name="MBL-050Crm:Cryo-TT-034:P_Limit_LO">
<description>Power coupler flange temperature too low</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>contact CRYO on-call and inform SCL on-call, power coupler flange temperature is too low, check heater output, if nominal then coupler flow needs to be adjusted (reduced)</details>
</guidance>
</pv>
<pv name="MBL-050Crm:Cryo-TT-034:P_Limit_LOLO">
<description>Power coupler flange temperature too high</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>contact CRYO on-call and inform SCL on-call, power coupler flange temperature is too low, check heater output, if nominal then coupler flow needs to be adjusted (reduced)</details>
</guidance>
</pv>
<pv name="MBL-050Crm:Cryo-TT-044:P_Limit_HIHI">
<description>Power coupler flange temperature low</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>contact CRYO on-call and inform SCL on-call, power coupler flange temperature is too high, check heater output, if nominal then coupler flow needs to be adjusted (increased)</details>
</guidance>
</pv>
<pv name="MBL-050Crm:Cryo-TT-044:P_Limit_LO">
<description>Power coupler flange temperature too low</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>contact CRYO on-call and inform SCL on-call, power coupler flange temperature is too low, check heater output, if nominal then coupler flow needs to be adjusted (reduced)</details>
</guidance>
</pv>
<pv name="MBL-050Crm:Cryo-TT-043:P_Limit_LOLO">
<description>Power coupler flange temperature too high</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>contact CRYO on-call and inform SCL on-call, power coupler flange temperature is too low, check heater output, if nominal then coupler flow needs to be adjusted (reduced)</details>
</guidance>
</pv>
<pv name="MBL-050Crm:WtrC-FS-012:Flow_OK_WF">
<description>! Alarm when signal drops from 1 to zero. No Water Flow Antenna 1</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>contact CRYO on-call and inform SCL on-call, assure Flange temperature TT-014 is correct. Risk of Water freeze if no flow and temperature too low</details>
</guidance>
</pv>
<pv name="MBL-050Crm:WtrC-FS-022:Flow_OK_WF">
<description>! Alarm when signal drops from 1 to zero. No Water Flow Antenna 2</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>contact CRYO on-call and inform SCL on-call, assure Flange temperature TT-024 is correct. Risk of Water freeze if no flow and temperature too low</details>
</guidance>
</pv>
<pv name="MBL-050Crm:WtrC-FS-032:Flow_OK_WF">
<description>! Alarm when signal drops from 1 to zero. No Water Flow Antenna 3</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>contact CRYO on-call and inform SCL on-call, assure Flange temperature TT-034 is correct. Risk of Water freeze if no flow and temperature too low</details>
</guidance>
</pv>
<pv name="MBL-050Crm:WtrC-FS-042:Flow_OK_WF">
<description>! Alarm when signal drops from 1 to zero. No Water Flow Antenna 4</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>contact CRYO on-call and inform SCL on-call, assure Flange temperature TT-044 is correct. Risk of Water freeze if no flow and temperature too low</details>
</guidance>
</pv>
</component>
<component name="Cryomodules\MBL-060 Cryomodule">
<pv name="MBL-060Crm:Cryo-LT-001:HIHI">
<description>LT-001 helium level extremely high</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>contact CRYO on-call and inform SCL on-call, Cryomodule liquid level too high (check the other gauge LT-002). Close supply valve CV01, CV02</details>
</guidance>
</pv>
<pv name="MBL-060Crm:Cryo-LT-002:HIHI">
<description>LT-002 helium level extremely high</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>contact CRYO on-call and inform SCL on-call, Cryomodule liquid level too high (check the other gauge LT-001). Close supply valve CV01, CV02</details>
</guidance>
</pv>
<pv name="MBL-060Crm:Cryo-LT-001:HI">
<description>LT-001 helium level high</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>contact CRYO on-call and inform SCL on-call, Cryomodule liquid level high (check the other gauge LT-002). Check level regulation valve settings, if needed: adjust LMN_LO and if necessary: Close supply valve CV01, CV02</details>
</guidance>
</pv>
<pv name="MBL-060Crm:Cryo-LT-002:HI">
<description>LT-002 helium level high</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>contact CRYO on-call and inform SCL on-call, Cryomodule liquid level high (check the other gauge LT-002). Check level regulation valve settings, if needed: adjust LMN_LO and if necessary: Close supply valve CV01, CV02</details>
</guidance>
</pv>
<pv name="MBL-060Crm:Cryo-LT-001:LO">
<description>LT-001 helium level low</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>contact CRYO on-call and inform SCL on-call, Cryomodule liquid level low (check the other gauge LT-001). Check level regulation valve settings, if needed: adjust LMN_HI</details>
</guidance>
</pv>
<pv name="MBL-060Crm:Cryo-LT-002:LO">
<description>LT-002 helium level low</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>contact CRYO on-call and inform SCL on-call, Cryomodule liquid level low (check the other gauge LT-002). Check level regulation valvesettings, if needed: adjust LMN_HI</details>
</guidance>
</pv>
<pv name="MBL-060Crm:Cryo-LT-001:LOLO">
<description>LT-002 helium level extremely low</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>contact CRYO on-call and inform SCL on-call, Cryomodule liquid level too low (check the other gauge LT-001). Check level regulation valve settings, if needed: adjust LMN_HI</details>
</guidance>
</pv>
<pv name="MBL-060Crm:Cryo-LT-002:LOLO">
<description>LT-002 helium level extremely low</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>contact CRYO on-call and inform SCL on-call, Cryomodule liquid level too low (check the other gauge LT-002). Check level regulation valvesettings, if needed: adjust LMN_HI</details>
</guidance>
</pv>
<pv name="MBL-060Crm:Cryo-PT-003:HIHI">
<description>Cavity tanks pressure is too high (typical value is 31mbar in 2K mode and 1050mbar in 4K mode)</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>contact CRYO on-call and inform SCL on-call, Cryomodule bath pressure too high (check the other gauge PT002). Close supply valve CV01, CV02 if necessary</details>
</guidance>
</pv>
<pv name="MBL-060Crm:Cryo-PT-003:Cable_Error">
<description>Cavity tanks Pressure Sensor cables are disconnected</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>contact CRYO on-call and inform SCL on-call, Cryomodule pressure cable seems disconnected (value gets stuck), assign PT002 as measuring device on CV04 and CV-090 </details>
</guidance>
</pv>
<pv name="MBL-060Crm:Cryo-PT-004:HIHI">
<description>Cavity tanks pressure is too high (typical value is 31mbar in 2K mode and 1050mbar in 4K mode)</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>contact CRYO on-call and inform SCL on-call,, Cryomodule bath pressure too high (check the other gauge PT003). Close supply valve CV01, CV02 if necessary</details>
</guidance>
</pv>
<pv name="MBL-060Crm:Cryo-PT-004:Cable_Error">
<description>Cavity tanks Pressure Sensor cables are disconnected</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>contact CRYO on-call and inform SCL on-call, Cryomodule pressure cable seems disconnected (value gets stuck), assign PT003 as measuring device on CV04 and CV-090 </details>
</guidance>
</pv>
<pv name="MBL-060Crm:Cryo-TT-014:P_Limit_HIHI">
<description>Power coupler flange temperature too high</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>contact CRYO on-call and inform SCL on-call, power coupler flange temperature is too high, check heater output, if nominal then coupler flow needs to be adjusted (increased)</details>
</guidance>
</pv>
<pv name="MBL-060Crm:Cryo-TT-014:P_Limit_LO">
<description>Power coupler flange temperature too low</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>contact CRYO on-call and inform SCL on-call, power coupler flange temperature is too low, check heater output, if nominal then coupler flow needs to be adjusted (reduced)</details>
</guidance>
</pv>
<pv name="MBL-060Crm:Cryo-TT-014:P_Limit_LOLO">
<description>Power coupler flange temperature too low</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>contact CRYO on-call and inform SCL on-call, power coupler flange temperature is too low, check heater output, if nominal then coupler flow needs to be adjusted (reduced)</details>
</guidance>
</pv>
<pv name="MBL-060Crm:Cryo-TT-024:P_Limit_HIHI">
<description>Power coupler flange temperature low</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>contact CRYO on-call and inform SCL on-call, power coupler flange temperature is too high, check heater output, if nominal then coupler flow needs to be adjusted (increased)</details>
</guidance>
</pv>
<pv name="MBL-060Crm:Cryo-TT-024:P_Limit_LO">
<description>Power coupler flange temperature too low</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>contact CRYO on-call and inform SCL on-call, power coupler flange temperature is too low, check heater output, if nominal then coupler flow needs to be adjusted (reduced)</details>
</guidance>
</pv>
<pv name="MBL-060Crm:Cryo-TT-024:P_Limit_LOLO">
<description>Power coupler flange temperature too high</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>contact CRYO on-call and inform SCL on-call, power coupler flange temperature is too low, check heater output, if nominal then coupler flow needs to be adjusted (reduced)</details>
</guidance>
</pv>
<pv name="MBL-060Crm:Cryo-TT-034:P_Limit_HIHI">
<description>Power coupler flange temperature low</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>contact CRYO on-call and inform SCL on-call, power coupler flange temperature is too high, check heater output, if nominal then coupler flow needs to be adjusted (increased)</details>
</guidance>
</pv>
<pv name="MBL-060Crm:Cryo-TT-034:P_Limit_LO">
<description>Power coupler flange temperature too low</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>contact CRYO on-call and inform SCL on-call, power coupler flange temperature is too low, check heater output, if nominal then coupler flow needs to be adjusted (reduced)</details>
</guidance>
</pv>
<pv name="MBL-060Crm:Cryo-TT-034:P_Limit_LOLO">
<description>Power coupler flange temperature too high</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>contact CRYO on-call and inform SCL on-call, power coupler flange temperature is too low, check heater output, if nominal then coupler flow needs to be adjusted (reduced)</details>
</guidance>
</pv>
<pv name="MBL-060Crm:Cryo-TT-044:P_Limit_HIHI">
<description>Power coupler flange temperature low</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>contact CRYO on-call and inform SCL on-call, power coupler flange temperature is too high, check heater output, if nominal then coupler flow needs to be adjusted (increased)</details>
</guidance>
</pv>
<pv name="MBL-060Crm:Cryo-TT-044:P_Limit_LO">
<description>Power coupler flange temperature too low</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>contact CRYO on-call and inform SCL on-call, power coupler flange temperature is too low, check heater output, if nominal then coupler flow needs to be adjusted (reduced)</details>
</guidance>
</pv>
<pv name="MBL-060Crm:Cryo-TT-043:P_Limit_LOLO">
<description>Power coupler flange temperature too high</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>contact CRYO on-call and inform SCL on-call, power coupler flange temperature is too low, check heater output, if nominal then coupler flow needs to be adjusted (reduced)</details>
</guidance>
</pv>
<pv name="MBL-060Crm:WtrC-FS-012:Flow_OK_WF">
<description>! Alarm when signal drops from 1 to zero. No Water Flow Antenna 1</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>contact CRYO on-call and inform SCL on-call, assure Flange temperature TT-014 is correct. Risk of Water freeze if no flow and temperature too low</details>
</guidance>
</pv>
<pv name="MBL-060Crm:WtrC-FS-022:Flow_OK_WF">
<description>! Alarm when signal drops from 1 to zero. No Water Flow Antenna 2</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>contact CRYO on-call and inform SCL on-call, assure Flange temperature TT-024 is correct. Risk of Water freeze if no flow and temperature too low</details>
</guidance>
</pv>
<pv name="MBL-060Crm:WtrC-FS-032:Flow_OK_WF">
<description>! Alarm when signal drops from 1 to zero. No Water Flow Antenna 3</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>contact CRYO on-call and inform SCL on-call, assure Flange temperature TT-034 is correct. Risk of Water freeze if no flow and temperature too low</details>
</guidance>
</pv>
<pv name="MBL-060Crm:WtrC-FS-042:Flow_OK_WF">
<description>! Alarm when signal drops from 1 to zero. No Water Flow Antenna 4</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>contact CRYO on-call and inform SCL on-call, assure Flange temperature TT-044 is correct. Risk of Water freeze if no flow and temperature too low</details>
</guidance>
</pv>
</component>
<component name="Cryomodules\MBL-070 Cryomodule">
<pv name="MBL-070Crm:Cryo-LT-001:HIHI">
<description>LT-001 helium level extremely high</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>contact CRYO on-call and inform SCL on-call, Cryomodule liquid level too high (check the other gauge LT-002). Close supply valve CV01, CV02</details>
</guidance>
</pv>
<pv name="MBL-070Crm:Cryo-LT-002:HIHI">
<description>LT-002 helium level extremely high</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>contact CRYO on-call and inform SCL on-call, Cryomodule liquid level too high (check the other gauge LT-001). Close supply valve CV01, CV02</details>
</guidance>
</pv>
<pv name="MBL-070Crm:Cryo-LT-001:HI">
<description>LT-001 helium level high</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>contact CRYO on-call and inform SCL on-call, Cryomodule liquid level high (check the other gauge LT-002). Check level regulation valve settings, if needed: adjust LMN_LO and if necessary: Close supply valve CV01, CV02</details>
</guidance>
</pv>
<pv name="MBL-070Crm:Cryo-LT-002:HI">
<description>LT-002 helium level high</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>contact CRYO on-call and inform SCL on-call, Cryomodule liquid level high (check the other gauge LT-002). Check level regulation valve settings, if needed: adjust LMN_LO and if necessary: Close supply valve CV01, CV02</details>
</guidance>
</pv>
<pv name="MBL-070Crm:Cryo-LT-001:LO">
<description>LT-001 helium level low</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>contact CRYO on-call and inform SCL on-call, Cryomodule liquid level low (check the other gauge LT-001). Check level regulation valve settings, if needed: adjust LMN_HI</details>
</guidance>
</pv>
<pv name="MBL-070Crm:Cryo-LT-002:LO">
<description>LT-002 helium level low</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>contact CRYO on-call and inform SCL on-call, Cryomodule liquid level low (check the other gauge LT-002). Check level regulation valvesettings, if needed: adjust LMN_HI</details>
</guidance>
</pv>
<pv name="MBL-070Crm:Cryo-LT-001:LOLO">
<description>LT-002 helium level extremely low</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>contact CRYO on-call and inform SCL on-call, Cryomodule liquid level too low (check the other gauge LT-001). Check level regulation valve settings, if needed: adjust LMN_HI</details>
</guidance>
</pv>
<pv name="MBL-070Crm:Cryo-LT-002:LOLO">
<description>LT-002 helium level extremely low</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>contact CRYO on-call and inform SCL on-call, Cryomodule liquid level too low (check the other gauge LT-002). Check level regulation valvesettings, if needed: adjust LMN_HI</details>
</guidance>
</pv>
<pv name="MBL-070Crm:Cryo-PT-003:HIHI">
<description>Cavity tanks pressure is too high (typical value is 31mbar in 2K mode and 1050mbar in 4K mode)</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>contact CRYO on-call and inform SCL on-call, Cryomodule bath pressure too high (check the other gauge PT002). Close supply valve CV01, CV02 if necessary</details>
</guidance>
</pv>
<pv name="MBL-070Crm:Cryo-PT-003:Cable_Error">
<description>Cavity tanks Pressure Sensor cables are disconnected</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>contact CRYO on-call and inform SCL on-call, Cryomodule pressure cable seems disconnected (value gets stuck), assign PT002 as measuring device on CV04 and CV-090 </details>
</guidance>
</pv>
<pv name="MBL-070Crm:Cryo-PT-004:HIHI">
<description>Cavity tanks pressure is too high (typical value is 31mbar in 2K mode and 1050mbar in 4K mode)</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>contact CRYO on-call and inform SCL on-call,, Cryomodule bath pressure too high (check the other gauge PT003). Close supply valve CV01, CV02 if necessary</details>
</guidance>
</pv>
<pv name="MBL-070Crm:Cryo-PT-004:Cable_Error">
<description>Cavity tanks Pressure Sensor cables are disconnected</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>contact CRYO on-call and inform SCL on-call, Cryomodule pressure cable seems disconnected (value gets stuck), assign PT003 as measuring device on CV04 and CV-090 </details>
</guidance>
</pv>
<pv name="MBL-070Crm:Cryo-TT-014:P_Limit_HIHI">
<description>Power coupler flange temperature too high</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>contact CRYO on-call and inform SCL on-call, power coupler flange temperature is too high, check heater output, if nominal then coupler flow needs to be adjusted (increased)</details>
</guidance>
</pv>
<pv name="MBL-070Crm:Cryo-TT-014:P_Limit_LO">
<description>Power coupler flange temperature too low</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>contact CRYO on-call and inform SCL on-call, power coupler flange temperature is too low, check heater output, if nominal then coupler flow needs to be adjusted (reduced)</details>
</guidance>
</pv>
<pv name="MBL-070Crm:Cryo-TT-014:P_Limit_LOLO">
<description>Power coupler flange temperature too low</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>contact CRYO on-call and inform SCL on-call, power coupler flange temperature is too low, check heater output, if nominal then coupler flow needs to be adjusted (reduced)</details>
</guidance>
</pv>
<pv name="MBL-070Crm:Cryo-TT-024:P_Limit_HIHI">
<description>Power coupler flange temperature low</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>contact CRYO on-call and inform SCL on-call, power coupler flange temperature is too high, check heater output, if nominal then coupler flow needs to be adjusted (increased)</details>
</guidance>
</pv>
<pv name="MBL-070Crm:Cryo-TT-024:P_Limit_LO">
<description>Power coupler flange temperature too low</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>contact CRYO on-call and inform SCL on-call, power coupler flange temperature is too low, check heater output, if nominal then coupler flow needs to be adjusted (reduced)</details>
</guidance>
</pv>
<pv name="MBL-070Crm:Cryo-TT-024:P_Limit_LOLO">
<description>Power coupler flange temperature too high</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>contact CRYO on-call and inform SCL on-call, power coupler flange temperature is too low, check heater output, if nominal then coupler flow needs to be adjusted (reduced)</details>
</guidance>
</pv>
<pv name="MBL-070Crm:Cryo-TT-034:P_Limit_HIHI">
<description>Power coupler flange temperature low</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>contact CRYO on-call and inform SCL on-call, power coupler flange temperature is too high, check heater output, if nominal then coupler flow needs to be adjusted (increased)</details>
</guidance>
</pv>
<pv name="MBL-070Crm:Cryo-TT-034:P_Limit_LO">
<description>Power coupler flange temperature too low</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>contact CRYO on-call and inform SCL on-call, power coupler flange temperature is too low, check heater output, if nominal then coupler flow needs to be adjusted (reduced)</details>
</guidance>
</pv>
<pv name="MBL-070Crm:Cryo-TT-034:P_Limit_LOLO">
<description>Power coupler flange temperature too high</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>contact CRYO on-call and inform SCL on-call, power coupler flange temperature is too low, check heater output, if nominal then coupler flow needs to be adjusted (reduced)</details>
</guidance>
</pv>
<pv name="MBL-070Crm:Cryo-TT-044:P_Limit_HIHI">
<description>Power coupler flange temperature low</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>contact CRYO on-call and inform SCL on-call, power coupler flange temperature is too high, check heater output, if nominal then coupler flow needs to be adjusted (increased)</details>
</guidance>
</pv>
<pv name="MBL-070Crm:Cryo-TT-044:P_Limit_LO">
<description>Power coupler flange temperature too low</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>contact CRYO on-call and inform SCL on-call, power coupler flange temperature is too low, check heater output, if nominal then coupler flow needs to be adjusted (reduced)</details>
</guidance>
</pv>
<pv name="MBL-070Crm:Cryo-TT-043:P_Limit_LOLO">
<description>Power coupler flange temperature too high</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>contact CRYO on-call and inform SCL on-call, power coupler flange temperature is too low, check heater output, if nominal then coupler flow needs to be adjusted (reduced)</details>
</guidance>
</pv>
<pv name="MBL-070Crm:WtrC-FS-012:Flow_OK_WF">
<description>! Alarm when signal drops from 1 to zero. No Water Flow Antenna 1</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>contact CRYO on-call and inform SCL on-call, assure Flange temperature TT-014 is correct. Risk of Water freeze if no flow and temperature too low</details>
</guidance>
</pv>
<pv name="MBL-070Crm:WtrC-FS-022:Flow_OK_WF">
<description>! Alarm when signal drops from 1 to zero. No Water Flow Antenna 2</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>contact CRYO on-call and inform SCL on-call, assure Flange temperature TT-024 is correct. Risk of Water freeze if no flow and temperature too low</details>
</guidance>
</pv>
<pv name="MBL-070Crm:WtrC-FS-032:Flow_OK_WF">
<description>! Alarm when signal drops from 1 to zero. No Water Flow Antenna 3</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>contact CRYO on-call and inform SCL on-call, assure Flange temperature TT-034 is correct. Risk of Water freeze if no flow and temperature too low</details>
</guidance>
</pv>
<pv name="MBL-070Crm:WtrC-FS-042:Flow_OK_WF">
<description>! Alarm when signal drops from 1 to zero. No Water Flow Antenna 4</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>contact CRYO on-call and inform SCL on-call, assure Flange temperature TT-044 is correct. Risk of Water freeze if no flow and temperature too low</details>
</guidance>
</pv>
</component>
<component name="Cryomodules\MBL-080 Cryomodule">
<pv name="MBL-080Crm:Cryo-LT-001:HIHI">
<description>LT-001 helium level extremely high</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>contact CRYO on-call and inform SCL on-call, Cryomodule liquid level too high (check the other gauge LT-002). Close supply valve CV01, CV02</details>
</guidance>
</pv>
<pv name="MBL-080Crm:Cryo-LT-002:HIHI">
<description>LT-002 helium level extremely high</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>contact CRYO on-call and inform SCL on-call, Cryomodule liquid level too high (check the other gauge LT-001). Close supply valve CV01, CV02</details>
</guidance>
</pv>
<pv name="MBL-080Crm:Cryo-LT-001:HI">
<description>LT-001 helium level high</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>contact CRYO on-call and inform SCL on-call, Cryomodule liquid level high (check the other gauge LT-002). Check level regulation valve settings, if needed: adjust LMN_LO and if necessary: Close supply valve CV01, CV02</details>
</guidance>
</pv>
<pv name="MBL-080Crm:Cryo-LT-002:HI">
<description>LT-002 helium level high</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>contact CRYO on-call and inform SCL on-call, Cryomodule liquid level high (check the other gauge LT-002). Check level regulation valve settings, if needed: adjust LMN_LO and if necessary: Close supply valve CV01, CV02</details>
</guidance>
</pv>
<pv name="MBL-080Crm:Cryo-LT-001:LO">
<description>LT-001 helium level low</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>contact CRYO on-call and inform SCL on-call, Cryomodule liquid level low (check the other gauge LT-001). Check level regulation valve settings, if needed: adjust LMN_HI</details>
</guidance>
</pv>
<pv name="MBL-080Crm:Cryo-LT-002:LO">
<description>LT-002 helium level low</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>contact CRYO on-call and inform SCL on-call, Cryomodule liquid level low (check the other gauge LT-002). Check level regulation valvesettings, if needed: adjust LMN_HI</details>
</guidance>
</pv>
<pv name="MBL-080Crm:Cryo-LT-001:LOLO">
<description>LT-002 helium level extremely low</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>contact CRYO on-call and inform SCL on-call, Cryomodule liquid level too low (check the other gauge LT-001). Check level regulation valve settings, if needed: adjust LMN_HI</details>
</guidance>
</pv>
<pv name="MBL-080Crm:Cryo-LT-002:LOLO">
<description>LT-002 helium level extremely low</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>contact CRYO on-call and inform SCL on-call, Cryomodule liquid level too low (check the other gauge LT-002). Check level regulation valvesettings, if needed: adjust LMN_HI</details>
</guidance>
</pv>
<pv name="MBL-080Crm:Cryo-PT-003:HIHI">
<description>Cavity tanks pressure is too high (typical value is 31mbar in 2K mode and 1050mbar in 4K mode)</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>contact CRYO on-call and inform SCL on-call, Cryomodule bath pressure too high (check the other gauge PT002). Close supply valve CV01, CV02 if necessary</details>
</guidance>
</pv>
<pv name="MBL-080Crm:Cryo-PT-003:Cable_Error">
<description>Cavity tanks Pressure Sensor cables are disconnected</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>contact CRYO on-call and inform SCL on-call, Cryomodule pressure cable seems disconnected (value gets stuck), assign PT002 as measuring device on CV04 and CV-090 </details>
</guidance>
</pv>
<pv name="MBL-080Crm:Cryo-PT-004:HIHI">
<description>Cavity tanks pressure is too high (typical value is 31mbar in 2K mode and 1050mbar in 4K mode)</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>contact CRYO on-call and inform SCL on-call,, Cryomodule bath pressure too high (check the other gauge PT003). Close supply valve CV01, CV02 if necessary</details>
</guidance>
</pv>
<pv name="MBL-080Crm:Cryo-PT-004:Cable_Error">
<description>Cavity tanks Pressure Sensor cables are disconnected</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>contact CRYO on-call and inform SCL on-call, Cryomodule pressure cable seems disconnected (value gets stuck), assign PT003 as measuring device on CV04 and CV-090 </details>
</guidance>
</pv>
<pv name="MBL-080Crm:Cryo-TT-014:P_Limit_HIHI">
<description>Power coupler flange temperature too high</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>contact CRYO on-call and inform SCL on-call, power coupler flange temperature is too high, check heater output, if nominal then coupler flow needs to be adjusted (increased)</details>
</guidance>
</pv>
<pv name="MBL-080Crm:Cryo-TT-014:P_Limit_LO">
<description>Power coupler flange temperature too low</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>contact CRYO on-call and inform SCL on-call, power coupler flange temperature is too low, check heater output, if nominal then coupler flow needs to be adjusted (reduced)</details>
</guidance>
</pv>
<pv name="MBL-080Crm:Cryo-TT-014:P_Limit_LOLO">
<description>Power coupler flange temperature too low</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>contact CRYO on-call and inform SCL on-call, power coupler flange temperature is too low, check heater output, if nominal then coupler flow needs to be adjusted (reduced)</details>
</guidance>
</pv>
<pv name="MBL-080Crm:Cryo-TT-024:P_Limit_HIHI">
<description>Power coupler flange temperature low</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>contact CRYO on-call and inform SCL on-call, power coupler flange temperature is too high, check heater output, if nominal then coupler flow needs to be adjusted (increased)</details>
</guidance>
</pv>
<pv name="MBL-080Crm:Cryo-TT-024:P_Limit_LO">
<description>Power coupler flange temperature too low</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>contact CRYO on-call and inform SCL on-call, power coupler flange temperature is too low, check heater output, if nominal then coupler flow needs to be adjusted (reduced)</details>
</guidance>
</pv>
<pv name="MBL-080Crm:Cryo-TT-024:P_Limit_LOLO">
<description>Power coupler flange temperature too high</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>contact CRYO on-call and inform SCL on-call, power coupler flange temperature is too low, check heater output, if nominal then coupler flow needs to be adjusted (reduced)</details>
</guidance>
</pv>
<pv name="MBL-080Crm:Cryo-TT-034:P_Limit_HIHI">
<description>Power coupler flange temperature low</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>contact CRYO on-call and inform SCL on-call, power coupler flange temperature is too high, check heater output, if nominal then coupler flow needs to be adjusted (increased)</details>
</guidance>
</pv>
<pv name="MBL-080Crm:Cryo-TT-034:P_Limit_LO">
<description>Power coupler flange temperature too low</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>contact CRYO on-call and inform SCL on-call, power coupler flange temperature is too low, check heater output, if nominal then coupler flow needs to be adjusted (reduced)</details>
</guidance>
</pv>
<pv name="MBL-080Crm:Cryo-TT-034:P_Limit_LOLO">
<description>Power coupler flange temperature too high</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>contact CRYO on-call and inform SCL on-call, power coupler flange temperature is too low, check heater output, if nominal then coupler flow needs to be adjusted (reduced)</details>
</guidance>
</pv>
<pv name="MBL-080Crm:Cryo-TT-044:P_Limit_HIHI">
<description>Power coupler flange temperature low</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>contact CRYO on-call and inform SCL on-call, power coupler flange temperature is too high, check heater output, if nominal then coupler flow needs to be adjusted (increased)</details>
</guidance>
</pv>
<pv name="MBL-080Crm:Cryo-TT-044:P_Limit_LO">
<description>Power coupler flange temperature too low</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>contact CRYO on-call and inform SCL on-call, power coupler flange temperature is too low, check heater output, if nominal then coupler flow needs to be adjusted (reduced)</details>
</guidance>
</pv>
<pv name="MBL-080Crm:Cryo-TT-043:P_Limit_LOLO">
<description>Power coupler flange temperature too high</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>contact CRYO on-call and inform SCL on-call, power coupler flange temperature is too low, check heater output, if nominal then coupler flow needs to be adjusted (reduced)</details>
</guidance>
</pv>
<pv name="MBL-080Crm:WtrC-FS-012:Flow_OK_WF">
<description>! Alarm when signal drops from 1 to zero. No Water Flow Antenna 1</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>contact CRYO on-call and inform SCL on-call, assure Flange temperature TT-014 is correct. Risk of Water freeze if no flow and temperature too low</details>
</guidance>
</pv>
<pv name="MBL-080Crm:WtrC-FS-022:Flow_OK_WF">
<description>! Alarm when signal drops from 1 to zero. No Water Flow Antenna 2</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>contact CRYO on-call and inform SCL on-call, assure Flange temperature TT-024 is correct. Risk of Water freeze if no flow and temperature too low</details>
</guidance>
</pv>
<pv name="MBL-080Crm:WtrC-FS-032:Flow_OK_WF">
<description>! Alarm when signal drops from 1 to zero. No Water Flow Antenna 3</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>contact CRYO on-call and inform SCL on-call, assure Flange temperature TT-034 is correct. Risk of Water freeze if no flow and temperature too low</details>
</guidance>
</pv>
<pv name="MBL-080Crm:WtrC-FS-042:Flow_OK_WF">
<description>! Alarm when signal drops from 1 to zero. No Water Flow Antenna 4</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>contact CRYO on-call and inform SCL on-call, assure Flange temperature TT-044 is correct. Risk of Water freeze if no flow and temperature too low</details>
</guidance>
</pv>
</component>
<component name="Cryomodules\MBL-090 Cryomodule">
<pv name="MBL-090Crm:Cryo-LT-001:HIHI">
<description>LT-001 helium level extremely high</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>contact CRYO on-call and inform SCL on-call, Cryomodule liquid level too high (check the other gauge LT-002). Close supply valve CV01, CV02</details>
</guidance>
</pv>
<pv name="MBL-090Crm:Cryo-LT-002:HIHI">
<description>LT-002 helium level extremely high</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>contact CRYO on-call and inform SCL on-call, Cryomodule liquid level too high (check the other gauge LT-001). Close supply valve CV01, CV02</details>
</guidance>
</pv>
<pv name="MBL-090Crm:Cryo-LT-001:HI">
<description>LT-001 helium level high</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>contact CRYO on-call and inform SCL on-call, Cryomodule liquid level high (check the other gauge LT-002). Check level regulation valve settings, if needed: adjust LMN_LO and if necessary: Close supply valve CV01, CV02</details>
</guidance>
</pv>
<pv name="MBL-090Crm:Cryo-LT-002:HI">
<description>LT-002 helium level high</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>contact CRYO on-call and inform SCL on-call, Cryomodule liquid level high (check the other gauge LT-002). Check level regulation valve settings, if needed: adjust LMN_LO and if necessary: Close supply valve CV01, CV02</details>
</guidance>
</pv>
<pv name="MBL-090Crm:Cryo-LT-001:LO">
<description>LT-001 helium level low</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>contact CRYO on-call and inform SCL on-call, Cryomodule liquid level low (check the other gauge LT-001). Check level regulation valve settings, if needed: adjust LMN_HI</details>
</guidance>
</pv>
<pv name="MBL-090Crm:Cryo-LT-002:LO">
<description>LT-002 helium level low</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>contact CRYO on-call and inform SCL on-call, Cryomodule liquid level low (check the other gauge LT-002). Check level regulation valvesettings, if needed: adjust LMN_HI</details>
</guidance>
</pv>
<pv name="MBL-090Crm:Cryo-LT-001:LOLO">
<description>LT-002 helium level extremely low</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>contact CRYO on-call and inform SCL on-call, Cryomodule liquid level too low (check the other gauge LT-001). Check level regulation valve settings, if needed: adjust LMN_HI</details>
</guidance>
</pv>
<pv name="MBL-090Crm:Cryo-LT-002:LOLO">
<description>LT-002 helium level extremely low</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>contact CRYO on-call and inform SCL on-call, Cryomodule liquid level too low (check the other gauge LT-002). Check level regulation valvesettings, if needed: adjust LMN_HI</details>
</guidance>
</pv>
<pv name="MBL-090Crm:Cryo-PT-003:HIHI">
<description>Cavity tanks pressure is too high (typical value is 31mbar in 2K mode and 1050mbar in 4K mode)</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>contact CRYO on-call and inform SCL on-call, Cryomodule bath pressure too high (check the other gauge PT002). Close supply valve CV01, CV02 if necessary</details>
</guidance>
</pv>
<pv name="MBL-090Crm:Cryo-PT-003:Cable_Error">
<description>Cavity tanks Pressure Sensor cables are disconnected</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>contact CRYO on-call and inform SCL on-call, Cryomodule pressure cable seems disconnected (value gets stuck), assign PT002 as measuring device on CV04 and CV-090 </details>
</guidance>
</pv>
<pv name="MBL-090Crm:Cryo-PT-004:HIHI">
<description>Cavity tanks pressure is too high (typical value is 31mbar in 2K mode and 1050mbar in 4K mode)</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>contact CRYO on-call and inform SCL on-call,, Cryomodule bath pressure too high (check the other gauge PT003). Close supply valve CV01, CV02 if necessary</details>
</guidance>
</pv>
<pv name="MBL-090Crm:Cryo-PT-004:Cable_Error">
<description>Cavity tanks Pressure Sensor cables are disconnected</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>contact CRYO on-call and inform SCL on-call, Cryomodule pressure cable seems disconnected (value gets stuck), assign PT003 as measuring device on CV04 and CV-090 </details>
</guidance>
</pv>
<pv name="MBL-090Crm:Cryo-TT-014:P_Limit_HIHI">
<description>Power coupler flange temperature too high</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>contact CRYO on-call and inform SCL on-call, power coupler flange temperature is too high, check heater output, if nominal then coupler flow needs to be adjusted (increased)</details>
</guidance>
</pv>
<pv name="MBL-090Crm:Cryo-TT-014:P_Limit_LO">
<description>Power coupler flange temperature too low</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>contact CRYO on-call and inform SCL on-call, power coupler flange temperature is too low, check heater output, if nominal then coupler flow needs to be adjusted (reduced)</details>
</guidance>
</pv>
<pv name="MBL-090Crm:Cryo-TT-014:P_Limit_LOLO">
<description>Power coupler flange temperature too low</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>contact CRYO on-call and inform SCL on-call, power coupler flange temperature is too low, check heater output, if nominal then coupler flow needs to be adjusted (reduced)</details>
</guidance>
</pv>
<pv name="MBL-090Crm:Cryo-TT-024:P_Limit_HIHI">
<description>Power coupler flange temperature low</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>contact CRYO on-call and inform SCL on-call, power coupler flange temperature is too high, check heater output, if nominal then coupler flow needs to be adjusted (increased)</details>
</guidance>
</pv>
<pv name="MBL-090Crm:Cryo-TT-024:P_Limit_LO">
<description>Power coupler flange temperature too low</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>contact CRYO on-call and inform SCL on-call, power coupler flange temperature is too low, check heater output, if nominal then coupler flow needs to be adjusted (reduced)</details>
</guidance>
</pv>
<pv name="MBL-090Crm:Cryo-TT-024:P_Limit_LOLO">
<description>Power coupler flange temperature too high</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>contact CRYO on-call and inform SCL on-call, power coupler flange temperature is too low, check heater output, if nominal then coupler flow needs to be adjusted (reduced)</details>
</guidance>
</pv>
<pv name="MBL-090Crm:Cryo-TT-034:P_Limit_HIHI">
<description>Power coupler flange temperature low</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>contact CRYO on-call and inform SCL on-call, power coupler flange temperature is too high, check heater output, if nominal then coupler flow needs to be adjusted (increased)</details>
</guidance>
</pv>
<pv name="MBL-090Crm:Cryo-TT-034:P_Limit_LO">
<description>Power coupler flange temperature too low</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>contact CRYO on-call and inform SCL on-call, power coupler flange temperature is too low, check heater output, if nominal then coupler flow needs to be adjusted (reduced)</details>
</guidance>
</pv>
<pv name="MBL-090Crm:Cryo-TT-034:P_Limit_LOLO">
<description>Power coupler flange temperature too high</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>contact CRYO on-call and inform SCL on-call, power coupler flange temperature is too low, check heater output, if nominal then coupler flow needs to be adjusted (reduced)</details>
</guidance>
</pv>
<pv name="MBL-090Crm:Cryo-TT-044:P_Limit_HIHI">
<description>Power coupler flange temperature low</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>contact CRYO on-call and inform SCL on-call, power coupler flange temperature is too high, check heater output, if nominal then coupler flow needs to be adjusted (increased)</details>
</guidance>
</pv>
<pv name="MBL-090Crm:Cryo-TT-044:P_Limit_LO">
<description>Power coupler flange temperature too low</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>contact CRYO on-call and inform SCL on-call, power coupler flange temperature is too low, check heater output, if nominal then coupler flow needs to be adjusted (reduced)</details>
</guidance>
</pv>
<pv name="MBL-090Crm:Cryo-TT-043:P_Limit_LOLO">
<description>Power coupler flange temperature too high</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>contact CRYO on-call and inform SCL on-call, power coupler flange temperature is too low, check heater output, if nominal then coupler flow needs to be adjusted (reduced)</details>
</guidance>
</pv>
<pv name="MBL-090Crm:WtrC-FS-012:Flow_OK_WF">
<description>! Alarm when signal drops from 1 to zero. No Water Flow Antenna 1</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>contact CRYO on-call and inform SCL on-call, assure Flange temperature TT-014 is correct. Risk of Water freeze if no flow and temperature too low</details>
</guidance>
</pv>
<pv name="MBL-090Crm:WtrC-FS-022:Flow_OK_WF">
<description>! Alarm when signal drops from 1 to zero. No Water Flow Antenna 2</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>contact CRYO on-call and inform SCL on-call, assure Flange temperature TT-024 is correct. Risk of Water freeze if no flow and temperature too low</details>
</guidance>
</pv>
<pv name="MBL-090Crm:WtrC-FS-032:Flow_OK_WF">
<description>! Alarm when signal drops from 1 to zero. No Water Flow Antenna 3</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>contact CRYO on-call and inform SCL on-call, assure Flange temperature TT-034 is correct. Risk of Water freeze if no flow and temperature too low</details>
</guidance>
</pv>
<pv name="MBL-090Crm:WtrC-FS-042:Flow_OK_WF">
<description>! Alarm when signal drops from 1 to zero. No Water Flow Antenna 4</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>contact CRYO on-call and inform SCL on-call, assure Flange temperature TT-044 is correct. Risk of Water freeze if no flow and temperature too low</details>
</guidance>
</pv>
</component>
<component name="Cryomodules\HBL-010 Cryomodule">
<pv name="HBL-010Crm:Cryo-LT-001:HIHI">
<description>LT-001 helium level extremely high</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>contact CRYO on-call and inform SCL on-call, Cryomodule liquid level too high (check the other gauge LT-002). Close supply valve CV01, CV02</details>
</guidance>
</pv>
<pv name="HBL-010Crm:Cryo-LT-002:HIHI">
<description>LT-002 helium level extremely high</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>contact CRYO on-call and inform SCL on-call, Cryomodule liquid level too high (check the other gauge LT-001). Close supply valve CV01, CV02</details>
</guidance>
</pv>
<pv name="HBL-010Crm:Cryo-LT-001:HI">
<description>LT-001 helium level high</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>contact CRYO on-call and inform SCL on-call, Cryomodule liquid level high (check the other gauge LT-002). Check level regulation valve settings, if needed: adjust LMN_LO and if necessary: Close supply valve CV01, CV02</details>
</guidance>
</pv>
<pv name="HBL-010Crm:Cryo-LT-002:HI">
<description>LT-002 helium level high</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>contact CRYO on-call and inform SCL on-call, Cryomodule liquid level high (check the other gauge LT-002). Check level regulation valve settings, if needed: adjust LMN_LO and if necessary: Close supply valve CV01, CV02</details>
</guidance>
</pv>
<pv name="HBL-010Crm:Cryo-LT-001:LO">
<description>LT-001 helium level low</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>contact CRYO on-call and inform SCL on-call, Cryomodule liquid level low (check the other gauge LT-001). Check level regulation valve settings, if needed: adjust LMN_HI</details>
</guidance>
</pv>
<pv name="HBL-010Crm:Cryo-LT-002:LO">
<description>LT-002 helium level low</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>contact CRYO on-call and inform SCL on-call, Cryomodule liquid level low (check the other gauge LT-002). Check level regulation valvesettings, if needed: adjust LMN_HI</details>
</guidance>
</pv>
<pv name="HBL-010Crm:Cryo-LT-001:LOLO">
<description>LT-002 helium level extremely low</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>contact CRYO on-call and inform SCL on-call, Cryomodule liquid level too low (check the other gauge LT-001). Check level regulation valve settings, if needed: adjust LMN_HI</details>
</guidance>
</pv>
<pv name="HBL-010Crm:Cryo-LT-002:LOLO">
<description>LT-002 helium level extremely low</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>contact CRYO on-call and inform SCL on-call, Cryomodule liquid level too low (check the other gauge LT-002). Check level regulation valvesettings, if needed: adjust LMN_HI</details>
</guidance>
</pv>
<pv name="HBL-010Crm:Cryo-PT-003:HIHI">
<description>Cavity tanks pressure is too high (typical value is 31mbar in 2K mode and 1050mbar in 4K mode)</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>contact CRYO on-call and inform SCL on-call, Cryomodule bath pressure too high (check the other gauge PT002). Close supply valve CV01, CV02 if necessary</details>
</guidance>
</pv>
<pv name="HBL-010Crm:Cryo-PT-003:Cable_Error">
<description>Cavity tanks Pressure Sensor cables are disconnected</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>contact CRYO on-call and inform SCL on-call, Cryomodule pressure cable seems disconnected (value gets stuck), assign PT002 as measuring device on CV04 and CV-090 </details>
</guidance>
</pv>
<pv name="HBL-010Crm:Cryo-PT-004:HIHI">
<description>Cavity tanks pressure is too high (typical value is 31mbar in 2K mode and 1050mbar in 4K mode)</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>contact CRYO on-call and inform SCL on-call,, Cryomodule bath pressure too high (check the other gauge PT003). Close supply valve CV01, CV02 if necessary</details>
</guidance>
</pv>
<pv name="HBL-010Crm:Cryo-PT-004:Cable_Error">
<description>Cavity tanks Pressure Sensor cables are disconnected</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>contact CRYO on-call and inform SCL on-call, Cryomodule pressure cable seems disconnected (value gets stuck), assign PT003 as measuring device on CV04 and CV-090 </details>
</guidance>
</pv>
<pv name="HBL-010Crm:Cryo-TT-014:P_Limit_HIHI">
<description>Power coupler flange temperature too high</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>contact CRYO on-call and inform SCL on-call, power coupler flange temperature is too high, check heater output, if nominal then coupler flow needs to be adjusted (increased)</details>
</guidance>
</pv>
<pv name="HBL-010Crm:Cryo-TT-014:P_Limit_LO">
<description>Power coupler flange temperature too low</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>contact CRYO on-call and inform SCL on-call, power coupler flange temperature is too low, check heater output, if nominal then coupler flow needs to be adjusted (reduced)</details>
</guidance>
</pv>
<pv name="HBL-010Crm:Cryo-TT-014:P_Limit_LOLO">
<description>Power coupler flange temperature too low</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>contact CRYO on-call and inform SCL on-call, power coupler flange temperature is too low, check heater output, if nominal then coupler flow needs to be adjusted (reduced)</details>
</guidance>
</pv>
<pv name="HBL-010Crm:Cryo-TT-024:P_Limit_HIHI">
<description>Power coupler flange temperature low</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>contact CRYO on-call and inform SCL on-call, power coupler flange temperature is too high, check heater output, if nominal then coupler flow needs to be adjusted (increased)</details>
</guidance>
</pv>
<pv name="HBL-010Crm:Cryo-TT-024:P_Limit_LO">
<description>Power coupler flange temperature too low</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>contact CRYO on-call and inform SCL on-call, power coupler flange temperature is too low, check heater output, if nominal then coupler flow needs to be adjusted (reduced)</details>
</guidance>
</pv>
<pv name="HBL-010Crm:Cryo-TT-024:P_Limit_LOLO">
<description>Power coupler flange temperature too high</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>contact CRYO on-call and inform SCL on-call, power coupler flange temperature is too low, check heater output, if nominal then coupler flow needs to be adjusted (reduced)</details>
</guidance>
</pv>
<pv name="HBL-010Crm:Cryo-TT-034:P_Limit_HIHI">
<description>Power coupler flange temperature low</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>contact CRYO on-call and inform SCL on-call, power coupler flange temperature is too high, check heater output, if nominal then coupler flow needs to be adjusted (increased)</details>
</guidance>
</pv>
<pv name="HBL-010Crm:Cryo-TT-034:P_Limit_LO">
<description>Power coupler flange temperature too low</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>contact CRYO on-call and inform SCL on-call, power coupler flange temperature is too low, check heater output, if nominal then coupler flow needs to be adjusted (reduced)</details>
</guidance>
</pv>
<pv name="HBL-010Crm:Cryo-TT-034:P_Limit_LOLO">
<description>Power coupler flange temperature too high</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>contact CRYO on-call and inform SCL on-call, power coupler flange temperature is too low, check heater output, if nominal then coupler flow needs to be adjusted (reduced)</details>
</guidance>
</pv>
<pv name="HBL-010Crm:Cryo-TT-044:P_Limit_HIHI">
<description>Power coupler flange temperature low</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>contact CRYO on-call and inform SCL on-call, power coupler flange temperature is too high, check heater output, if nominal then coupler flow needs to be adjusted (increased)</details>
</guidance>
</pv>
<pv name="HBL-010Crm:Cryo-TT-044:P_Limit_LO">
<description>Power coupler flange temperature too low</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>contact CRYO on-call and inform SCL on-call, power coupler flange temperature is too low, check heater output, if nominal then coupler flow needs to be adjusted (reduced)</details>
</guidance>
</pv>
<pv name="HBL-010Crm:Cryo-TT-043:P_Limit_LOLO">
<description>Power coupler flange temperature too high</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>contact CRYO on-call and inform SCL on-call, power coupler flange temperature is too low, check heater output, if nominal then coupler flow needs to be adjusted (reduced)</details>
</guidance>
</pv>
<pv name="HBL-010Crm:WtrC-FS-012:Flow_OK_WF">
<description>! Alarm when signal drops from 1 to zero. No Water Flow Antenna 1</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>contact CRYO on-call and inform SCL on-call, assure Flange temperature TT-014 is correct. Risk of Water freeze if no flow and temperature too low</details>
</guidance>
</pv>
<pv name="HBL-010Crm:WtrC-FS-022:Flow_OK_WF">
<description>! Alarm when signal drops from 1 to zero. No Water Flow Antenna 2</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>contact CRYO on-call and inform SCL on-call, assure Flange temperature TT-024 is correct. Risk of Water freeze if no flow and temperature too low</details>
</guidance>
</pv>
<pv name="HBL-010Crm:WtrC-FS-032:Flow_OK_WF">
<description>! Alarm when signal drops from 1 to zero. No Water Flow Antenna 3</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>contact CRYO on-call and inform SCL on-call, assure Flange temperature TT-034 is correct. Risk of Water freeze if no flow and temperature too low</details>
</guidance>
</pv>
<pv name="HBL-010Crm:WtrC-FS-042:Flow_OK_WF">
<description>! Alarm when signal drops from 1 to zero. No Water Flow Antenna 4</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>contact CRYO on-call and inform SCL on-call, assure Flange temperature TT-044 is correct. Risk of Water freeze if no flow and temperature too low</details>
</guidance>
</pv>
</component>
<component name="Cryomodules\HBL-020 Cryomodule">
<pv name="HBL-020Crm:Cryo-LT-001:HIHI">
<description>LT-001 helium level extremely high</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>contact CRYO on-call and inform SCL on-call, Cryomodule liquid level too high (check the other gauge LT-002). Close supply valve CV01, CV02</details>
</guidance>
</pv>
<pv name="HBL-020Crm:Cryo-LT-002:HIHI">
<description>LT-002 helium level extremely high</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>contact CRYO on-call and inform SCL on-call, Cryomodule liquid level too high (check the other gauge LT-001). Close supply valve CV01, CV02</details>
</guidance>
</pv>
<pv name="HBL-020Crm:Cryo-LT-001:HI">
<description>LT-001 helium level high</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>contact CRYO on-call and inform SCL on-call, Cryomodule liquid level high (check the other gauge LT-002). Check level regulation valve settings, if needed: adjust LMN_LO and if necessary: Close supply valve CV01, CV02</details>
</guidance>
</pv>
<pv name="HBL-020Crm:Cryo-LT-002:HI">
<description>LT-002 helium level high</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>contact CRYO on-call and inform SCL on-call, Cryomodule liquid level high (check the other gauge LT-002). Check level regulation valve settings, if needed: adjust LMN_LO and if necessary: Close supply valve CV01, CV02</details>
</guidance>
</pv>
<pv name="HBL-020Crm:Cryo-LT-001:LO">
<description>LT-001 helium level low</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>contact CRYO on-call and inform SCL on-call, Cryomodule liquid level low (check the other gauge LT-001). Check level regulation valve settings, if needed: adjust LMN_HI</details>
</guidance>
</pv>
<pv name="HBL-020Crm:Cryo-LT-002:LO">
<description>LT-002 helium level low</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>contact CRYO on-call and inform SCL on-call, Cryomodule liquid level low (check the other gauge LT-002). Check level regulation valvesettings, if needed: adjust LMN_HI</details>
</guidance>
</pv>
<pv name="HBL-020Crm:Cryo-LT-001:LOLO">
<description>LT-002 helium level extremely low</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>contact CRYO on-call and inform SCL on-call, Cryomodule liquid level too low (check the other gauge LT-001). Check level regulation valve settings, if needed: adjust LMN_HI</details>
</guidance>
</pv>
<pv name="HBL-020Crm:Cryo-LT-002:LOLO">
<description>LT-002 helium level extremely low</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>contact CRYO on-call and inform SCL on-call, Cryomodule liquid level too low (check the other gauge LT-002). Check level regulation valvesettings, if needed: adjust LMN_HI</details>
</guidance>
</pv>
<pv name="HBL-020Crm:Cryo-PT-003:HIHI">
<description>Cavity tanks pressure is too high (typical value is 31mbar in 2K mode and 1050mbar in 4K mode)</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>contact CRYO on-call and inform SCL on-call, Cryomodule bath pressure too high (check the other gauge PT002). Close supply valve CV01, CV02 if necessary</details>
</guidance>
</pv>
<pv name="HBL-020Crm:Cryo-PT-003:Cable_Error">
<description>Cavity tanks Pressure Sensor cables are disconnected</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>contact CRYO on-call and inform SCL on-call, Cryomodule pressure cable seems disconnected (value gets stuck), assign PT002 as measuring device on CV04 and CV-090 </details>
</guidance>
</pv>
<pv name="HBL-020Crm:Cryo-PT-004:HIHI">
<description>Cavity tanks pressure is too high (typical value is 31mbar in 2K mode and 1050mbar in 4K mode)</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>contact CRYO on-call and inform SCL on-call,, Cryomodule bath pressure too high (check the other gauge PT003). Close supply valve CV01, CV02 if necessary</details>
</guidance>
</pv>
<pv name="HBL-020Crm:Cryo-PT-004:Cable_Error">
<description>Cavity tanks Pressure Sensor cables are disconnected</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>contact CRYO on-call and inform SCL on-call, Cryomodule pressure cable seems disconnected (value gets stuck), assign PT003 as measuring device on CV04 and CV-090 </details>
</guidance>
</pv>
<pv name="HBL-020Crm:Cryo-TT-014:P_Limit_HIHI">
<description>Power coupler flange temperature too high</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>contact CRYO on-call and inform SCL on-call, power coupler flange temperature is too high, check heater output, if nominal then coupler flow needs to be adjusted (increased)</details>
</guidance>
</pv>
<pv name="HBL-020Crm:Cryo-TT-014:P_Limit_LO">
<description>Power coupler flange temperature too low</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>contact CRYO on-call and inform SCL on-call, power coupler flange temperature is too low, check heater output, if nominal then coupler flow needs to be adjusted (reduced)</details>
</guidance>
</pv>
<pv name="HBL-020Crm:Cryo-TT-014:P_Limit_LOLO">
<description>Power coupler flange temperature too low</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>contact CRYO on-call and inform SCL on-call, power coupler flange temperature is too low, check heater output, if nominal then coupler flow needs to be adjusted (reduced)</details>
</guidance>
</pv>
<pv name="HBL-020Crm:Cryo-TT-024:P_Limit_HIHI">
<description>Power coupler flange temperature low</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>contact CRYO on-call and inform SCL on-call, power coupler flange temperature is too high, check heater output, if nominal then coupler flow needs to be adjusted (increased)</details>
</guidance>
</pv>
<pv name="HBL-020Crm:Cryo-TT-024:P_Limit_LO">
<description>Power coupler flange temperature too low</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>contact CRYO on-call and inform SCL on-call, power coupler flange temperature is too low, check heater output, if nominal then coupler flow needs to be adjusted (reduced)</details>
</guidance>
</pv>
<pv name="HBL-020Crm:Cryo-TT-024:P_Limit_LOLO">
<description>Power coupler flange temperature too high</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>contact CRYO on-call and inform SCL on-call, power coupler flange temperature is too low, check heater output, if nominal then coupler flow needs to be adjusted (reduced)</details>
</guidance>
</pv>
<pv name="HBL-020Crm:Cryo-TT-034:P_Limit_HIHI">
<description>Power coupler flange temperature low</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>contact CRYO on-call and inform SCL on-call, power coupler flange temperature is too high, check heater output, if nominal then coupler flow needs to be adjusted (increased)</details>
</guidance>
</pv>
<pv name="HBL-020Crm:Cryo-TT-034:P_Limit_LO">
<description>Power coupler flange temperature too low</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>contact CRYO on-call and inform SCL on-call, power coupler flange temperature is too low, check heater output, if nominal then coupler flow needs to be adjusted (reduced)</details>
</guidance>
</pv>
<pv name="HBL-020Crm:Cryo-TT-034:P_Limit_LOLO">
<description>Power coupler flange temperature too high</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>contact CRYO on-call and inform SCL on-call, power coupler flange temperature is too low, check heater output, if nominal then coupler flow needs to be adjusted (reduced)</details>
</guidance>
</pv>
<pv name="HBL-020Crm:Cryo-TT-044:P_Limit_HIHI">
<description>Power coupler flange temperature low</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>contact CRYO on-call and inform SCL on-call, power coupler flange temperature is too high, check heater output, if nominal then coupler flow needs to be adjusted (increased)</details>
</guidance>
</pv>
<pv name="HBL-020Crm:Cryo-TT-044:P_Limit_LO">
<description>Power coupler flange temperature too low</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>contact CRYO on-call and inform SCL on-call, power coupler flange temperature is too low, check heater output, if nominal then coupler flow needs to be adjusted (reduced)</details>
</guidance>
</pv>
<pv name="HBL-020Crm:Cryo-TT-043:P_Limit_LOLO">
<description>Power coupler flange temperature too high</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>contact CRYO on-call and inform SCL on-call, power coupler flange temperature is too low, check heater output, if nominal then coupler flow needs to be adjusted (reduced)</details>
</guidance>
</pv>
<pv name="HBL-020Crm:WtrC-FS-012:Flow_OK_WF">
<description>! Alarm when signal drops from 1 to zero. No Water Flow Antenna 1</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>contact CRYO on-call and inform SCL on-call, assure Flange temperature TT-014 is correct. Risk of Water freeze if no flow and temperature too low</details>
</guidance>
</pv>
<pv name="HBL-020Crm:WtrC-FS-022:Flow_OK_WF">
<description>! Alarm when signal drops from 1 to zero. No Water Flow Antenna 2</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>contact CRYO on-call and inform SCL on-call, assure Flange temperature TT-024 is correct. Risk of Water freeze if no flow and temperature too low</details>
</guidance>
</pv>
<pv name="HBL-020Crm:WtrC-FS-032:Flow_OK_WF">
<description>! Alarm when signal drops from 1 to zero. No Water Flow Antenna 3</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>contact CRYO on-call and inform SCL on-call, assure Flange temperature TT-034 is correct. Risk of Water freeze if no flow and temperature too low</details>
</guidance>
</pv>
<pv name="HBL-020Crm:WtrC-FS-042:Flow_OK_WF">
<description>! Alarm when signal drops from 1 to zero. No Water Flow Antenna 4</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>contact CRYO on-call and inform SCL on-call, assure Flange temperature TT-044 is correct. Risk of Water freeze if no flow and temperature too low</details>
</guidance>
</pv>
</component>
<component name="Cryomodules\HBL-030 Cryomodule">
<pv name="HBL-030Crm:Cryo-LT-001:HIHI">
<description>LT-001 helium level extremely high</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>contact CRYO on-call and inform SCL on-call, Cryomodule liquid level too high (check the other gauge LT-002). Close supply valve CV01, CV02</details>
</guidance>
</pv>
<pv name="HBL-030Crm:Cryo-LT-002:HIHI">
<description>LT-002 helium level extremely high</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>contact CRYO on-call and inform SCL on-call, Cryomodule liquid level too high (check the other gauge LT-001). Close supply valve CV01, CV02</details>
</guidance>
</pv>
<pv name="HBL-030Crm:Cryo-LT-001:HI">
<description>LT-001 helium level high</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>contact CRYO on-call and inform SCL on-call, Cryomodule liquid level high (check the other gauge LT-002). Check level regulation valve settings, if needed: adjust LMN_LO and if necessary: Close supply valve CV01, CV02</details>
</guidance>
</pv>
<pv name="HBL-030Crm:Cryo-LT-002:HI">
<description>LT-002 helium level high</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>contact CRYO on-call and inform SCL on-call, Cryomodule liquid level high (check the other gauge LT-002). Check level regulation valve settings, if needed: adjust LMN_LO and if necessary: Close supply valve CV01, CV02</details>
</guidance>
</pv>
<pv name="HBL-030Crm:Cryo-LT-001:LO">
<description>LT-001 helium level low</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>contact CRYO on-call and inform SCL on-call, Cryomodule liquid level low (check the other gauge LT-001). Check level regulation valve settings, if needed: adjust LMN_HI</details>
</guidance>
</pv>
<pv name="HBL-030Crm:Cryo-LT-002:LO">
<description>LT-002 helium level low</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>contact CRYO on-call and inform SCL on-call, Cryomodule liquid level low (check the other gauge LT-002). Check level regulation valvesettings, if needed: adjust LMN_HI</details>
</guidance>
</pv>
<pv name="HBL-030Crm:Cryo-LT-001:LOLO">
<description>LT-002 helium level extremely low</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>contact CRYO on-call and inform SCL on-call, Cryomodule liquid level too low (check the other gauge LT-001). Check level regulation valve settings, if needed: adjust LMN_HI</details>
</guidance>
</pv>
<pv name="HBL-030Crm:Cryo-LT-002:LOLO">
<description>LT-002 helium level extremely low</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>contact CRYO on-call and inform SCL on-call, Cryomodule liquid level too low (check the other gauge LT-002). Check level regulation valvesettings, if needed: adjust LMN_HI</details>
</guidance>
</pv>
<pv name="HBL-030Crm:Cryo-PT-003:HIHI">
<description>Cavity tanks pressure is too high (typical value is 31mbar in 2K mode and 1050mbar in 4K mode)</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>contact CRYO on-call and inform SCL on-call, Cryomodule bath pressure too high (check the other gauge PT002). Close supply valve CV01, CV02 if necessary</details>
</guidance>
</pv>
<pv name="HBL-030Crm:Cryo-PT-003:Cable_Error">
<description>Cavity tanks Pressure Sensor cables are disconnected</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>contact CRYO on-call and inform SCL on-call, Cryomodule pressure cable seems disconnected (value gets stuck), assign PT002 as measuring device on CV04 and CV-090 </details>
</guidance>
</pv>
<pv name="HBL-030Crm:Cryo-PT-004:HIHI">
<description>Cavity tanks pressure is too high (typical value is 31mbar in 2K mode and 1050mbar in 4K mode)</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>contact CRYO on-call and inform SCL on-call,, Cryomodule bath pressure too high (check the other gauge PT003). Close supply valve CV01, CV02 if necessary</details>
</guidance>
</pv>
<pv name="HBL-030Crm:Cryo-PT-004:Cable_Error">
<description>Cavity tanks Pressure Sensor cables are disconnected</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>contact CRYO on-call and inform SCL on-call, Cryomodule pressure cable seems disconnected (value gets stuck), assign PT003 as measuring device on CV04 and CV-090 </details>
</guidance>
</pv>
<pv name="HBL-030Crm:Cryo-TT-014:P_Limit_HIHI">
<description>Power coupler flange temperature too high</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>contact CRYO on-call and inform SCL on-call, power coupler flange temperature is too high, check heater output, if nominal then coupler flow needs to be adjusted (increased)</details>
</guidance>
</pv>
<pv name="HBL-030Crm:Cryo-TT-014:P_Limit_LO">
<description>Power coupler flange temperature too low</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>contact CRYO on-call and inform SCL on-call, power coupler flange temperature is too low, check heater output, if nominal then coupler flow needs to be adjusted (reduced)</details>
</guidance>
</pv>
<pv name="HBL-030Crm:Cryo-TT-014:P_Limit_LOLO">
<description>Power coupler flange temperature too low</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>contact CRYO on-call and inform SCL on-call, power coupler flange temperature is too low, check heater output, if nominal then coupler flow needs to be adjusted (reduced)</details>
</guidance>
</pv>
<pv name="HBL-030Crm:Cryo-TT-024:P_Limit_HIHI">
<description>Power coupler flange temperature low</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>contact CRYO on-call and inform SCL on-call, power coupler flange temperature is too high, check heater output, if nominal then coupler flow needs to be adjusted (increased)</details>
</guidance>
</pv>
<pv name="HBL-030Crm:Cryo-TT-024:P_Limit_LO">
<description>Power coupler flange temperature too low</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>contact CRYO on-call and inform SCL on-call, power coupler flange temperature is too low, check heater output, if nominal then coupler flow needs to be adjusted (reduced)</details>
</guidance>
</pv>
<pv name="HBL-030Crm:Cryo-TT-024:P_Limit_LOLO">
<description>Power coupler flange temperature too high</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>contact CRYO on-call and inform SCL on-call, power coupler flange temperature is too low, check heater output, if nominal then coupler flow needs to be adjusted (reduced)</details>
</guidance>
</pv>
<pv name="HBL-030Crm:Cryo-TT-034:P_Limit_HIHI">
<description>Power coupler flange temperature low</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>contact CRYO on-call and inform SCL on-call, power coupler flange temperature is too high, check heater output, if nominal then coupler flow needs to be adjusted (increased)</details>
</guidance>
</pv>
<pv name="HBL-030Crm:Cryo-TT-034:P_Limit_LO">
<description>Power coupler flange temperature too low</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>contact CRYO on-call and inform SCL on-call, power coupler flange temperature is too low, check heater output, if nominal then coupler flow needs to be adjusted (reduced)</details>
</guidance>
</pv>
<pv name="HBL-030Crm:Cryo-TT-034:P_Limit_LOLO">
<description>Power coupler flange temperature too high</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>contact CRYO on-call and inform SCL on-call, power coupler flange temperature is too low, check heater output, if nominal then coupler flow needs to be adjusted (reduced)</details>
</guidance>
</pv>
<pv name="HBL-030Crm:Cryo-TT-044:P_Limit_HIHI">
<description>Power coupler flange temperature low</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>contact CRYO on-call and inform SCL on-call, power coupler flange temperature is too high, check heater output, if nominal then coupler flow needs to be adjusted (increased)</details>
</guidance>
</pv>
<pv name="HBL-030Crm:Cryo-TT-044:P_Limit_LO">
<description>Power coupler flange temperature too low</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>contact CRYO on-call and inform SCL on-call, power coupler flange temperature is too low, check heater output, if nominal then coupler flow needs to be adjusted (reduced)</details>
</guidance>
</pv>
<pv name="HBL-030Crm:Cryo-TT-043:P_Limit_LOLO">
<description>Power coupler flange temperature too high</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>contact CRYO on-call and inform SCL on-call, power coupler flange temperature is too low, check heater output, if nominal then coupler flow needs to be adjusted (reduced)</details>
</guidance>
</pv>
<pv name="HBL-030Crm:WtrC-FS-012:Flow_OK_WF">
<description>! Alarm when signal drops from 1 to zero. No Water Flow Antenna 1</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>contact CRYO on-call and inform SCL on-call, assure Flange temperature TT-014 is correct. Risk of Water freeze if no flow and temperature too low</details>
</guidance>
</pv>
<pv name="HBL-030Crm:WtrC-FS-022:Flow_OK_WF">
<description>! Alarm when signal drops from 1 to zero. No Water Flow Antenna 2</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>contact CRYO on-call and inform SCL on-call, assure Flange temperature TT-024 is correct. Risk of Water freeze if no flow and temperature too low</details>
</guidance>
</pv>
<pv name="HBL-030Crm:WtrC-FS-032:Flow_OK_WF">
<description>! Alarm when signal drops from 1 to zero. No Water Flow Antenna 3</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>contact CRYO on-call and inform SCL on-call, assure Flange temperature TT-034 is correct. Risk of Water freeze if no flow and temperature too low</details>
</guidance>
</pv>
<pv name="HBL-030Crm:WtrC-FS-042:Flow_OK_WF">
<description>! Alarm when signal drops from 1 to zero. No Water Flow Antenna 4</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>contact CRYO on-call and inform SCL on-call, assure Flange temperature TT-044 is correct. Risk of Water freeze if no flow and temperature too low</details>
</guidance>
</pv>
</component>
<component name="Cryomodules\HBL-040 Cryomodule">
<pv name="HBL-040Crm:Cryo-LT-001:HIHI">
<description>LT-001 helium level extremely high</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>contact CRYO on-call and inform SCL on-call, Cryomodule liquid level too high (check the other gauge LT-002). Close supply valve CV01, CV02</details>
</guidance>
</pv>
<pv name="HBL-040Crm:Cryo-LT-002:HIHI">
<description>LT-002 helium level extremely high</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>contact CRYO on-call and inform SCL on-call, Cryomodule liquid level too high (check the other gauge LT-001). Close supply valve CV01, CV02</details>
</guidance>
</pv>
<pv name="HBL-040Crm:Cryo-LT-001:HI">
<description>LT-001 helium level high</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>contact CRYO on-call and inform SCL on-call, Cryomodule liquid level high (check the other gauge LT-002). Check level regulation valve settings, if needed: adjust LMN_LO and if necessary: Close supply valve CV01, CV02</details>
</guidance>
</pv>
<pv name="HBL-040Crm:Cryo-LT-002:HI">
<description>LT-002 helium level high</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>contact CRYO on-call and inform SCL on-call, Cryomodule liquid level high (check the other gauge LT-002). Check level regulation valve settings, if needed: adjust LMN_LO and if necessary: Close supply valve CV01, CV02</details>
</guidance>
</pv>
<pv name="HBL-040Crm:Cryo-LT-001:LO">
<description>LT-001 helium level low</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>contact CRYO on-call and inform SCL on-call, Cryomodule liquid level low (check the other gauge LT-001). Check level regulation valve settings, if needed: adjust LMN_HI</details>
</guidance>
</pv>
<pv name="HBL-040Crm:Cryo-LT-002:LO">
<description>LT-002 helium level low</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>contact CRYO on-call and inform SCL on-call, Cryomodule liquid level low (check the other gauge LT-002). Check level regulation valvesettings, if needed: adjust LMN_HI</details>
</guidance>
</pv>
<pv name="HBL-040Crm:Cryo-LT-001:LOLO">
<description>LT-002 helium level extremely low</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>contact CRYO on-call and inform SCL on-call, Cryomodule liquid level too low (check the other gauge LT-001). Check level regulation valve settings, if needed: adjust LMN_HI</details>
</guidance>
</pv>
<pv name="HBL-040Crm:Cryo-LT-002:LOLO">
<description>LT-002 helium level extremely low</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>contact CRYO on-call and inform SCL on-call, Cryomodule liquid level too low (check the other gauge LT-002). Check level regulation valvesettings, if needed: adjust LMN_HI</details>
</guidance>
</pv>
<pv name="HBL-040Crm:Cryo-PT-003:HIHI">
<description>Cavity tanks pressure is too high (typical value is 31mbar in 2K mode and 1050mbar in 4K mode)</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>contact CRYO on-call and inform SCL on-call, Cryomodule bath pressure too high (check the other gauge PT002). Close supply valve CV01, CV02 if necessary</details>
</guidance>
</pv>
<pv name="HBL-040Crm:Cryo-PT-003:Cable_Error">
<description>Cavity tanks Pressure Sensor cables are disconnected</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>contact CRYO on-call and inform SCL on-call, Cryomodule pressure cable seems disconnected (value gets stuck), assign PT002 as measuring device on CV04 and CV-090 </details>
</guidance>
</pv>
<pv name="HBL-040Crm:Cryo-PT-004:HIHI">
<description>Cavity tanks pressure is too high (typical value is 31mbar in 2K mode and 1050mbar in 4K mode)</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>contact CRYO on-call and inform SCL on-call,, Cryomodule bath pressure too high (check the other gauge PT003). Close supply valve CV01, CV02 if necessary</details>
</guidance>
</pv>
<pv name="HBL-040Crm:Cryo-PT-004:Cable_Error">
<description>Cavity tanks Pressure Sensor cables are disconnected</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>contact CRYO on-call and inform SCL on-call, Cryomodule pressure cable seems disconnected (value gets stuck), assign PT003 as measuring device on CV04 and CV-090 </details>
</guidance>
</pv>
<pv name="HBL-040Crm:Cryo-TT-014:P_Limit_HIHI">
<description>Power coupler flange temperature too high</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>contact CRYO on-call and inform SCL on-call, power coupler flange temperature is too high, check heater output, if nominal then coupler flow needs to be adjusted (increased)</details>
</guidance>
</pv>
<pv name="HBL-040Crm:Cryo-TT-014:P_Limit_LO">
<description>Power coupler flange temperature too low</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>contact CRYO on-call and inform SCL on-call, power coupler flange temperature is too low, check heater output, if nominal then coupler flow needs to be adjusted (reduced)</details>
</guidance>
</pv>
<pv name="HBL-040Crm:Cryo-TT-014:P_Limit_LOLO">
<description>Power coupler flange temperature too low</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>contact CRYO on-call and inform SCL on-call, power coupler flange temperature is too low, check heater output, if nominal then coupler flow needs to be adjusted (reduced)</details>
</guidance>
</pv>
<pv name="HBL-040Crm:Cryo-TT-024:P_Limit_HIHI">
<description>Power coupler flange temperature low</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>contact CRYO on-call and inform SCL on-call, power coupler flange temperature is too high, check heater output, if nominal then coupler flow needs to be adjusted (increased)</details>
</guidance>
</pv>
<pv name="HBL-040Crm:Cryo-TT-024:P_Limit_LO">
<description>Power coupler flange temperature too low</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>contact CRYO on-call and inform SCL on-call, power coupler flange temperature is too low, check heater output, if nominal then coupler flow needs to be adjusted (reduced)</details>
</guidance>
</pv>
<pv name="HBL-040Crm:Cryo-TT-024:P_Limit_LOLO">
<description>Power coupler flange temperature too high</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>contact CRYO on-call and inform SCL on-call, power coupler flange temperature is too low, check heater output, if nominal then coupler flow needs to be adjusted (reduced)</details>
</guidance>
</pv>
<pv name="HBL-040Crm:Cryo-TT-034:P_Limit_HIHI">
<description>Power coupler flange temperature low</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>contact CRYO on-call and inform SCL on-call, power coupler flange temperature is too high, check heater output, if nominal then coupler flow needs to be adjusted (increased)</details>
</guidance>
</pv>
<pv name="HBL-040Crm:Cryo-TT-034:P_Limit_LO">
<description>Power coupler flange temperature too low</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>contact CRYO on-call and inform SCL on-call, power coupler flange temperature is too low, check heater output, if nominal then coupler flow needs to be adjusted (reduced)</details>
</guidance>
</pv>
<pv name="HBL-040Crm:Cryo-TT-034:P_Limit_LOLO">
<description>Power coupler flange temperature too high</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>contact CRYO on-call and inform SCL on-call, power coupler flange temperature is too low, check heater output, if nominal then coupler flow needs to be adjusted (reduced)</details>
</guidance>
</pv>
<pv name="HBL-040Crm:Cryo-TT-044:P_Limit_HIHI">
<description>Power coupler flange temperature low</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>contact CRYO on-call and inform SCL on-call, power coupler flange temperature is too high, check heater output, if nominal then coupler flow needs to be adjusted (increased)</details>
</guidance>
</pv>
<pv name="HBL-040Crm:Cryo-TT-044:P_Limit_LO">
<description>Power coupler flange temperature too low</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>contact CRYO on-call and inform SCL on-call, power coupler flange temperature is too low, check heater output, if nominal then coupler flow needs to be adjusted (reduced)</details>
</guidance>
</pv>
<pv name="HBL-040Crm:Cryo-TT-043:P_Limit_LOLO">
<description>Power coupler flange temperature too high</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>contact CRYO on-call and inform SCL on-call, power coupler flange temperature is too low, check heater output, if nominal then coupler flow needs to be adjusted (reduced)</details>
</guidance>
</pv>
<pv name="HBL-040Crm:WtrC-FS-012:Flow_OK_WF">
<description>! Alarm when signal drops from 1 to zero. No Water Flow Antenna 1</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>contact CRYO on-call and inform SCL on-call, assure Flange temperature TT-014 is correct. Risk of Water freeze if no flow and temperature too low</details>
</guidance>
</pv>
<pv name="HBL-040Crm:WtrC-FS-022:Flow_OK_WF">
<description>! Alarm when signal drops from 1 to zero. No Water Flow Antenna 2</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>contact CRYO on-call and inform SCL on-call, assure Flange temperature TT-024 is correct. Risk of Water freeze if no flow and temperature too low</details>
</guidance>
</pv>
<pv name="HBL-040Crm:WtrC-FS-032:Flow_OK_WF">
<description>! Alarm when signal drops from 1 to zero. No Water Flow Antenna 3</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>contact CRYO on-call and inform SCL on-call, assure Flange temperature TT-034 is correct. Risk of Water freeze if no flow and temperature too low</details>
</guidance>
</pv>
<pv name="HBL-040Crm:WtrC-FS-042:Flow_OK_WF">
<description>! Alarm when signal drops from 1 to zero. No Water Flow Antenna 4</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>contact CRYO on-call and inform SCL on-call, assure Flange temperature TT-044 is correct. Risk of Water freeze if no flow and temperature too low</details>
</guidance>
</pv>
</component>
<component name="Cryomodules\HBL-050 Cryomodule">
<pv name="HBL-050Crm:Cryo-LT-001:HIHI">
<description>LT-001 helium level extremely high</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>contact CRYO on-call and inform SCL on-call, Cryomodule liquid level too high (check the other gauge LT-002). Close supply valve CV01, CV02</details>
</guidance>
</pv>
<pv name="HBL-050Crm:Cryo-LT-002:HIHI">
<description>LT-002 helium level extremely high</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>contact CRYO on-call and inform SCL on-call, Cryomodule liquid level too high (check the other gauge LT-001). Close supply valve CV01, CV02</details>
</guidance>
</pv>
<pv name="HBL-050Crm:Cryo-LT-001:HI">
<description>LT-001 helium level high</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>contact CRYO on-call and inform SCL on-call, Cryomodule liquid level high (check the other gauge LT-002). Check level regulation valve settings, if needed: adjust LMN_LO and if necessary: Close supply valve CV01, CV02</details>
</guidance>
</pv>
<pv name="HBL-050Crm:Cryo-LT-002:HI">
<description>LT-002 helium level high</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>contact CRYO on-call and inform SCL on-call, Cryomodule liquid level high (check the other gauge LT-002). Check level regulation valve settings, if needed: adjust LMN_LO and if necessary: Close supply valve CV01, CV02</details>
</guidance>
</pv>
<pv name="HBL-050Crm:Cryo-LT-001:LO">
<description>LT-001 helium level low</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>contact CRYO on-call and inform SCL on-call, Cryomodule liquid level low (check the other gauge LT-001). Check level regulation valve settings, if needed: adjust LMN_HI</details>
</guidance>
</pv>
<pv name="HBL-050Crm:Cryo-LT-002:LO">
<description>LT-002 helium level low</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>contact CRYO on-call and inform SCL on-call, Cryomodule liquid level low (check the other gauge LT-002). Check level regulation valvesettings, if needed: adjust LMN_HI</details>
</guidance>
</pv>
<pv name="HBL-050Crm:Cryo-LT-001:LOLO">
<description>LT-002 helium level extremely low</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>contact CRYO on-call and inform SCL on-call, Cryomodule liquid level too low (check the other gauge LT-001). Check level regulation valve settings, if needed: adjust LMN_HI</details>
</guidance>
</pv>
<pv name="HBL-050Crm:Cryo-LT-002:LOLO">
<description>LT-002 helium level extremely low</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>contact CRYO on-call and inform SCL on-call, Cryomodule liquid level too low (check the other gauge LT-002). Check level regulation valvesettings, if needed: adjust LMN_HI</details>
</guidance>
</pv>
<pv name="HBL-050Crm:Cryo-PT-003:HIHI">
<description>Cavity tanks pressure is too high (typical value is 31mbar in 2K mode and 1050mbar in 4K mode)</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>contact CRYO on-call and inform SCL on-call, Cryomodule bath pressure too high (check the other gauge PT002). Close supply valve CV01, CV02 if necessary</details>
</guidance>
</pv>
<pv name="HBL-050Crm:Cryo-PT-003:Cable_Error">
<description>Cavity tanks Pressure Sensor cables are disconnected</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>contact CRYO on-call and inform SCL on-call, Cryomodule pressure cable seems disconnected (value gets stuck), assign PT002 as measuring device on CV04 and CV-090 </details>
</guidance>
</pv>
<pv name="HBL-050Crm:Cryo-PT-004:HIHI">
<description>Cavity tanks pressure is too high (typical value is 31mbar in 2K mode and 1050mbar in 4K mode)</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>contact CRYO on-call and inform SCL on-call,, Cryomodule bath pressure too high (check the other gauge PT003). Close supply valve CV01, CV02 if necessary</details>
</guidance>
</pv>
<pv name="HBL-050Crm:Cryo-PT-004:Cable_Error">
<description>Cavity tanks Pressure Sensor cables are disconnected</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>contact CRYO on-call and inform SCL on-call, Cryomodule pressure cable seems disconnected (value gets stuck), assign PT003 as measuring device on CV04 and CV-090 </details>
</guidance>
</pv>
<pv name="HBL-050Crm:Cryo-TT-014:P_Limit_HIHI">
<description>Power coupler flange temperature too high</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>contact CRYO on-call and inform SCL on-call, power coupler flange temperature is too high, check heater output, if nominal then coupler flow needs to be adjusted (increased)</details>
</guidance>
</pv>
<pv name="HBL-050Crm:Cryo-TT-014:P_Limit_LO">
<description>Power coupler flange temperature too low</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>contact CRYO on-call and inform SCL on-call, power coupler flange temperature is too low, check heater output, if nominal then coupler flow needs to be adjusted (reduced)</details>
</guidance>
</pv>
<pv name="HBL-050Crm:Cryo-TT-014:P_Limit_LOLO">
<description>Power coupler flange temperature too low</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>contact CRYO on-call and inform SCL on-call, power coupler flange temperature is too low, check heater output, if nominal then coupler flow needs to be adjusted (reduced)</details>
</guidance>
</pv>
<pv name="HBL-050Crm:Cryo-TT-024:P_Limit_HIHI">
<description>Power coupler flange temperature low</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>contact CRYO on-call and inform SCL on-call, power coupler flange temperature is too high, check heater output, if nominal then coupler flow needs to be adjusted (increased)</details>
</guidance>
</pv>
<pv name="HBL-050Crm:Cryo-TT-024:P_Limit_LO">
<description>Power coupler flange temperature too low</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>contact CRYO on-call and inform SCL on-call, power coupler flange temperature is too low, check heater output, if nominal then coupler flow needs to be adjusted (reduced)</details>
</guidance>
</pv>
<pv name="HBL-050Crm:Cryo-TT-024:P_Limit_LOLO">
<description>Power coupler flange temperature too high</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>contact CRYO on-call and inform SCL on-call, power coupler flange temperature is too low, check heater output, if nominal then coupler flow needs to be adjusted (reduced)</details>
</guidance>
</pv>
<pv name="HBL-050Crm:Cryo-TT-034:P_Limit_HIHI">
<description>Power coupler flange temperature low</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>contact CRYO on-call and inform SCL on-call, power coupler flange temperature is too high, check heater output, if nominal then coupler flow needs to be adjusted (increased)</details>
</guidance>
</pv>
<pv name="HBL-050Crm:Cryo-TT-034:P_Limit_LO">
<description>Power coupler flange temperature too low</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>contact CRYO on-call and inform SCL on-call, power coupler flange temperature is too low, check heater output, if nominal then coupler flow needs to be adjusted (reduced)</details>
</guidance>
</pv>
<pv name="HBL-050Crm:Cryo-TT-034:P_Limit_LOLO">
<description>Power coupler flange temperature too high</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>contact CRYO on-call and inform SCL on-call, power coupler flange temperature is too low, check heater output, if nominal then coupler flow needs to be adjusted (reduced)</details>
</guidance>
</pv>
<pv name="HBL-050Crm:Cryo-TT-044:P_Limit_HIHI">
<description>Power coupler flange temperature low</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>contact CRYO on-call and inform SCL on-call, power coupler flange temperature is too high, check heater output, if nominal then coupler flow needs to be adjusted (increased)</details>
</guidance>
</pv>
<pv name="HBL-050Crm:Cryo-TT-044:P_Limit_LO">
<description>Power coupler flange temperature too low</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>contact CRYO on-call and inform SCL on-call, power coupler flange temperature is too low, check heater output, if nominal then coupler flow needs to be adjusted (reduced)</details>
</guidance>
</pv>
<pv name="HBL-050Crm:Cryo-TT-043:P_Limit_LOLO">
<description>Power coupler flange temperature too high</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>contact CRYO on-call and inform SCL on-call, power coupler flange temperature is too low, check heater output, if nominal then coupler flow needs to be adjusted (reduced)</details>
</guidance>
</pv>
<pv name="HBL-050Crm:WtrC-FS-012:Flow_OK_WF">
<description>! Alarm when signal drops from 1 to zero. No Water Flow Antenna 1</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>contact CRYO on-call and inform SCL on-call, assure Flange temperature TT-014 is correct. Risk of Water freeze if no flow and temperature too low</details>
</guidance>
</pv>
<pv name="HBL-050Crm:WtrC-FS-022:Flow_OK_WF">
<description>! Alarm when signal drops from 1 to zero. No Water Flow Antenna 2</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>contact CRYO on-call and inform SCL on-call, assure Flange temperature TT-024 is correct. Risk of Water freeze if no flow and temperature too low</details>
</guidance>
</pv>
<pv name="HBL-050Crm:WtrC-FS-032:Flow_OK_WF">
<description>! Alarm when signal drops from 1 to zero. No Water Flow Antenna 3</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>contact CRYO on-call and inform SCL on-call, assure Flange temperature TT-034 is correct. Risk of Water freeze if no flow and temperature too low</details>
</guidance>
</pv>
<pv name="HBL-050Crm:WtrC-FS-042:Flow_OK_WF">
<description>! Alarm when signal drops from 1 to zero. No Water Flow Antenna 4</description>
<latching>false</latching>
<annunciating>true</annunciating>
<guidance>
<title>[Cryo Operator Action]</title>
<details>contact CRYO on-call and inform SCL on-call, assure Flange temperature TT-044 is correct. Risk of Water freeze if no flow and temperature too low</details>
</guidance>
</pv>
</component>
</component>
</config>